Feature
Notes

Configuration Tables

Wiring

 

 


Zone Controller
Master and Slave type
s

Configuration Tables

Doorway / InSite Code

Label

Description

Units

Default Value

Range

C1
SACT
Sensor Action; sets pre-processing for temperature input and selects external input modes.
0: use local sensor unless remote hardwired sensor connected (see use of nviRemoteTemp for Open systems)
1: average of valid sensor values
2: maximum of valid sensor values
3: minimum of valid sensor values
4: use remote sensor as Occupation input , VFC shorted is occupied
5: use networked temperature (nviRemoteTemp) if valid, else
remote hardwired if valid, else local
6: use remote sensor as Occupancy / standby input, VFC shorted is occupied with close control. open circuit is standby or non-occupied according to zone occupancy pattern
7: use remote sensor as Occupation input, internal occupancy AND external VFC shorted is occupied, external VFC open is non-occupied. Response is delayed by IDLY mins if set
8:use remote sensor as External input to select Holiday operation. Can be wired to Security system to force Holiday operation when building is unoccupied.

9:use remote sensor input as remote occupation override.
-
0
0 to 9
C2
SCAL
Calibrate sensor value
Deg C
0
-5.0 to 5.0
C3
SPMD
Midpoint of absolute setpoint adjustment range
Deg C
20
2 to 100
C4
SPRG
Range of absolute setpoint adjustment about midpoint
Deg C
5
0.0 to 25.0
C5
SPDB
Setpoint deadband between heating and cooling setpoints. If zero disables cooling
Deg C
0
0.0 to 10.0
C6
SBDB
Additional deadband used in Standby Mode and Optimum off
Deg C
2
0.0 to 10.0
C7
SLVM
Slave Mode; (only in Master Zone versions)
1: send Occupation times to Slave Zones
2: send Setpoint to Slave Zones
3: send both Times and setpoint to Slave
-
2
1 to 3
C7
SPTY
Setpoint Type; (only in Slave Zone versions)
0: use local setpoint
1: use remote setpoint, disable local OSS
-
1
0 to 1
C8
TWOP
Used to select two pipe control modes
0: normal operation
1:mixed actuator control modre
2:inteligent actuator mode
-
0
0 to 2
C9
XHRS
Extension hours when override pressed outside occupation
Hrs
1
0.0 to 8.0
C10
DEGF
Selects temperature display
0: Display temperature in Deg C
1: Display temperature in Deg F
-
0
0 to 1
C11
FRSE
Fabric/Frost rise
Deg C
0
0.0 to 10.0
C12
SPAJ
Range over which setpoint can be adjusted in one session
Deg C
2
0.0 to 25.0
C13
SPDF
Use default setpoint
0: Setpoint reverts to default at start of each occupancy
period
1: Setpoint stays at last value set i.e. does not revert to
default at start of occupancy period
-
0
0 to 1
C14
ALRM
Alarm mode;
0: ignore alarms
1: report alarms
2: report alarms, shut down all outputs (i.e. Submodules) on alarm
3: report alarms, shut down all outputs (i.e. Submodules) on STOP alarm or sensor fail alarm
-
1
0 to 3
C15
ALST
Not used in this application
-
0
0 to 1
C16
AMON
Displays that alarms are present on the Zone Display
0: disables alarm monitoring
1: only monitors own alarms
2: only monitors alarms from own domain
3: monitors all alarms
-
0
0 to 3
C17
MANL
Controller output when in Manual Hand mode
%
0
-100 to 100
C18
HTSC
Heat Source; points Energy Demand to source of Heating energy
-
1
0 to 8255
C19
CLSC
Cool Source; points Energy Demand to source of Cooling energy
-
0
0 to 8255
C20
OCDS
Occupation Destination; points Occupancy Demand at another controller
-
0
0 to 8255
C21
HTCT
Setpoint selector;
0: send Heating Demand signal as % (for VT Circuit Control)
1- 100: send this value as CT setpoint (for CT Circuit Control)
-
0
0 to 100
C22
CLCT
Not used in this application
-
0
0 to 20
C23
IDLY
Interlock Input Timer
-
0
0 to 255 mins
C24
SNDT
Set to enable own temperature reading to be sent to AHU (or Monitor module) as Return temperature
-
0
0 to 1

