Feature
Notes
Configuration Tables    Wiring    

Slave Zone Controller
DIN Rail Mounting

 

Configuration Tables

Configuration Parameters

Doorway / InSite Code

Label

Description

Units

Default Value

Range

C1
SACT
Sensor Action; sets pre-processing for temperature input and selects external input modes.
0: use local sensor unless remote hardwired sensor connected (see use of nviRemoteTemp for Open systems)
1: average of valid sensor values
2: maximum of valid sensor values
3: minimum of valid sensor values
4: use remote sensor as Occupation input , VFC shorted is occupied
5: use networked temperature (nviRemoteTemp) if valid, else
remote hardwired if valid, else local
6: use remote sensor as Occupancy / standby input, VFC shorted is occupied with close control. open circuit is standby or non-occupied according to zone occupancy pattern
7: use remote sensor as Occupation input, internal occupancy AND external VFC shorted is occupied, external VFC open is non-occupied
8: use remote sensor as Holiday Override input; change to shorted overrides controller to permanent holiday (HDAY= -1 displays as OFF on Zone Controller); change to open circuit clears Holiday mode provided that HDAY is still equal to -1
9: use remote sensor as push-button override input, hold input closed for at least 10seconds. Use of a timed release button is recommended

10: use remote sensor as 'heating enabled', short circuit enables heating, open circuit disables heating. The IDLY timer can also be used to delay the application of the disable signal.
-
0
0 to 9
C2
SCAL
Calibrate sensor value
Deg C
0
-5.0 to 5.0
C3
SPMD
Midpoint of absolute setpoint adjustment range
Deg C
20
2 to 100
C4
SPRG
Range of absolute setpoint adjustment about midpoint
Deg C
5
0.0 to 25.0
C5
SPDB
Setpoint deadband between heating and cooling setpoints. If zero disables cooling
Deg C
0
0.0 to 10.0
C6
SBDB
Additional deadband used in Standby Mode and Optimum off
Deg C
2
0.0 to 10.0
C7
SPTY
Setpoint Type; (only in Slave Zone versions)
0: use local setpoint
1: use remote setpoint, disable local OSS
-
0
0 to 1
C8
TWOP
Two pipe control mode
-
0
0 to 2
C9
XHRS
Extension hours when override pressed outside occupation
Hrs
1
0.0 to 8.0
C10
FRSE
Fabric/Frost rise
Deg C
0
0.0 to 10.0
C11
MIND
Supply minimum demand, used for switching between heating and cooling
%
4
0 to 10
C12
OCCO
When set controller will only run during the occupied period
-
0
0 to 1
C13
HPRD
Heating valve period or minimum on time
secs/10
-
1 to 240
C14
HDLY
Interlock delay:
negative value delays fan after heating starts
positive value cause run on of fan after heating shuts down
Mins
0
-60.0 to 60.0
C15
CPRD
Cooling valve period or minimum on time
secs/10
-
1 to 240
C16
CDLY
Interlock delay
negative value delays fan after cooling starts
positive value cause run on of fan after cooling shuts down
Mins
0
-60.0 to 60.0
C17
FPRD
Fan period, minimum time to change fan speed steps (7R only)
secs/10
-
1 to 240
C18
SPDF
Update default setpoint when setpoint update recieved from MultiMaster controller or Lighting LCD plate
-
0
0 to 1
C19
ALRM
Alarm mode;
0: ignore alarms
1: report alarms
2: report alarms, shut down all outputs (i.e. Submodules) on alarm
3: report alarms, shut down all outputs (i.e. Submodules) on STOP alarm or sensor fail alarm
-
1
0 to 3
C20
ALST
Not used in this application
-
0
0 to 1
C21
MANL
Controller output when in Manual Hand mode
%
0
-100 to 100
C22
HTSC
Heat Source; points Energy Demand to source of Heating energy
-
1
0 to 8255
C23
CLSC
Cool Source; points Energy Demand to source of Cooling energy
-
0
0 to 8255
C24
OCDS
Occupation Destination; points Occupancy Demand at another controller
-
0
0 to 8255
C25
HTCT
Setpoint selector;
0: send Heating Demand signal as % (for VT Circuit Control)
1- 100: send this value as CT setpoint (for CT Circuit Control)
-
0
0 to 100
C26
CLCT
Not used in this application
-
0
0 to 20
C27
IDLY
Interlock Delay, delays activation of input interlock (SACT7)
mins
0
0 to 255
C28
SNDT
Set to enable own temperature reading to be sent to AHU (or Monitor module) as Return temperature
-
0
0 to 1

