Data sheet |
|
NAT Actuator Submodule for Natural Ventilation |
|
ACT / DIN / NAT / 3T / ... (Triac output)
ACT / DIN / NAT / AOP / ... (0-10V)
|
|
Main Features
Automatic Control of Atrium Windows, Roof Lights or Dampers in
Naturally Ventilated buildings
Night purge interlock with one or more AHU plants
Control based on Cooling Demand, Wind Speed and Wind Direction and
Outside Temperature
Works in conjunction with a Sontay Weather Station and SeaChange Wind Interface
Module
|
|
Summary Features
General
The SeaChange
natural ventilation sub modules are used to provide automatic Control of
Atrium Windows, Roof Lights or Dampers in Naturally Ventilated
applications. They can be used to drive Raise/Lower type actuator motors or 0-10V DC actuator
motors depending on the application and the design criteria.
The natural ventilation version of the Actuator sub module
is generally similar to the standard version, however, the built-in control
strategies have been extended to provide additional features and functionality
for naturally ventilated buildings.
Control functions
The Window Controller controls the opening
of automated windows and dampers in Naturally Ventilated buildings. The controller
registers as an Actuator submodule and can be used with AHU, Secondary Cooling,
Zone controllers as the parent module.
The window opening can be modified by Wind Speed and Direction
as measured by a SeaChange Wind Interface module. Further settings allow the
window opening to be limited by the Outside temperature.
When used on 3T hardware only one window actuator can be
controlled per module with the raise/lower driver, whereas if Analogue output
hardware is used then two diametrically opposed windows can be controlled from
one Actuator submodule.
The module receives cooling demands and occupancy from it's
parent module, while occupied the module will open the window as defined by
the Minimum Fresh Air setting MNFA, unless the cooling demand is greater
in which case the window will open an amount equal to the cooling demand. The
maximum window opening can be overridden based on Wind Speed, Direction and
Outside temperature as detailed below.
Depending
on your application, the Actuators can be registered to either a zone
controller or a cooling secondary circuit module.
Where cooling demands in the building are generated
multiple Zones
and AHUsin the appropriate area of the building, a cooling secondary circuit
controller is used to coordinate the cooling demands. The Actuator submodule can be
setup to modify the window opening based on demand, wind speed, wind direction
and outside temperature.
Wind Speed Override
Two configuration parameters define the Wind speed operation.
MNWS Minimum Wind Speed defines the lower wind speed limit below
which no wind override occurs
MXWS Maximum Wind Speed defines the upper wind speed limit at which the
Window will be overriden closed
Between these limits the maximum window opening will be progressivly changed
from 100% to 0%. The incoming demand signal will be rescaled to match the modified
maximum opening, so if the demand was 50% and the Wind Speed was dictating a
maximum opening of 60% then the window would be opened 30% (50% of 60%).
Setting both parameters to zero will disable this feature.
Wind Direction Override (NAT version only)
Three parameters define the Wind Direction override.
NOWS No Wind Speed, for wind speeds below this
value the direction of the wind is ignored
WNWD Window Direction, this is the compass bearing measured from inside
the building looking perpendicularly out of the window.
Compass Point |
Bearing
|
North |
0 |
North East |
45 |
East |
90 |
South East |
135 |
South |
180 |
South West |
225 |
West |
270
|
North West |
315 |
North |
360 |
DDEV Direction Deviation. The window will be
allowed to open to maximum when the wind is from the direction diametrically
opposed to the Window Direction. Wind direction is always specified as the direction
which the wind is coming from, so with a northerly wind, a south facing window
is on the lee side of the bulding and can be opened. The Direction Deviation
parameter specifies how much the wind direction needs to change from the downwind
condition before the window needs to be shut. The diagram plots maximum window
opening against wind direction deviation for a number of settings of DDEV
Direction Deviation. It can be seen from this that if the DDEV is greater
than 180 the window can be allowed to open a small amount even when the wind
is blowing directly onto it.

Setting the DDEV Direction Deviation parameter to
zero will disable the Wind Direction Override.
Outside Temperature Override
(NAT version only)
This override prevents or limits window opening when
the outside temperature is below or between preset temperature limits.
OUTT Outside Top limit, if the Outside temperature
falls below this setting then the Maximum window opening will be progressivly
reduced until
OUTS Outside Shut limit is reached where the Maximum window opening will
be at 0%
If both these parameters are set to zero then this feature
will be disabled.
Calculation Mode
(NAT version only)
The factors calculated for each of the Window opening
restrictions described above may be combined in one of two ways as defined by
the CALC configuration variable.
CALC=0 Factors Multiplied
The indivudual factors from each calculation are multiplied
together so for example if the Wind Speed factor is 80%, the Wind Direction
Factor 50% and the Outside Temperature factor is 60% then the resulting re-scale
applied to the window opening would be 0.8 *0.5 *0.6* 100 or 24%, in this case
100% cooling demand would open the window by just 24%
CALC=1 Minimum
In this case the lowest factor would be used to rescale
the demand, with the same figures as above the Wind Direction factor of 50%
is the lowest so 100% cooling demand would be re-scaled to 50%.
Each of the individual factors can be viewed on the sensor
page, OSFR Outside Factor, WSFR Wind Speed Factor and WDFR
Wind Direction Factor. The sensor FACT Resultant Factor displays the
result of the combining calculation.
Options and Product Codes
ACT / DIN / NAT / 3T / [driver option]
Driver options
Cooling
Option |
Output A |
Output B |
Output C |
/ 201 |
Time Proportional |
Not used |
Occupation or Optimum start switch |
/ 205 |
Window/Damper Open |
Window/Damper Close |
Occupation or Optimum start switch |
ACT / DIN / NAT / AOP / [driver option]
Driver options
Cooling
Option |
Output A |
Output B |
/ 821 |
0-100% Demand = 0-10V dc |
Occupation or Optimum Start Switch * |
| |
Input Configuration (3T and AOP) |
Input 3-4 input a |
Temperature sensor (optional) or VFC status / alarm / occupancy |
Input 5-6 input b |
Temperature sensor (optional) |
SC Controls Ltd
PO Box313
Wadhurst
East Sussex
TN5 6JL
phone 08707 606040
fax 08707 606041
e-mail seachange@sccontrols.co.uk
http:// www.seachange.co.uk