 

 

Monitoring Parameters

Doorway / InSite Code

Label

Description

Units

Default Value

Range

I1 (C30)
FRST
Frost or Fabric protection in operation
-
-
0 to 1
I2 (C31)
OCC
Occupied
-
-
0 to 1
I3 (C32)
OSRT
Optimum Start in operation
-
-
0 to 1
I4 (C33)
OOFF
Optimum Off in operation
-
-
0 to 1
I5 (C34)
COOL
Controller in cooling mode
-
-
0 to 1
I6 (C35)
COND
Condensation detected
-
-
0 to 1
I8 (C37)
XOCC
External Occupation signal
-
-
0 to 1
W1 (C38)
AUTO
Controller in automatic control
-
-
0 to 1
W2 (C39)
OVRD
Override W1 and W2 used together with Doorway Auto/manual dialog box
-
-
0 to 1
W3 (C40)
MOVR
Patress Version only Master Overide, if set a change in Override on the master will be reflected in all the Slaves within the Master's group (only in Master Zone versions)
-
-
0 to 1
W3 (C40)
LCKB
DIN version only Lock Buttons: if a MultiMaster controller is present on the system then the controllers buttons will be locked when the MultiMaster is Locked and this parameter is set, (only in slave versions)
-
-
0 to 1
W4 (C41)
MHOL
Patrass Version only Master Holiday, if set changes to number of Holiday days will be sent to all Zone Controllers (only in Master Zone versions)
-
-
0 to 1
W4 (C41)
MMDE
DIN version only Master Mode, if set changes a slave controller to a Master in that it can be used to supervise setpoints and times schedules in slave registered to it. (only in Slave Zone versions)
-
-
0 to 1
W5 (C42)
HAND
Manual HAND Mode, when set controller output set by value of MANL
-
-
0 to 1
W6 (C43)
GTON
Global Trim: activates receipt of a global setpoint trim, used with MultiMaster controllers.
-
-
0 to 1
W7 (C44)
SERV
Set to force controller to send a registration message, clears auomatically
-
-
0 to 1
W8 (C45)
CGST
Configuration mode
-
-
0 to 1
S1* (C50)
ROOM
Controller measured temperature
Deg C
-
5 to 30
S2* (C51)
DMND
Controller output
%
-
-100 to 100
S3 (C52)
REQD
Controller current setpoint
Deg C
-
5 to 30
S4 (C53)
HTOP
Heating output
%
-
0 to 100
S5 (C54)
CLOP
Cooling output
%
-
0 to 100
S6 (C55)
RHUM
Relative Humidity (only valid if networked TRH sensor registered)
%RH
-
0 to 100
S7 (C56)
OPST
Last Optimum Start time
Hrs
-
0 to 24
S8 (C57)
OPOK
Last Optimum Start complete (OK)
Hrs
-
0 to 24
K1 (C60)
SPOC
Occupied setpoint
Deg C
20
5.0 to 95.0
K2 (C61)
SPNO
Non-occupied setpoint
Deg C
10
5.0 to 95.0
K3 (C62)
SPSV
Supervised setpoint, from master controller
Deg C
0
0.0 to 95.0
K4 (C63)
SPRH
Humidity protection setpoint
%RH
0
0 to 95
K5 (C64)
MXOS
Maximum Optimum Start time (hours)
Hrs
6
0.1 to 24.0
K6 (C65)
MXOF
Maximum Optimum Stop time (hours)
Hrs
2
0 to 4.0
K7 (C66)
NOSV
Non Occupied Supervised setpoint
Deg C
0
0.0 to 95.0
 
 
Engineering Parameters; only accessible via Doorway and InSite
 
 
 
C90
NOAL
No alarms
-
-
0 to 1
C91
SENF
Sensor fail alarm
-
-
0 to 1
C92
RPVF
Remote PV fail alarm
-
-
0 to 1
C93
CNDF
Condensation alarm
-
-
0 to 1
C94
STOP
Stop alarm received
-
-
0 to 1
C121
MZON
Master Zone, if set to zero on a ZSL node using InSite then the slave link is cleared
-
-
0 to 200
 
 