Pump Speed Control Submodule

with 2 x 0-10V DC Outputs

Feature
Notes
Configuration Tables Wiring    

Configuration Parameters

Doorway / InSite Code

Label

Description

Units

Default Value

Range

C1
SPOC
Occupied setpoint
-
50
Re-scalable
C2
MXPV
Maximum Sensor Scaling (value @10V)
-
100
Re-scalable
C3
MNPV
Minimum Sensor Scaling (value@0V)
-
0
Re-scalable
C4
DPPV
Decimal places for engineering scaling
-
1
0 to 4
C5
MXSP
Maximum setpoint value
-
100
Re-scalable
C6
MNSP
Minimum setpoint value
-
0
Re-scalable
C7
MNOP
Minimum Output
%
5
0 to 100
C8
INVL
Invert control sense:
0: increasing error reduces output
1: increasing error increases output
-
0
0 to 1
C9
ELAG
Percentage lag or lead for second output
%
0
-50 to 50
C10
HPRD
Stroke time or minimum on time for driver
Secs/10
-
1 to 60
C11
HDLY
Interlock delay:
Negative value delays fan (or pump) after heating starts
Positive value cause run on of fan after heating shuts down
Mins
0
-30 to 30
C12
CPRD
Stroke time or minimum on time for driver
Secs/10
-
1 to 60
C13
CDLY
Interlock delay:
Negative value delays fan (or pump) after cooling starts
Positive value cause run on of fan after cooling shuts down
Mins
0
-30 to 30
C14
MANL
Manual level , from Doorway
%
0
0 to 100
C15
TYPE
Pump(set) switching type:
(when regd to BLR/DIN/STD or HIL):
1: Primary Pump(s)
2: VT Pump(s)

(when regd to special BLR/DIN/DHW)
3: DHW Pump(s)

(when regd to VTC, VTU or CTU)
4: Heating Optimum Start
5: Heating Occupation only
6: Heating Demand >5%

(when regd to CLR, VTU or CTU)
7: Cooling Optimum Start
8: Cooling Occupation only
9: Cooling Demand >5%
-
1
1 to 9
C16
ACNL
Analogue Channel select:
1: select channel b terminals 5+6
2: select channel a terminals 3+4
-
0
0 to 2
C17
ALRM
Alarm mode:
0: ignore alarms
1: report alarms
2: report alarms, shut down all outputs on alarm
3: report alarms, shut down all outputs on STOP alarm or sensor fail alarm
-
0
0 to 3
C18
ALST
Not used in this application
-
1
0 to 1
C19
MXVA
Maximum Voltage output a
Vdc
10
0 to 10
C20
MNVA
Minimum Voltage output a
Vdc
0
0 to 10
C20
MXVB
Maximum Voltage output b
Vdc
10
0 to 10
C21
MNVB
Minimum Voltage output b
Vdc
0
0 to 10

Monitoring Parameters

Doorway / InSite Code

Label

Description

Units

Default Value

Range

I2 (C31)
OCCD
Occupied
-
-
0 to 1
I3 (C32)
WMUP
Optimum Start
-
-
0 to 1
I6 (C35)
RLYA
Triac A Status (special order 3T versions only)
-
-
0 to 1
I7 (C36)
RLYB
Triac B Status (special order 3T versions only)
-
-
0 to 1
I8 (C37)
RLYC
Triac C Status (special order 3T versions only)
-
-
0 to 1
W1 (C38)
AUTO
Automatic/Manual Status
-
-
0 to 1
W2 (C39)
OVRD
Override
-
-
0 to 1
W5 (C42)
HAND
Manual Hand; use with MANL to set output level
-
0
0 to 1
W6 (C43)
POT
not used in this application
-
1
0 to 1
W7 (C44)
SERV
Service Pin Message (to Doorway and InSite, self resetting)
-
-
0 to 1
S1* (C50)
PVKP
Pressure reading
-
-
Re-scalable
S2* (C51)
HCOP
Control output to drivers
%
-
-100 to 100
S3 (C52)
RQKP
Controller current setpoint
-
-
Re-scalable
S4 (C53)
DMND
Speed
%
-
0 to 100
K1 (C60)
SPOC
Occupied setpoint
-
50
Re-scalable
K2 (C61)
MXPV
Maximum Sensor Scaling (value @10V)
-
100
Re-scalable
K3 (C62)
MNPV
Minimum Sensor Scaling (value@0V)
-
0
Re-scalable
K4 (C63)
DPPV
Decimal places for engineering scaling
-
1
0 to 4
 
 
Engineering Parameters; only accessible via Doorway and InSite
 
 
 
C90
NOAL
No Alarms; all alarms cleared when set to 1
-
-
0 or 1
C91
SENF
Sensor Failed (when set to 1)
-
-
0 or 1
C92
EXTN
Volt-Free Contact alarm (when set to 1)
-
-
0 or 1
C93
STOP
STOP alarm received (when set to 1)
-
-
0 or 1
 
 
* 24 hour plots available for these values by default
 
 
 
 
 
Plotting interval and plotted variable changeable via Doorway or InSite
 
 
 