Feature
Notes

Data Sheet

Wiring

 

Feature Notes

 

Temperature Sensors
with Thermistor Elements

 

SEN/.../.../...

 

Main Features

Temperature Sensors for all common applications

Close tolerance Thermistor Elements (+/- 0.2 Deg C accuracy within range 0 to 70 Deg C)

Sensor Products

Plant Room Sensors

Immersion Temperature Sensor IP65 rated.

SEN / PR / IMM / 001
Measures the temperature of liquids in pipework and vessels.
Direct mounting into a brass or stainless steel pocket (separately available as an accessory).
Enclosure
Dimensions: 57mm x 90mm diameter
Material: Flame retardant ABS
IP rated 67
Ambient: -10 to 60 Deg C
Probe
Houses sensor element
Dimensions: 150mm x 6mm diameter
Material: Brass
Connection: 2 way terminal block, polarity independant

Mounting

If the sensor is to be mounted outside, it is recommended that the unit be mounted with the cable entry at the bottom. In addition, if the cable is fed from above the sensor we also recommend that a rain loop is placed in the cable before entry into the sensor.
Remove the front cover by twisting the lid and separating from the main body to make the electrical connections. Fix the sensor in to the pocket and secure with the grub screw provided with the pocket.
Feed the cable through the waterproof gland and terminate the cores at the terminal block. Leave some slack inside the unit, tighten the cable gland onto the cable to ensure watertightness. Replace the lid after the electrical connections have been made.

 

Plant Room Sensors

Clamp-On Temperature Sensor IP65

SEN / PR / CLP / 001
Measures pipe surface temperature.
Includes steel band strap for clamping onto pipes (may require longer strap for larger vessels).
Enclosure
Dimensions: 57mm x 90mm diameter
Material: Flame retardant ABS
IP rated 67
Ambient: -10 to 60 Deg C
Probe
Houses sensor element
Material: Brass
Connection: 2 way terminal block, polarity independant
Cable: 1.5m of PTFE 2 core screened cable

Mounting

If the sensor is to be mounted outside, it is recommended that the unit be mounted with the two cable entries at the sides. In addition, if the cables are fed from above the IP65 housing we also recommend that a rain loop is placed in the cable before entry into the sensor.
Remove the front cover by twisting the lid and separating from the main body. Using the base of the housing as a template mark the hole centres. Drill two pilot holes at 85mm centres in the surface on which the sensor is to be mounted, and fix the sensor with appropriate screws. The housing is designed to make it easy for an electric screwdriver to be used if desired.
Feed the cables through the waterproof glands and terminate the cores at the terminal blocks. Leaving some slack inside the units, tighten the cable glands onto the cables to ensure watertightness. Replace the lid after the electrical connections have been made.

 

Plant Room Sensors

Outside Air Temperature Sensor IP65

SEN / PR / OAT / 001
Measures outside air temperature.
Sensing element is contained within 10mm diameter brass cap, located externally in the shadow of the lid to avoid solar gain in most applications.
Enclosure
Dimensions: 57mm x 90mm diameter
Material: Flame retardant ABS
IP rated 67
Ambient: -10 to 60 Deg C
10mm diameter brass cap houses sensor element
Connection: 2 way terminal block, polarity independant

Mounting

Outside air sensors should always be situated in a sheltered position on a north facing wall.
Avoid mounting the sensor in direct sunlight. It is recommended that the unit be mounted with the cable entry at the bottom. In addition, if the cable is fed from above the sensor we also recommend that a rain loop is placed in the cable before entry into the sensor.
Remove the front cover by twisting the lid and separating from the main body. Using the base of the housing as a template mark the hole centres. Drill two pilot holes at 85mm centres in the surface on which the sensor is to be mounted, and fix the sensor with appropriate screws. The housing is designed to make it easy for an electric screwdriver to be used if desired.
Feed the cable through the waterproof gland and terminate the cores at the terminal block. Leaving some slack inside the units, tighten the cable gland onto the cable to ensure watertightness. Replace the lid after the electrical connections have been made.

