Feature
|
Configuration Tables |
Wiring |
|
|
Feature Notes |
|
Pump Changeover Submodule |
|
PCO / DIN / 3T / ... |
|
Main FeaturesControls a Pair of Pumps or Fans providing Auto Changeover and Duty RotationCan use Contactor status signals or Flow Proving Switches (single or dual)Hours Run logged for each PumpPump Fail alarm outputPump Exercising Routine |
![]() |

Input 3-4 |
Pump 1 flow status |
Input 5-6 |
Pump 2 flow status |
NOAL |
No Alarms. |
FLFA |
Flow Failed pump A output 1 |
FLFB |
Flow Failed pump B output 2 |
DPMF |
Dual Pump Failure. |
STOP |
System STOP alarm received. |
FMD = 1 |
Standby pump output remains on. |
FMD = 2 |
Standby pump output remains on. |
FMD = 3 |
Standby pump output turned off. |
ACLR = 1 |
Pumps reset automatically after Occupancy; if |
ACLR = 0 |
Pumps remain latched in Failure Mode until |
ACLR = 1 |
Changeover Submodule sends special STOP alarm on
DPMF condition. |
ACLR = 1 |
DHW outputs are not held off while alarms |
ACLR = 0 |
DHW outputs are not held off while alarms |
ACLR = 1 |
In Secondary Circuit Controller: ILKP = 1 |
Option |
Output A |
Output B |
Output Spare |
Registered to BLR |
Registered to ZON/ZSL/DHW |
/ 001 |
Pump A |
Pump B |
Alarm Sounder |
Primary Pumps |
|
/ 002 |
Pump A |
Pump B |
Alarm Sounder |
VT Pumps |
|
/ 003 |
Pump A |
Pump B |
Alarm Sounder |
DHW Pumps |
|
/ 004 |
Pump A |
Pump B |
Alarm Sounder |
Heating Optimum Start Switch |
|
/ 005 |
Pump A |
Pump B |
Alarm Sounder |
Heating Occupation Switch |
|
/ 006 |
Pump A |
Pump B |
Alarm Sounder |
Heating Demand |
|
/ 007 |
Pump A |
Pump B |
Alarm Sounder |
Cooling Optimum Start Switch |
|
/ 008 |
Pump A |
Pump B |
Alarm Sounder |
Cooling Occupation Switch |
|
/ 009 |
Pump A |
Pump B |
Alarm Sounder |
Cooling Demand |
Input Configuration |
|
Input 3-4 status 1 |
VFC status pump A |
Input 5-6 status 2 |
VFC status pump B |