Feature
Notes

Configuration Tables

Wiring

 

 

Intelligent Actuator Submodule
with network powered valve actuator

 

ACT / VLV/ LPV

 

Configuration Parameters

Doorway / InSite Code

Label

Description

Units

Default Value

Range

C1
CPSN
Current Valve position (read only)
%
-
0 to 100
C2
RPSN
Required Valve position
If this value is changed the actuator will change to HAND mode and will motor to the selected position.
HAND mode will continue until either the power to the unit is cycled or the HAND setting is cleared from InSite
%
-
0 to 100
C3
DMND
Heating or cooling demand signal from Zone Controller
%
-
0 to 100
C4
HAND
When set to 1 the actuator will follow the position set on RPSN and will ignore control demands from the system.
(Setting to zero also clears any residual values on the special two pipe demand input which otherwise would take precidence over the Heating and Cooling demands)
-
0
0 to 1
C5
COOL
When set the actuator responds to Cooling demands, otherwise it responds to Heating demands
-
0
0 to 1
C6
REVA
Reverse acting
when set the actuator is reverse acting, at 100% the actuator stem is fully retracted.
-
0
0 to 1
C7
PERD
Actuation Period
This is in the factory by on production 90nm actuators 63 seconds, 180 and 280 actuators 150 seconds
-
to suit type
50 to 200 seconds
C8
SERV
when set causes the actuator to broadcast an identifying service message
-
0
0 to 1
C9
DRMX
Demand Rescale Maximum
allow the control demand to be re-scaled before being passed to the actuator. This setting must be larger than DRMN
-
100
0 to 100
C10
DRMN
Demand Rescale Minimum
allow the control demand to be re-scaled before being passed to the actuator. This setting must be smaller than DRMX
-
0
0 to 100
C11
ENDS
Drive to EndStop
0: Completed
1: Fully Retract
2: Fully Extend
-
0
0 to 2
C12
VLST
Valve Status
0: Stopped
1: Closing
2: Opening
-
read only
0 to 2