 

Plant Room Sensors

Duct Temperature Sensor

SEN / PR / DCT / 001
Measures air temperature in ducts.

Sensing element is contained within 150mm long brass probe with holes to allow air to flow directly over the element.

A neoprene gasket is supplied to ensure a good seal onto the duct.

Enclosure
Dimensions: 57mm x 90mm diameter
Material: Flame retardant ABS
IP rated 67
Ambient: -10 to 80 Deg C

Probe
Houses sensor element
Dimensions: 150mm x 6mm diameter
Material: Brass
Connection: 2 way terminal block, polarity independant

Mounting

If the sensor enclosure is to be mounted outside, it is recommended that the unit be mounted with the cable entry at the bottom. In addition, if the cable is fed from above the sensor we also recommend that a rain loop is placed in the cable before entry into the sensor.
Remove the front cover by twisting the lid and separating from the main body. Using the base of the housing as a template mark the hole centres. Drill two pilot holes at 85mm centres in the surface on which the sensor is to be mounted. Apply the gasket provided to the base of the housing. Align the holes in the probe so that they point into the airflow, not at right-angles to it. Press onto the side of the ductwork to form a seal between the sensor and the duct. Fix the sensor with appropriate screws. The housing is designed to make it easy for an electric screwdriver to be used if desired.
Feed the cable through the waterproof gland and terminate the cores at the terminal block. Leaving some slack inside the units, tighten the cable gland onto the cable to ensure watertightness. Replace the lid after the electrical connections have been made.

 

Accessories

Pocket for Immersion Temperature Sensor

SEN / BP
Brass Pocket for Immersion Temperature Sensor
SEN / SS
Stainless Steel Pocket for Immersion Temperature Sensor
Pockets are designed to accept 150mm x 6mm diameter probes, which are locked in position by a grub screw.
Brass Pocket
Material: Brass
Range: -20 to 110 Deg C
Max Pressure: 10 bar
(out to in)
Stainless Steel Pocket
Material: Stainless Steel 316
Range: -20 to 400 Deg C
Max Pressure: 16bar
(out to in)

Mounting

Pockets can be installed in any system that is constructed from compatible materials whose operating pressures are within the specified ranges and fit into a 1/2" BSPT boss using a thread-seal compound.
In pipework systems, fit into an elbow such that the pocket runs down the centre of the pipe, against the direction of flow

 

Pattress Mount Sensors

Room Temperature Sensor

SEN / PTR / ROM / 001
Measures air temperature in indoor spaces.
Sensing element is mounted in a white moulded enclosure for surface mounting on a wall or pattress box.
Enclosure
Material: Flame retardant ABS
Dimensions: 83mm x 83mm x 27mm.
Ambient Range -10 to 60 Deg C
Connections are made via a terminal block, polarity independant.

Mounting

Remove the tamperproof screw at the bottom of the housing and gently pull outwards from the base. Using the base of the housing as a template mark the hole centres and fix to the wall with suitable screws. Alternatively, the housing can be mounted on to a pattress box.

 

Pattress Mount Sensors

Room Temperature Sensor with Setpoint Adjust

SEN / PTR / ROM / 002
Room Temperature Sensor with Setpoint Adjustment Potentiometer
Enclosure
As standard room sensor
Setpoint Adjustment: 1 to 11k ohm pot

Mounting

Remove the tamperproof screw at the bottom of the housing and gently pull outwards from the base. Using the base of the housing as a template mark the hole centres and fix to the wall with suitable screws. Alternatively, the housing can be mounted on to a pattress box. See SEN/PTR/ROM/OO1 for fixing details.
Connections
TB1: Terminals 3 and 4: Setpoint resistance
TB1: Terminals 5 and 6: Temperature sensor

 

Pattress Mount Sensors

Room Temperature Sensor with Setpoint Adjust and Fan Switch

SEN / PTR / ROM / 003
Room Temperature Sensor with Setpoint Adjust and Fan speed Adjust Switch
Enclosure
As standard room sensor
Setpoint Adjustment: 1 to 11k ohm pot
Fanspeed Adjustment: 5 position slide switch setting resistance

