Doorway / InSite Code
|
Label
|
Description
|
Units
|
Default Value
|
Range
|
C1
|
SPNO
|
Non Occupied setpoint
|
Deg C
|
30
|
10 to 50
|
C2
|
SACT
|
Sensor action
0: Use temp b sensor for control and optionally use temp
a sensor for monitoring or VFC using INMD
1: Use average of valid sensor values (INMD = 0)
2: Use maximum of valid sensor values (INMD = 0)
3: Use minimum of valid sensor values (INMD = 0)
|
-
|
0
|
0 to 3
|
C3
|
MAXH
|
Maximum Heating Setpoint (rescaled from demand)
|
Deg C
|
30
|
0 to 90
|
C4
|
MINH
|
Minimum Heating Setpoint (rescaled from demand)
|
Deg C
|
20
|
0 to 90
|
C5
|
MAXC
|
Maximum Cooling Setpoint (rescaled from demand)
|
Deg C
|
18
|
2 to 30
|
C6
|
MINC
|
Minimum Cooling Setpoint (rescaled from demand)
|
Deg C
|
10
|
2 to 30
|
C7
|
INMD
|
Input Mode for input terminals 3 and 4 temp a
0: Additional temperature input for max, min, ave using SACT
1: External occupation (input linked = Occupied) AND
with internal Occupation
2: External occupation (input linked = Occupied) OR
with internal Occupation
3: External Occupation signal only
4: Alarm input
5: Pump alarm
|
-
|
0
|
0 to 5
|
C8
|
MIND
|
Minimum Demand for occupation output to operate
|
%
|
5
|
0 to 100
|
C9
|
OCCO
|
Occupied Only (select Optimum Start or Occupation Switch operation)
0: Occupancy starts at Optimum Start time
1: Occupancy starts at Occupation Start time
|
-
|
0
|
0 to 1
|
C10
|
HPRD
|
Heating Driver Stroke/Minimum On Time
|
Secs/10
|
18
|
1 to 240
|
C11
|
HDLY
|
Heating Interlock Delay
Negative value opens valve before pump starts
Positive value runs pump on after valve shuts down
|
Mins
|
5
|
-60 to 60
|
C12
|
CPRD
|
Cooling Driver Stroke/Minimum On Time
|
Secs/10
|
18
|
1 to 240
|
C13
|
CDLY
|
Cooling Interlock Delay
Negative value opens valve before pump starts
Positive value runs pump on after valve shuts down
|
Mins
|
5
|
-60 to 60
|
C14
|
FPRD
|
Fan Period, minimum time to change fan speed steps
|
Secs/10
|
12
|
1 to 240
|
C15
|
FRPT
|
Frost Protection Mode
0: No action
1: Open valve 50%
2: Open valve and run pump
|
-
|
2
|
0 to 2
|
C16
|
MANL
|
Manual Level, set by Doorway or InSite
|
%
|
0
|
-100 to 100
|
C17
|
CMDE
|
Control Mode
0: Control loop disabled, demand passed direct to outputs
1: Normal control
2: On/ Off control
|
-
|
1
|
0 to 2
|
C18
|
* TWOP
|
Two Pipe Heat Pump Mode
0: Normal Mode
1: Two Pipe Heating & Cooling Mode
When the parameter TWOP, the controller will only allow heating
output if the flow temperature is above 20degC and only allow cooling if it is
below 20degC. Since the same control valve is used for both heating and cooling, the
internal driver needs to be set to redirect the cooling demands to the
heating driver. Special universal drivers can be set during
production on request
* This feature is provided on a special version of ACT
module (available on request). The standard ACT module does not
provide this feature
|
-
|
0
|
0 to 2
|
C19
|
WMDE
|
Window Mode
0: Normal Mode
1: Window Mode
When Window Mode is set and a Raise Lower Driver is used the automatic
driving to the end stops to correct the position calculation is disabled.
