Doorway / InSite Code |
Label |
Description |
Units |
Default Value |
Range |
C1 |
MNFA |
Minimum Fresh Air |
% |
10 |
0 to 100 |
C2 |
NOWS |
Minimum Wind Speed for Wind Direction Indication to be valid
|
m/sec |
1 |
0 to 25 |
C3 |
MXWS |
Maximum Wind Speed (Window Shut) |
m/sec |
0 |
0 to 25 |
C4 |
MNWS |
Minimum Wind Speed (Window open) |
m/sec |
0 |
0 to 15 |
C5 |
WNWD |
Window Direction
|
Degrees |
0 |
0 to 360 |
C6 |
DDEV |
Wind Direction Deviation, the deviation in Wind Direction
from dead down wind when the Window will be forced shut. |
Degrees |
0 |
0 to 360 |
C7 |
INMD |
Input Mode use of terminals 'input a' :
0: additional temperature input for max,min,average use SACT
1: external input (short = occupied) AND internal occ
2: external input OR internal occ
3: external input signal only
4: Alarm input
5: Alarm if input does not match Pump/Fan State
Note modes 2 & 3 are only suitable for use with Actuator in Control
Mode 2, small plant driver mode. |
- |
0 |
0 to 5 |
C8 |
MIND |
Minimum demand, used for defining Occupancy switching
for the Fan/Pump:
0: will run pump/fan throughout Occupancy
>0: will require minimum demand level before pump/fan will run
|
- |
4 |
0 to 10 |
C9 |
OCCO |
When set controller will only run during the occupied
period |
- |
0 |
0 to 1 |
C10 |
HPRD |
Heating valve period or minimum on time
|
secs/10 |
Depends on type |
1 to 60 |
C11 |
HDLY |
Interlock delay:
negative value delays fan (or pump) after heating starts
positive value cause run on of fan after heating shuts down
|
mins |
0 |
-30 to 30 |
C12 |
CPRD |
Cooling valve period or minimum on time
|
secs/10 |
Depends on type |
1 to 60 |
C13 |
CDLY |
Interlock delay:
negative value delays fan (or pump) after cooling starts
positive value cause run on of fan after cooling shuts down
|
mins |
0 |
-30 to 30 |
C14 |
FPRD |
Fan period, minimum time to change fan speed steps
(6R + 7R version only) |
secs/10 |
12 |
1 to 60 |
C15 |
CALC |
Calculation Mode:
0: Multiply the Factors
1: use Loweset Factor
|
- |
0 |
0 to 1 |
C16 |
MANL |
Manual level , from Doorway
|
% |
0 |
-100 to 100 |
C17 |
CMDE |
Control Mode:
0: driver only inputs used for monitoring or alarm
1: closed loop control, input b primary sensor
2: on/off control, heating or cooling demand will be 100% when controller
is 'occupied'. Sensor inputs used for monitoring or alarm functions |
- |
0 |
0 to 2 |
C18 |
ALRM |
Alarm mode:
0: ignore alarms
1: report alarms
2: report alarms, shut down all outputs on local alarm
3: report alarms, shut down all outputs on STOP alarm or local alarm
4: report alarms, shut down all outputs on STOP alarm only
|
- |
0 |
0 to 4 |
C19 |
ALST |
Sets alarm state
|
- |
0 |
0 to 1 |
C20 |
MXVA |
Maximum Voltage output a (for AOP types only) |
V |
10 |
0 to 10 |
C21 |
MNVA |
Minimum Voltage output a (for AOP types only) |
V |
0 |
0 to 10 |
C22 |
MXVB |
Maximum Voltage output b (for AOP types only) |
V |
10 |
0 to 10 |
C23 |
MNVB |
Minimum Voltage output b (for AOP types only) |
V |
