Room Controller
with Fan Speed Override for Fan Coil Modules
Configuration Tables
| Doorway / InSite Code | Label | Description | Units | Default Value | Range |
| C1 | SACT | Sensor Action; sets pre-processing for temperature input and
selects external input modes. 0: use local sensor unless remote hardwired sensor connected (see use of nviRemoteTemp for Open systems) 1: average of valid sensor values 2: maximum of valid sensor values 3: minimum of valid sensor values 4: use remote sensor as Occupation input , VFC shorted is occupied 5: use networked temperature (nviRemoteTemp) if valid, else remote hardwired if valid, else local 6: use remote sensor as Occupancy / standby input, VFC shorted is occupied with close control. open circuit is standby or non-occupied according to zone occupancy pattern 7: use remote sensor as Occupation input, internal occupancy AND external VFC shorted is occupied, external VFC open is non-occupied |
- | 0 | 0 to 7 |
| C2 | SCAL | Calibrate sensor value |
Deg C | 0 | -5 to 5 |
| C3 | SPMD | Midpoint of absolute setpoint adjustment range | Deg C | 20 | 5 to 95 |
| C4 | SPRG | Range of absolute setpoint adjustment about midpoint | Deg C | 5 | 0 to 10 |
| C5 | SPDB | Setpoint deadband between heating and cooling setpoints. If
zero disables cooling |
Deg C | 0 | 0 to 10 |
| C6 | SBDB | Additional deadband used in Standby Mode and Optimum off | Deg C | 2 | 0 to 10 |
| C7 | SPTY | Setpoint Type; (only in Slave Zone versions) 0: use local setpoint 1: use remote setpoint, disable local OSS |
- | 1 | 1 to 3 |
| C8 | MNOP | Minimum output invoked if within 1C of setpoint, used to keep VT circuit running (alternative to using MIND = 0 in VT Controller) | % | 0 | 0 to 10 |
| C9 | XHRS | Extension hours when override pressed outside occupation | Hrs | 1 | 0 to 8 |
| C10 | DEGF | Selects displays in degrees Fahrenheit when set to 1 | - | 0 | 0 to 1 |
| C11 | FRSE | Fabric/Frost rise; added to SPNO to form termination temperature for heating run if temperature dips below SPNO value during non-occupation | Deg C | 0 | 0 to 10 |
| C12 | SPAJ | Setpoint Adjust; range of instantaneous setpoint adjustment using knob | Deg C | 2 | 0 to 10 |
| C13 | SPDF | Setpoint Default; if set to 1 setpoint changes with the knob update the default setpoint (i.e. the setpoint will not revert to a default during the next occupancy period) | Deg C | 0 | 0 to 1 |
| C14 | FNMD | Fan Mode 1: heat only 2: cool only 3: heat and cool 4: fan limited in Heat to speed 1 5: minimum speed 1 fan never off |
- | 3 | 1 to 5 |
| C15 | DISP | Default display 1: Room Temperature 2: Required temperature |
- | 1 | 1 to 2 |
| C16 | ALRM | Alarm mode; 0: ignore alarms 1: report alarms 2: report alarms, shut down all outputs (i.e. Submodules) on alarm 3: report alarms, shut down all outputs (i.e. Submodules) on STOP alarm or sensor fail alarm |
- | 1 | 0 to 3 |
| C17 | ALST | Not used in this application | - | 0 | 0 to 1 |
| C18 | AMON | Displays that alarms are present on the Zone
Display 0: disables alarm monitoring 1: only monitors own alarms 2: only monitors alarms from own domain 3: monitors all alarms |
- | 0 | 0 to 3 |
| C19 | MANL | Controller output when in Manual Hand mode | % | 0 | -100 to 100 |
| C20 | HTSC | Heat Source; points Energy Demand to source of Heating energy | - | 1 | 0 to 8255 |
| C21 | CLSC | Cool Source; points Energy Demand to source of Cooling energy | - | 0 | 0 to 8255 |