Mounting

Remove the tamperproof screw at the bottom of the housing and gently pull outwards from the base. Using the base of the housing as a template mark the hole centres and fix to the wall with suitable screws. Alternatively, the housing can be mounted on to a pattress box. See SEN/PTR/ROM/OO1 for fixing details.
Connections
TB1: Terminals 1 and 2: Fan Speed resistance
TB1: Terminals 3 and 4: Setpoint resistance
TB1: Terminals 5 and 6: Temperature sensor

 

Pattress Mount Sensors

Room Temperature Sensor with Setpoint Adjust and Override Switch

Picture currently not available.
SEN / PTR / ROM / 004
Room Temperature Sensor with Setpoint Adjust and Occupation Switch
Enclosure
As standard room sensor
Setpoint Adjustment: 1 to 11k ohm pot
Occupation Switch (/004): Rocker switch for on/off operation
NB Option switches MUST NOT be used to switch 230Vac

Mounting

Remove the tamperproof screw at the bottom of the housing and gently pull outwards from the base. Using the base of the housing as a template mark the hole centres and fix to the wall with suitable screws. Alternatively, the housing can be mounted on to a pattress box. See SEN/PTR/ROM/OO1 for fixing details.
Connections
TB1: Terminals 3 and 4: Setpoint resistance
TB1: Terminals 5 and 6: Temperature sensor
TB2: Terminal 14: Occupation switch NO
TB2: Terminal 15: Occupation switch Common
TB2: Terminal 16: Occupation switch NC

 

Pattress Mount Sensors

Indoor Black Bulb Sensor

SEN / PTR / BLK / 001
Black Bulb Sensor
Measures black bulb air temperature in indoor spaces.
Sensing element is mounted in a white moulded enclosure for surface mounting on a wall or pattress box.
Enclosure
Material: Flame retardant ABS
Dimensions: 83mm x 83mm x 27mm.
Ambient Range -10 to 60 Deg C
Connections are made via a terminal block, polarity independant.

Mounting

Remove the tamperproof screw at the bottom of the housing and gently pull outwards from the base. Using the base of the housing as a template mark the hole centres and fix to the wall with suitable screws. Alternatively, the housing can be mounted on to a pattress box. See SEN/PTR/ROM/OO1 for fixing details.

 

Pattress Mount Sensors

Room Temperature Sensors - Special Finishes

The room temperature sensors are also available in a number of alternative finishes for special requirements. These finishes are not stocked but are available on special request. Some samples are shown alongside.
 
Enclosure
Material: Flame retardant ABS
Dimensions: 83mm x 83mm x 27mm.
Ambient Range -10 to 60 Deg C
Connections are made via a terminal block, polarity independent.

Mounting

Remove the tamperproof screw at the bottom of the housing and gently pull outwards from the base. Using the base of the housing as a template mark the hole centres and fix to the wall with suitable screws. Alternatively, the housing can be mounted on to a pattress box. See SEN/PTR/ROM/OO1 for fixing details.

 

Flying Lead Sensors

Bead Sensors

SEN / FL / 1M / 001
Bead Temperature Sensor with 1M Flying Lead
SEN / FL / 3M / 001
Bead Temperature Sensor with 3M Flying Lead
Measures air temperature, especially in fan coil units etc.
Probe
Houses sensor element
Dimensions: 35mm x 6mm diameter
Material: 316 Stainless Steel
Connection: 2 core flying lead 1m or 3m, polarity independant
Ambient -40 to 60 DegC

 

 

