Feature
Notes

Configuration Tables

Wiring

 

 

Pump Changeover Submodule

with 3 x Triac Outputs

Configuration Tables

Doorway / InSite Code

Label

Description

Units

Default Value

Range

C1
ALRM
Alarm Mode
0: Ignore alarms
1: Report all alarms to Doorway/InSite,
2: Report all alarms, shut down on STOP alarm, send special STOP alarm to boiler on DPMF alarm
-
0
0 to 2
C2
ALST
Alarm report sense
0: Alarm if input = 0 (contact open), pump running if input = 1 (closed)
1: Alarm if input = 1 (contact closed), pump running if input = 0 (open)
-
0
0 to 1
C3
FMDE
Failure Mode
1: Both pumps remain enabled
2: Last pump remains enabled
3: Both pumps disabled
-
2
1 to 3
C4
DLAY
Delay to wait for proof of flow
Secs
10
1 to 250
C5
MXHR
Maximum hours run before duty pump changeover
Hrs
24
1 to 200
C6
MNON
Minimum on time
Mins
5
0 to 200
C7
MXDY
Maximum days off time for pump exercise
Days
7
0 to 10
C8
NPMP
Number of pumps controlled
-
2
1 to 2
C9
TYPE
Output type (for SeaChange use only)
-
-
1 to 12

Monitoring Parameters

Doorway / InSite Code

Label

Description

Units

Default Value

Range

I1 (C30)
FL A
Flow status pump A
-
-
0 to 1
I2 (C31)
FL B
Flow status pump B
-
-
0 to 1
I3 (C32)
EN A
Do not adjust (for smartkontrols use only)
-
-
-
I4 (C33)
EN B
Do not adjust (for smartkontrols use only)
-
-
-
I5 (C34)
FAIL
Single or Dual Pump Failure
-
-
0 to 1
I6 (C35)
PMPA
Triac output 1 status Pump A
-
-
0 to 1
I7 (C36)
PMPB
Triac output 2 status Pump B
-
-
0 to 1
I8 (C37)
ALRS
Triac output spare status Alarm Sounder
-
-
0 to 1
W1 (C38)
AUTO
Automatic/Manual Status
-
-
0 to 1
W2 (C39)
OVRD
Override
-
-
0 to 1
W3 (C40)
RSTA
Reset hours run pump A
-
-
0 to 1
W4 (C41)
RSTB
Reset hours run pump B
-
-
0 to 1
W5 (C42)
RNON
Enable pump run on
-
1
0 to 1
W6 (C43)
ACLR
Automatically clear alarms
-
1
0 to 1
W7 (C44)
SERV
Service Pin Message (to Doorway and InSite, self resetting)
-
-
0 to 1
S1* (C50)
HRSA
Hours run pump A
Hrs
-
-
S2* (C51)
HRSB
Hours run pump B
Hrs
-
-
S3 (C52)
MXDM
Control demand from parent module
%
-
-100 to 100
 
 
Engineering Parameters; only accessible via Doorway and InSite
 
 
 
C90
NOAL
No Alarms; all alarms cleared when set to 1
-
-
0 or 1
C91
FLFA
Flow Failed pump A (when set to 1)
-
-
0 or 1
C92
FLFB
Flow Failed pump B (when set to 1)
-
-
0 or 1
C93
DPMF
Dual Pump Failure (when set to 1)
-
-
0 or 1
C94
STOP
STOP alarm received (when set to 1)
-
-
0 or 1
 
 
* 24 hour plots available for these values by default
 
 
 
 
 