0 |
0 to 10 |
Doorway / InSite Code |
Label |
Description |
Units |
Default Value |
Range |
I1 (C30)
|
FRST
|
Frost Protection Mode (SPNO violated)
|
- |
- |
0 to 1 |
I2 (C31)
|
OCCD |
Occupied
|
- |
- |
0 to 1 |
I3 (C32)
|
WMUP |
Not used in this version |
- |
- |
0 to 1 |
I4 (C33)
|
EXIP |
External Input State
|
- |
- |
0 to 1 |
I5 (C34)
|
COOL |
Cooling mode
|
- |
- |
0 to 1 |
I6 (C35)
|
RLYA
|
Triac A Status (3T versions only) |
- |
- |
0 to 1 |
I7 (C36)
|
RLYB
|
Triac B Status (3T versions only) |
- |
- |
0 to 1 |
I8 (C37)
|
RLYC
|
Triac C Status (3T versions only) |
- |
- |
0 to 1 |
W1 (C38)
|
AUTO
|
Automatic/Manual Status
|
- |
- |
0 to 1 |
W2 (C39)
|
OVRD
|
Override
|
- |
- |
0 to 1 |
W5 (C42) |
HAND
|
Manual Hand; use with MANL to set output level
|
- |
0
|
0 to 1 |
W6 (C43) |
POT |
Selects whether the board mounted potentiometer option is fitted or
not |
- |
0
|
0 to 1 |
W7 (C44)
|
SERV
|
Service Pin Msg (to Doorway +InSite, self resetting)
|
- |
- |
0 to 1 |
S1* (C50) |
TEMP |
Measured temperature
|
Deg C
|
- |
0 to 95 |
S2* (C51)
|
HCOP |
Heat cool output to drivers (cooling negative)
|
%
|
- |
-100 to 100 |
S3 (C52)
|
REQD |
Current setpoint
|
Deg C
|
- |
5 to 90 |
S4 (C53)
|
HDMD |
Heat demand from loop or from Zone Controller
|
%
|
- |
0 to 100 |
S5 (C54) |
CDMD |
Cool demand from loop or from Zone Controller
|
%
|
- |
0 to 100 |
S6 (C55)
|
FDMD
|
Fan demand |
%
|
- |
0 to 100 |
S7 (C56)
|
OSFR |
Outside Temperature Override Factor |
%
|
- |
0 to 100 |
S8 (C57) |
WSFR |
Wind Speed Override Factor |
%
|
- |
0 to 100 |
S9 (C58) |
WDFR |
Wind Direction Override Factor |
%
|
- |
0 to 100 |
S10 (C59) |
FACT |
Overall Override Factor |
%
|
- |
0 to 100 |
K1 (C60)
|
MXWS |
Maximum Wind Speed, speed at which Window is Overriden shut |
m/sec |
0 |
0 to 25 |
K2 (C61) |
MNWS |
Minimum Wind Speed, speed at which window is still allowed to be 100%
open |
m/sec |
0 |
0 to 25 |
K3 (C62)
|
|
Reserved for supervised setpoint from master controller
|
- |
- |
- |
K4 (C63) |
WNWD |
Window Direction, compass bearing looking directly out of the window
|
Degrees |
0 |
0 to 360 |
K5 (C64) |
DDEV |
Wind Direction deviation, deviation from dead down wind where window
must be shut |
Degrees |
0 |
0 to 160 |
K6 (C65)
|
NOWS |
No Wind, below this Wind Speed the Wind Direction is ignored |
m/sec |
1 |
0 to 25 |
K7 (C66) |
MNFA |
Minimum Fresh Air setting for the Window opening |
% |
10 |
0 to 100 |
K8 (C67) |
OUTT |
Outside Temperature Top limit, at which the window can be fully open |
Deg C |
0 |
0 to 25 |
K9 (C68) |
OUTB |
Outside Temperature Bottom limit, at or below which the window will
be shut |
Deg C |
0 |
0 to 25 |
|
|
Engineering Parameters; only accessible via Doorway and InSite |
|
|
|
C180
|
DI A
|
Input 3-4 digital status
|
- |
- |
0 or 1 |
C181
|
DI B
|
Input 5-6 digital status
|
- |
- |
0 or 1 |
|
|
* 24 hour plots available for these values by default |
|
|
|
|
|
Plotting interval and plotted variable changeable via Doorway or InSite |
|
|
|