Feature
|
Configuration Tables |
Wiring |
|
|
|
Zone Controller
Master and Slave types
Configuration Tables
Doorway / InSite Code |
Label |
Description |
Units |
Default Value |
Range |
C1 |
SACT |
Sensor Action; sets pre-processing for temperature input and selects
external input modes.
|
- |
0 |
0 to 9 |
C2 |
SCAL |
Calibrate sensor value
|
Deg C |
0 |
-5.0 to 5.0 |
C3 |
SPMD |
Midpoint of absolute setpoint adjustment range |
Deg C |
20 |
2 to 100 |
C4 |
SPRG |
Range of absolute setpoint adjustment about midpoint |
Deg C |
5 |
0.0 to 25.0 |
C5 |
SPDB |
Setpoint deadband between heating and cooling setpoints. If zero disables
cooling
|
Deg C |
0 |
0.0 to 10.0 |
C6 |
SBDB |
Additional deadband used in Standby Mode and Optimum off |
Deg C |
2 |
0.0 to 10.0 |
C7 |
SLVM |
Slave Mode; (only in Master Zone versions)
|
- |
2 |
1 to 3 |
C7 |
SPTY |
Setpoint Type; (only in Slave Zone versions)
|
- |
1 |
0 to 1 |
C8 |
TWOP |
Used to select two pipe control modes
|
- |
0 |
0 to 2 |
C9 |
XHRS |
Extension hours when override pressed outside occupation |
Hrs |
1 |
0.0 to 8.0 |
C10 |
DEGF |
Selects temperature display
|
- |
0 |
0 to 1 |
C11 |
FRSE |
Fabric/Frost rise |
Deg C |
0 |
0.0 to 10.0 |
C12 |
SPAJ |
Range over which setpoint can be adjusted in one session |
Deg C |
2 |
0.0 to 25.0 |
C13 |
SPDF |
Use default setpoint
|
- |
0 |
0 to 1 |
C14 |
ALRM |
Alarm mode;
|
- |
1 |
0 to 3 |
C15 |
ALST |
Not used in this application |
- |
0 |
0 to 1 |
C16 |
AMON |
Displays that alarms are present on the Zone Display
|
- |
0 |
0 to 3 |
C17 |
MANL |
Controller output when in Manual Hand mode |
% |
0 |
-100 to 100 |
C18 |
HTSC |
Heat Source; points Energy Demand to source of Heating energy |
- |
1 |
0 to 8255 |
C19 |
CLSC |
Cool Source; points Energy Demand to source of Cooling energy |
- |
0 |
0 to 8255 |
C20 |
OCDS |
Occupation Destination; points Occupancy Demand at another controller |
- |
0 |
0 to 8255 |
C21 |
HTCT |
Setpoint selector;
|
- |
0 |
0 to 100 |
C22 |
CLCT |
Not used in this application |
- |
0 |
0 to 20 |
C23 |
IDLY |
Interlock Input Timer |
- |
0 |
0 to 255 mins |
C24 |
SNDT |
Set to enable own temperature reading to be sent to AHU (or Monitor module) as Return temperature |
- |
0 |
0 to 1 |
Monitoring Parameters |
|||||
Doorway / InSite Code |
Label |
Description |
Units |
Default Value |
Range |
I1 (C30) |
FRST |
Frost or Fabric protection in operation |
- |
- |
0 to 1 |
I2 (C31) |
OCC |
Occupied |
- |
- |
0 to 1 |
I3 (C32) |
OSRT |
Optimum Start in operation |
- |
- |
0 to 1 |
I4 (C33) |
OOFF |
Optimum Off in operation |
- |
- |
0 to 1 |
I5 (C34) |
COOL |
Controller in cooling mode |
- |
- |
0 to 1 |
I6 (C35) |
COND |
Condensation detected |
- |
- |
0 to 1 |
I8 (C37) |
XOCC |
External Occupation signal |
- |
- |
0 to 1 |
W1 (C38) |
AUTO |
Controller in automatic control |
- |
- |
0 to 1 |
W2 (C39) |
OVRD |
Override W1 and W2 used together with Doorway Auto/manual dialog box |
- |
- |
0 to 1 |
W3 (C40) |
