Configuration Parameters
|
Doorway / InSite Code
|
Label
|
Description
|
Units
|
Default Value
|
Range
|
C1
|
SPNO
|
Non Occupied setpoint
|
Deg C
|
30
|
10 to 50
|
C2
|
SACT
|
Sensor action
0: Use temp b sensor for control and optionally use temp
a sensor for monitoring or VFC using INMD
1: Use average of valid sensor values (INMD = 0)
2: Use maximum of valid sensor values (INMD = 0)
3: Use minimum of valid sensor values (INMD = 0)
|
-
|
0
|
0 to 3
|
C3
|
MAXH
|
Maximum Heating Setpoint (rescaled from demand)
|
Deg C
|
30
|
0 to 90
|
C4
|
MINH
|
Minimum Heating Setpoint (rescaled from demand)
|
Deg C
|
20
|
0 to 90
|
C5
|
MAXC
|
Maximum Cooling Setpoint (rescaled from demand)
|
Deg C
|
18
|
2 to 30
|
C6
|
MINC
|
Minimum Cooling Setpoint (rescaled from demand)
|
Deg C
|
10
|
2 to 30
|
C7
|
INMD
|
Input Mode for input terminals 3 and 4 temp a
0: Additional temperature input for max, min, ave using SACT
1: External occupation (input linked = Occupied) AND
with internal Occupation
2: External occupation (input linked = Occupied) OR
with internal Occupation
3: External Occupation signal only
4: Alarm input
5: Pump alarm
|
-
|
0
|
0 to 5
|
C8
|
MIND
|
Minimum Demand for occupation output to operate
|
%
|
5
|
0 to 100
|
C9
|
OCCO
|
Occupied Only (select Optimum Start or Occupation Switch operation)
0: Occupancy starts at Optimum Start time
1: Occupancy starts at Occupation Start time
|
-
|
0
|
0 to 1
|
C10
|
HPRD
|
Heating Driver Stroke/Minimum On Time
|
Secs/10
|
18
|
1 to 240
|
C11
|
HDLY
|
Heating Interlock Delay
Negative value opens valve before pump starts
Positive value runs pump on after valve shuts down
|
Mins
|
5
|
-60 to 60
|
C12
|
CPRD
|
Cooling Driver Stroke/Minimum On Time
|
Secs/10
|
18
|
1 to 240
|
C13
|
CDLY
|
Cooling Interlock Delay
Negative value opens valve before pump starts
Positive value runs pump on after valve shuts down
|
Mins
|
5
|
-60 to 60
|
C14
|
FPRD
|
Fan Period, minimum time to change fan speed steps
|
Secs/10
|
12
|
1 to 240
|
C15
|
FRPT
|
Frost Protection Mode
0: No action
1: Open valve 50%
2: Open valve and run pump
|
-
|
2
|
0 to 2
|
C16
|
MANL
|
Manual Level, set by Doorway or InSite
|
%
|
0
|
-100 to 100
|
C17
|
CMDE
|
Control Mode
0: Control loop disabled, demand passed direct to outputs
1: Normal control
2: On/ Off control
|
-
|
1
|
0 to 2
|
C18
|
ALRM
|
Alarm mode
0: Ignore alarms
1: Report all alarms to Doorway/InSite,
no control action, no flashing Temp indicator
2: Report all alarms, shut down all outputs on local alarm
3: Report all alarms, shut down on STOP alarm or local alarm
4: Report all alarms, shut down on STOP alarm only
|
-
|
0
|
0 to 4
|
C19
|
ALST
|
Alarm report sense
0: Alarm if input = 0 (contact open), healthy if input = 1 (closed)
1: Alarm if input = 1 (contact closed), healthy if input = 0 (open)
|
-
|
0
|
0 to 1
|
C20
|
MXVA
|
Maximum Voltage output a (for AOP types only)
|
Vdc
|
10
|
0 to 10
|
C21
|
MNVA
|
Maximum Voltage output a (for AOP types only)
|
Vdc
|
0
|
0 to 10
|
C22
|
MXVB
|
Maximum Voltage output b (for AOP types only)
|
Vdc
|
10
|
0 to 10
|
C23
|
MNVB
|
Maximum Voltage output b (for AOP types only)
|
Vdc
|
0
|
0 to 10
|