Flying Lead Sensors

Thimble Sensors

SEN / THM / P
Thimble Temperature Sensor with White Plastic Finish
SEN / THM / BR
Thimble Temperature Sensor with Brass Finish
SEN / THM / ALP
Thimble Temperature Sensor with Polished Aluminium Finish
SEN / THM / ALB
Thimble Temperature Sensor with Brushed Aluminium Finish
SEN / THM / SS
Thimble Temperature Sensor with Stainless Steel Finish
Measures air temperature in indoor spaces.
Probe
Houses sensor element
Dimensions: 45mm x 22mm diameter
Thread: M16 x 1.5mm x 25mm (internal 11mm x 20mm)
Material (/P): Flame retardant ABS
Material (/BR): Brass
Material (/ALP): Polished Aliminium
Material (/ALB): Brushed Aluminium
Material (/SS): 316 Stainless Steel
Connection: 2 core flying lead 1m, polarity independant
Ambient -10 to 60 DegC
Mounting
Drill a suitable hole in the mounting surface. Pass the flying lead and threaded part of the body through the hole. Secure with the fixing nut provided.

Sensor Resistance Tables

The following table shows temperature v resistance in Ohms for the tight tolerance (+/-0.2degC) negative temperature coefficient thermistor used in SeaChange products. Uses Thermistor Type 10k3A1.

Deg C

Ohms

Deg C

Ohms

Deg C

Ohms

Deg C

Ohms

-50
667828
1
31030
16
15001
35
6530
-40
335671
2
29500
17
14325
40
5325
-30
176683
3
28054
18
13623
45
4367
-20
96974
4
26688
19
13053
50
3601
-10
55298
5
25396
20
12494
55
2985
-5
42314
6
24173
21
11943
60
2487
0
32650
7
23016
22
11420
65
2082
 
 
8
21921
23
10923
70
1751
 
 
9
20885
24
10450
75
1480
 
 
10
19904
25
10000
80
1256
 
 
11
18974
26
9572
85
1070
 
 
12
18092
27
9165
90
916.1
 
 
13
17257
28
8777
95
787.0
 
 
14
16465
29
8408
100
678.6
 
 
15
15714
30
8056
105
587.3
 
 
 
 
 
 
110
510.1
 
 
 
 
 
 
115
444.5
 
 
 
 
 
 
120
388.6

Networked Sensors

A range of networked temperature and humidity sensor products are also available. Please contact SC Controls for details. Any thermistor temperature sensor (using the 10k3A1 scaling) can be retrofitted to a networked application by the addition of the interface SEN / PR / INT / TMP / 001.

 

Options and Product Codes

Thermistor Sensors

SEN / [application] / [option] / [variant]

Plant Room Sensors

Code

 
SEN / PR / IMM / 001
Immersion Temperature Sensor IP65
SEN / PR / CLP / 001
Clamp-On Temperature Sensor IP65
SEN / PR / OAT / 001
Outside Air Temperature Sensor IP65
SEN / PR / DCT / 001
Duct Temperature Sensor

Accessories

Code

 
SEN / BP
Brass Pocket for Immersion Temperature Sensor
SEN / SS
Stainless Steel Pocket for Immersion Temperature Sensor

Pattress Mount Sensors

Code

 
SEN / PTR / ROM / 001
Room Temperature Sensor
SEN / PTR / ROM / 002
Room Temperature Sensor with Setpoint Adjust
SEN / PTR / ROM / 003
Room Temperature Sensor with Setpoint Adjust
and Fanspeed Adjust Switch
SEN / PTR / ROM / 004
Room Temperature Sensor with Setpoint Adjust
and Occupation Switch
SEN / PTR / BLK / 001
Black Bulb Sensor

Flying Lead Sensors

Code

 
SEN / FL / 1M / 001
Bead Temperature Sensor with 1M Flying Lead
SEN / FL / 3M / 001
Bead Temperature Sensor with 3M Flying Lead

Thimble Sensors

Code

 
SEN / THM / P
Thimble Temperature Sensor with White Plastic Finish
SEN / THM / BR
Thimble Temperature Sensor with Brass Finish
SEN / THM / ALP
Thimble Temperature Sensor with Polished Aluminium Finish
SEN / THM / ALB
Thimble Temperature Sensor with Brushed Aluminium Finish
SEN / THM / SS
Thimble Temperature Sensor with Stainless Steel Finish
SC Controls Ltd