Configuration Parameters
|
Doorway / InSite Code
|
Label
|
Description
|
Units
|
Default Value
|
Range
|
C1
|
CPSN
|
Current Valve position (read only)
|
%
|
-
|
0 to 100
|
C2
|
RPSN
|
Required Valve position
If this value is changed the actuator will change to HAND mode and will
motor to the selected position.
HAND mode will continue until either the power to the unit is cycled or
the HAND setting is cleared from InSite
|
%
|
-
|
0 to 100
|
C3
|
DMND
|
Heating or cooling demand signal from Zone Controller
|
%
|
-
|
0 to 100
|
C4
|
HAND
|
When set to 1 the actuator will follow the position set on RPSN and
will ignore control demands from the system.
(Setting to zero also clears any residual values on the special two
pipe demand input which otherwise would take precidence over the Heating
and Cooling demands)
|
-
|
0
|
0 to 1
|
C5
|
COOL
|
When set the actuator responds to Cooling demands, otherwise it responds
to Heating demands
|
-
|
0
|
0 to 1
|
C6
|
REVA
|
Reverse acting
when set the actuator is reverse acting, at 100% the actuator stem is
fully retracted.
|
-
|
0
|
0 to 1
|
C7
|
PERD
|
Actuation Period
This is in the factory by on production 90nm actuators 63 seconds, 180
and 280 actuators 150 seconds
|
-
|
to suit type
|
50 to 200 seconds
|
C8
|
SERV
|
when set causes the actuator to broadcast an identifying service message
|
-
|
0
|
0 to 1
|
C9
|
DRMX
|
Demand Rescale Maximum
allow the control demand to be re-scaled before being passed to the actuator.
This setting must be larger than DRMN
|
-
|
100
|
0 to 100
|
C10
|
DRMN
|
Demand Rescale Minimum
allow the control demand to be re-scaled before being passed to the actuator.
This setting must be smaller than DRMX
|
-
|
0
|
0 to 100
|
C11
|
ENDS
|
Drive to EndStop
0: Completed
1: Fully Retract
2: Fully Extend
|
-
|
0
|
0 to 2
|
C12
|
VLST
|
Valve Status
0: Stopped
1: Closing
2: Opening
|
-
|
read only
|
0 to 2
|