Monitoring Parameters
|
Doorway / InSite Code
|
Label
|
Description
|
Units
|
Default Value
|
Range
|
I1 (C30)
|
PURG
|
Night Purge activated from interlocked AHU
|
-
|
-
|
0 to 1
|
I2 (C31)
|
OCCD
|
Occupied
|
-
|
-
|
0 to 1
|
I3 (C32)
|
WMUP
|
Optimum Start
|
-
|
-
|
0 to 1
|
I4 (C33)
|
EXTI
|
External Input
|
-
|
-
|
0 to 1
|
I5 (C34)
|
COOL
|
Cooling Mode
|
-
|
-
|
0 to 1
|
I6 (C35)
|
RLYA
|
Triac A Status
|
-
|
-
|
0 to 1
|
I7 (C36)
|
RLYB
|
Triac B Status
|
-
|
-
|
0 to 1
|
I8 (C37)
|
RLYC
|
Triac C Status
|
-
|
-
|
0 to 1
|
W1 (C38)
|
AUTO
|
Automatic/Manual Status
|
-
|
-
|
0 to 1
|
W2 (C39)
|
OVRD
|
Override
|
-
|
-
|
0 to 1
|
W5 (C42)
|
HAND
|
Manual Hand; use with MANL to set output level
|
-
|
0
|
0 to 1
|
W6 (C43)
|
POT
|
not used in this application
|
-
|
1
|
0 to 1
|
W7 (C44)
|
SERV
|
Service Pin Message (to Doorway and InSite, self resetting)
|
-
|
-
|
0 to 1
|
S1* (C50)
|
TEMP
|
Control Temperature
|
Deg C
|
-
|
-
|
S2* (C51)
|
DMND
|
Heating or Cooling output to drivers
|
%
|
-
|
-100 to 100
|
S3 (C52)
|
REQD
|
Controller current setpoint
|
Deg C
|
-
|
-
|
S4 (C53)
|
HDMD
|
Heating driver output
|
%
|
-
|
0 to 100
|
S5 (C54)
|
CDMD
|
Cooling driver output
|
%
|
-
|
0 to 100
|
S6 (C55)
|
FDMD
|
Fan / pump driver output
|
%
|
-
|
0 to 100
|
S7 (C56)
|
AIRQ
|
Air Quality
|
%
|
-
|
0 to 100
|
K1 (C60)
|
MAXH
|
Maximum Heating Setpoint (rescaled from demand)
|
Deg C
|
30
|
0 to 90
|
K2 (C61)
|
MINH
|
Minimum Heating Setpoint (rescaled from demand)
|
Deg C
|
20
|
0 to 90
|
K4 (C63)
|
MAXC
|
Maximum Cooling Setpoint (rescaled from demand)
|
Deg C
|
18
|
2 to 30
|
K5 (C64)
|
MINC
|
Minimum Cooling Setpoint (rescaled from demand)
|
Deg C
|
10
|
2 to 30
|
K6 (C65)
|
NOSH
|
Non Occupied Setpoint Heating
|
Deg C
|
10
|
0 to 90
|
K7 (C66)
|
NOSC
|
Non Occupied Setpoint Cooling
|
Deg C
|
35
|
1 to 90
|
K8 (C67)
|
MXAQ
|
Air Quality value for Maximum output override
|
%
|
0
|
0 to 100
|
K9 (C68)
|
MNAQ
|
Air Quality value for Minimum output override
|
%
|
0
|
0 to 100
|
|
|
Engineering Parameters; only accessible via Doorway and InSite
|
|
|
|
C90
|
NOAL
|
No Alarms; all alarms cleared when set to 1
|
-
|
-
|
0 or 1
|
C91
|
SENF
|
Sensor Failed (when set to 1)
|
-
|
-
|
0 or 1
|
C92
|
EXTN
|
Volt-Free Contact alarm (when set to 1)
|
-
|
-
|
0 or 1
|
C93
|
PMPF
|
Pump Failed (when set to 1)
|
-
|
-
|
0 or 1
|
C94
|
STOP
|
STOP alarm received (when set to 1)
|
-
|
-
|
0 or 1
|
C122
|
MODO
|
Modulate Open only
Some window controllers only modulate on opening signals and shut completely
on reciept of a closing signal. This parameter when set modifies the action
of the raise lower driver to match this need.
|
%
|
0
|
0 to 1
|
C123
|
ADDI
|
Address Index
selects one of the eight possible AHU Night Purge interlocks, AHU number
given on C124
|
-
|
1
|
1 to 8
|
C124
|
AHU
|
AHU number
defines which AHU to interlock for NIght Purge
|
-
|
0
|
0 to 50
|
C180
|
DI A
|
Input 3-4 digital status
|
-
|
-
|
0 or 1
|
C181
|
DI B
|
Input 5-6 digital status
|
-
|
-
|
0 or 1
|
|
|
* 24 hour plots available for these values by default
|
|
|
|
|
|
Plotting interval and plotted variable changeable via Doorway or InSite
|
|
|
|