MOVR |
Patress Version only Master Overide, if set a change in Override on the master will be reflected in all the Slaves within the Master's group (only in Master Zone versions) |
- |
- |
0 to 1 |
W3 (C40) |
LCKB |
DIN version only Lock Buttons: if a MultiMaster controller is present on the system then the controllers buttons will be locked when the MultiMaster is Locked and this parameter is set, (only in slave versions) |
- |
- |
0 to 1 |
W4 (C41) |
MHOL |
Patrass Version only Master Holiday, if set changes to number of Holiday days will be sent to all Zone Controllers (only in Master Zone versions) |
- |
- |
0 to 1 |
W4 (C41) |
MMDE |
DIN version only Master Mode, if set changes a slave controller to a Master in that it can be used to supervise setpoints and times schedules in slave registered to it. (only in Slave Zone versions) |
- |
- |
0 to 1 |
W5 (C42) |
HAND |
Manual HAND Mode, when set controller output set by value of MANL |
- |
- |
0 to 1 |
W6 (C43) |
GTON |
Global Trim: activates receipt of a global setpoint trim, used with MultiMaster controllers. |
- |
- |
0 to 1 |
W7 (C44) |
SERV |
Set to force controller to send a registration message, clears auomatically |
- |
- |
0 to 1 |
W8 (C45) |
CGST |
Configuration mode |
- |
- |
0 to 1 |
S1* (C50) |
ROOM |
Controller measured temperature |
Deg C |
- |
5 to 30 |
S2* (C51) |
DMND |
Controller output |
% |
- |
-100 to 100 |
S3 (C52) |
REQD |
Controller current setpoint |
Deg C |
- |
5 to 30 |
S4 (C53) |
HTOP |
Heating output
|
% |
- |
0 to 100 |
S5 (C54) |
CLOP |
Cooling output |
% |
- |
0 to 100 |
S6 (C55) |
RHUM |
Relative Humidity (only valid if networked TRH sensor registered) |
%RH |
- |
0 to 100 |
S7 (C56) |
OPST |
Last Optimum Start time |
Hrs |
- |
0 to 24 |
S8 (C57) |
OPOK |
Last Optimum Start complete (OK) |
Hrs |
- |
0 to 24 |
K1 (C60) |
SPOC |
Occupied setpoint |
Deg C |
20 |
5.0 to 95.0 |
K2 (C61) |
SPNO |
Non-occupied setpoint
|
Deg C |
10 |
5.0 to 95.0 |
K3 (C62) |
SPSV |
Supervised setpoint, from master controller
|
Deg C |
0 |
0.0 to 95.0 |
K4 (C63) |
SPRH |
Humidity protection setpoint
|
%RH |
0 |
0 to 95 |
K5 (C64) |
MXOS |
Maximum Optimum Start time (hours)
|
Hrs |
6 |
0.1 to 24.0 |
K6 (C65) |
MXOF |
Maximum Optimum Stop time (hours)
|
Hrs |
2 |
0 to 4.0 |
K7 (C66) |
NOSV |
Non Occupied Supervised setpoint |
Deg C |
0 |
0.0 to 95.0 |
|
|
|
Engineering Parameters; only accessible via Doorway and InSite |
|
|
|
C90 |
NOAL |
No alarms |
- |
- |
0 to 1 |
C91 |
SENF |
Sensor fail alarm |
- |
- |
0 to 1 |
C92 |
RPVF |
Remote PV fail alarm |
- |
- |
0 to 1 |
C93 |
CNDF |
Condensation alarm |
- |
- |
0 to 1 |
C94 |
STOP |
Stop alarm received |
- |
- |
0 to 1 |
C121 |
MZON |
Master Zone, if set to zero on a ZSL node using InSite then the slave link is cleared |
- |
- |
0 to 200 |
|
|
|
* 24 hour plots available for these values by default |
|
|
|
|
|
|
Plotting interval and plotted variable changeable via Doorway or InSite |
|
|
|