|
-
|
1
|
0 to 2
|
C20
|
ALRM
|
Alarm mode
0: Ignore alarms
1: Report all alarms to Doorway/InSite,
no control action, no flashing Temp indicator
2: Report all alarms, shut down all outputs on local alarm
3: Report all alarms, shut down on STOP alarm or local alarm
4: Report all alarms, shut down on STOP alarm only
|
-
|
0
|
0 to 4
|
C21
|
ALST
|
Alarm report sense
0: Alarm if input = 0 (contact open), healthy if input = 1 (closed)
1: Alarm if input = 1 (contact closed), healthy if input = 0 (open)
|
-
|
0
|
0 to 1
|
C22
|
MXVA
|
Maximum Voltage output a (for AOP types only)
|
Vdc
|
10
|
0 to 10
|
C23
|
MNVA
|
Maximum Voltage output a (for AOP types only)
|
Vdc
|
0
|
0 to 10
|
C24
|
MXVB
|
Maximum Voltage output b (for AOP types only)
|
Vdc
|
10
|
0 to 10
|
C25
|
MNVB
|
Maximum Voltage output b (for AOP types only)
|
Vdc
|
0
|
0 to 10
|
Doorway / InSite Code
|
Label
|
Description
|
Units
|
Default Value
|
Range
|
I1 (C30)
|
FRST
|
Frost Protection Mode (SPNO violated)
|
-
|
-
|
0 to 1
|
I2 (C31)
|
OCCD
|
Occupied
|
-
|
-
|
0 to 1
|
I3 (C32)
|
WMUP
|
Optimum Start
|
-
|
-
|
0 to 1
|
I4 (C33)
|
EXTI
|
External Input
|
-
|
-
|
0 to 1
|
I5 (C34)
|
COOL
|
Cooling Mode
|
-
|
-
|
0 to 1
|
I6 (C35)
|
RLYA
|
Triac A Status
|
-
|
-
|
0 to 1
|
I7 (C36)
|
RLYB
|
Triac B Status
|
-
|
-
|
0 to 1
|
I8 (C37)
|
RLYC
|
Triac C Status
|
-
|
-
|
0 to 1
|
W1 (C38)
|
AUTO
|
Automatic/Manual Status
|
-
|
-
|
0 to 1
|
W2 (C39)
|
OVRD
|
Override
|
-
|
-
|
0 to 1
|
W5 (C42)
|
HAND
|
Manual Hand; use with MANL to set output level
|
-
|
0
|
0 to 1
|
W6 (C43)
|
POT
|
not used in this application
|
-
|
1
|
0 to 1
|
W7 (C44)
|
SERV
|
Service Pin Message (to Doorway and InSite, self resetting)
|
-
|
-
|
0 to 1
|
S1* (C50)
|
TEMP
|
Control Temperature
|
Deg C
|
-
|
-
|
S2* (C51)
|
DMND
|
Heating or Cooling output to drivers
|
%
|
-
|
-100 to 100
|
S3 (C52)
|
REQD
|
Controller current setpoint
|
Deg C
|
-
|
-
|
S4 (C53)
|
HDMD
|
Heating driver output
|
%
|
-
|
0 to 100
|
S5 (C54)
|
CDMD
|
Cooling driver output
|
%
|
-
|
0 to 100
|
S6 (C55)
|
FDMD
|
Fan / pump driver output
|
%
|
-
|
0 to 100
|
K1 (C60)
|
MAXH
|
Maximum Heating Setpoint (rescaled from demand)
|
Deg C
|
30
|
0 to 90
|
K2 (C61)
|
MINH
|
Minimum Heating Setpoint (rescaled from demand)
|
Deg C
|
20
|
0 to 90
|
K4 (C63)
|
MAXC
|
Maximum Cooling Setpoint (rescaled from demand)
|
Deg C
|
18
|
2 to 30
|
K5 (C64)
|
MINC
|
Minimum Cooling Setpoint (rescaled from demand)
|
Deg C
|
10
|
2 to 30
|
K6 (C65)
|
NOSH
|
Non Occupied Setpoint Heating
|
Deg C
|
10
|
0 to 90
|
K7 (C66)
|
NOSC
|
Non Occupied Setpoint Cooling
|
Deg C
|
35
|
1 to 90
|
|
|
Engineering Parameters; only accessible via Doorway and InSite
|
|
|
|
C90
|
NOAL
|
No Alarms; all alarms cleared when set to 1
|
-
|
-
|
0 or 1
|
C91
|
SENF
|
Sensor Failed (when set to 1)
|
-
|
-
|
0 or 1
|
C92
|
EXTN
|
Volt-Free Contact alarm (when set to 1)
|
-
|
-
|
0 or 1
|
C93
|
PMPF
|
Pump Failed (when set to 1)
|
-
|
-
|
0 or 1
|
C94
|
STOP
|
STOP alarm received (when set to 1)
|
-
|
-
|
0 or 1
|
C180
|
DI A
|
Input 3-4 digital status
|
-
|
-
|
0 or 1
|
C181
|
DI B
|
Input 5-6 digital status
|
-
|
-
|
0 or 1
|
|
|
* 24 hour plots available for these values by default
|
|
|
|
|
|
Plotting interval and plotted variable changeable via Doorway or InSite
|
|
|
|