| C22 | OCDS | Occupation Destination; points Occupancy Demand at another controller | - | 0 | 0 to 8255 |
| C23 | HTCT | Setpoint selector; 0: send Heating Demand signal as % (for VT Circuit Control) 1- 100: send this value as CT setpoint (for CT Circuit Control) |
- | 0 | 0 to 100 |
| C24 | CLCT | Not used in this application | - | 0 | 0 to 20 |
| C25 | ISS3 | Set to force single domain operation (should only be needed when using issue 3 Floor Controllers) | - | 0 | 0 to 1 |
| C26 | SNDT | Set to enable own temperature reading to be sent to AHU (or Monitor module) as Return temperature | - | 0 | 0 to 1 |
Monitoring Parameters
| Doorway / InSite Code | Label | Description | Units | Default Value | Range |
| I1 (C30) | FRST | Frost or Fabric protection in operation | - | - | 0 to 1 |
| I2 (C31) | OCC | Occupied | - | - | 0 to 1 |
| I3 (C32) | OSRT | Optimum Start in operation | - | - | 0 to 1 |
| I4 (C33) | OOFF | Optimum Off in operation | - | - | 0 to 1 |
| I5 (C34) | COOL | Cooling mode status | - | - | 0 to 1 |
| I6 (C35) | COND | Condensation detected | - | - | 0 to 1 |
| I8 (C37) | XOCC | External Occupation signal | - | - | 0 to 1 |
| W1 (C38) | AUTO | Controller in automatic control | - | - | 0 to 1 |
| W2 (C39) | OVRD | Override W1 and W2 used together with Doorway Auto/manual dialog box | - | - | 0 to 1 |
| W3 (C40) | RLET | Room let | - | - | 0 to 1 |
| W4 (C41) | STBY | Room in standby | - | - | 0 to 1 |
| W5 (C42) | HAND | Manual HAND Mode, when set controller output set by value of MANL | - | - | 0 to 1 |
| W7 (C44) | SERV | Set to force controller to send a registration message, clears auomatically | - | - | 0 to 1 |
| W8 (C45) | CGST | Configuration mode | - | - | 0 to 1 |
| S1* (C50) | ROOM | Controller measured temperature | Deg C | - | 5 to 30 |
| S2* (C51) | DMND | Controller output | % | - | -100 to 100 |
| S3 (C52) | REQD | Controller current setpoint | Deg C | - | 5 to 30 |
| S4 (C53) | HTOP | Heating output | % | - | 0 to 100 |
| S5 (C54) | CLOP | Cooling output | % | - | 0 to 100 |
| S6 (C55) | RHUM | Relative Humidity (only valid if networked TRH sensor registered) | %RH | - | 0 to 100 |
| S7 (C56) | OPST | Last Optimum Start time | Hrs | - | 0 to 24 |
| S8 (C57) | OPOK | Last Optimum Start complete (OK) | Hrs | - | 0 to 24 |
| K1 (C60) | SPOC | Occupied setpoint | Deg C | 20 | 10 to 30 |
| K2 (C61) | SPNO | Non-occupied setpoint | Deg C | 10 | 5 to 30 |
| K3 (C62) | SPSV | Supervised setpoint, from master controller | Deg C | 0 | 0 to 30 |
| K4 (C63) | SPRH | Humidity protection setpoint | %RH | 0 | 0 to 95 |
| K5 (C64) | MXOS | Maximum Optimum Start time (hours) | Hrs | 6 | 1 to 24 |
| K6 (C65) | MXOF | Maximum Optimum Stop time (hours) | Hrs | 2 | 0 to 4 |
| K7 (C66) | NOSV | Non Occupied Supervised setpoint | Deg C | 0 | 0 to 30 |
| K8 (C67) | FSPD | Fan speed status | - | - | 0 to 3 |
| Engineering Parameters; only accessible via Doorway and InSite | |||||
| C90 | NOAL | No alarms | - | - | 0 to 1 |
| C91 | SENF | Sensor fail alarm | - | - | 0 to 1 |
| C92 | RPVF | Remote PV fail alarm | - | - | 0 to 1 |
| C93 | CNDF | Condensation alarm | - | - | 0 to 1 |
| C94 | STOP | Stop alarm received | - | - | 0 to 1 |
| C121 | MZON | Master Zone, if set to zero on a ZSL node using InSite then the slave link is cleared | - | - | 0 to 200 |
| * 24 hour plots available for these values by default Plotting interval and plotted variable changeable via Doorway or InSite |