 

Monitoring Parameters

Doorway / InSite Code

Label

Description

Units

Default Value

Range

I1 (C30)
FRST
Frost or Fabric protection in operation
-
-
0 to 1
I2 (C31)
OCC
Occupied
-
-
0 to 1
I3 (C32)
OSRT
Optimum Start in operation
-
-
0 to 1
I4 (C33)
OOFF
Optimum Off in operation
-
-
0 to 1
I6 (C35)
RLYA
Output channel A
-
-
0 to 1
I7 (C36)
RLYB
Output channel B
-
-
0 to 1
I8 (C37)
RLYC
Output channel C
-
-
0 to 1
W1 (C38)
AUTO
Controller in automatic control
-
-
0 to 1
W2 (C39)
OVRD
Override W1 and W2 used together with Doorway Auto/manual dialog box
-
-
0 to 1
W3 (C40)
LCKB
Lock Buttons: if a MultiMaster controller is present on the system then the controllers buttons will be locked when the MultiMaster is Locked and this parameter is set, (only in slave versions)
-
-
0 to 1
W4 (C41)
MMDE
Master Mode, if set changes a slave controller to a Master in that it can be used to supervise setpoints and times schedules in slave registered to it. (only in Slave Zone versions)
-
-
0 to 1
W5 (C42)
HAND
Manual HAND Mode, when set controller output set by value of MANL
-
-
0 to 1
W7 (C44)
SERV
Set to force controller to send a registration message, clears auomatically
-
-
0 to 1
W8 (C45)
CGST
Configuration mode
-
-
0 to 1
S1* (C50)
ROOM
Controller measured temperature
Deg C
-
5 to 30
S2* (C51)
DMND
Controller output
%
-
-100 to 100
S3 (C52)
REQD
Controller current setpoint
Deg C
-
5 to 30
S4 (C53)
HTOP
Heating output
%
-
0 to 100
S5 (C54)
CLOP
Cooling output
%
-
0 to 100
S6 (C55)
RHUM
Relative Humidity (only valid if networked TRH sensor registered)
%RH
-
0 to 100
S7 (C56)
OPST
Last Optimum Start time
Hrs
-
0 to 24
S8 (C57)
OPOK
Last Optimum Start complete (OK)
Hrs
-
0 to 24
K1 (C60)
SPOC
Occupied setpoint
Deg C
20
10 to 30
K2 (C61)
SPNO
Non-occupied setpoint
Deg C
10
5 to 30
K3 (C62)
SPSV
Supervised setpoint, from master controller
Deg C
0
0 to 30
K4 (C63)
SPRH
Humidity protection setpoint
%RH
0
0 to 95
K5 (C64)
MXOS
Maximum Optimum Start time (hours)
Hrs
6
1 to 24
K6 (C65)
MXOF
Maximum Optimum Stop time (hours)
Hrs
2
0 to 4
K7 (C66)
NOSV
Non Occupied Supervised setpoint
Deg C
0
0 to 30
 
 
Engineering Parameters; only accessible via Doorway and InSite
 
 
 
C90
NOAL
No alarms
-
-
0 to 1
C91
SENF
Sensor fail alarm
-
-
0 to 1
C92
RPVF
Remote PV fail alarm
-
-
0 to 1
C93
CNDF
Condensation alarm
-
-
0 to 1
C94
STOP
Stop alarm received
-
-
0 to 1
C105
MXHT
Limit heat output from heating control loop to the driver
%
100
0 to 100
 
 
* 24 hour plots available for these values by default
 
 
 
 
 