Feature |
Data Sheet |
Wiring |
Feature Notes |
|
Temperature Sensors |
|
SEN/.../.../... |
|
Main FeaturesTemperature Sensors for all common applications
|
![]() |
Plant Room Sensors |
Immersion Temperature Sensor IP65 rated. |
![]() |
SEN / PR / IMM / 001
|
Enclosure
|
MountingIf the sensor is to be mounted outside, it is recommended that the unit be mounted with the cable entry at the bottom. In addition, if the cable is fed from above the sensor we also recommend that a rain loop is placed in the cable before entry into the sensor.Remove the front cover by twisting the lid and separating from the main body to make the electrical connections. Fix the sensor in to the pocket and secure with the grub screw provided with the pocket.Feed the cable through the waterproof gland and terminate the cores at the terminal block. Leave some slack inside the unit, tighten the cable gland onto the cable to ensure watertightness. Replace the lid after the electrical connections have been made. |
Plant Room Sensors |
Clamp-On Temperature Sensor IP65 |
![]() |
SEN / PR / CLP / 001
|
Enclosure
|
MountingIf the sensor is to be mounted outside, it is recommended that the unit be mounted with the two cable entries at the sides. In addition, if the cables are fed from above the IP65 housing we also recommend that a rain loop is placed in the cable before entry into the sensor.Remove the front cover by twisting the lid and separating from the main body. Using the base of the housing as a template mark the hole centres. Drill two pilot holes at 85mm centres in the surface on which the sensor is to be mounted, and fix the sensor with appropriate screws. The housing is designed to make it easy for an electric screwdriver to be used if desired.Feed the cables through the waterproof glands and terminate the cores at the terminal blocks. Leaving some slack inside the units, tighten the cable glands onto the cables to ensure watertightness. Replace the lid after the electrical connections have been made. |
Plant Room Sensors |
Outside Air Temperature Sensor IP65 |
![]() |
SEN / PR / OAT / 001
|
Enclosure |
MountingOutside air sensors should always be situated in a sheltered position on a north facing wall.Avoid mounting the sensor in direct sunlight. It is recommended that the unit be mounted with the cable entry at the bottom. In addition, if the cable is fed from above the sensor we also recommend that a rain loop is placed in the cable before entry into the sensor.Remove the front cover by twisting the lid and separating from the main body. Using the base of the housing as a template mark the hole centres. Drill two pilot holes at 85mm centres in the surface on which the sensor is to be mounted, and fix the sensor with appropriate screws. The housing is designed to make it easy for an electric screwdriver to be used if desired.Feed the cable through the waterproof gland and terminate the cores at the terminal block. Leaving some slack inside the units, tighten the cable gland onto the cable to ensure watertightness. Replace the lid after the electrical connections have been made. |
Plant Room Sensors |
Duct Temperature Sensor |
![]() |
SEN / PR / DCT / 001 Sensing element is contained within 150mm long brass probe with holes to allow air to flow directly over the element. A neoprene gasket is supplied to ensure a good seal onto the duct. |
| Enclosure Probe |
MountingIf the sensor enclosure is to be mounted outside, it is recommended that the unit be mounted with the cable entry at the bottom. In addition, if the cable is fed from above the sensor we also recommend that a rain loop is placed in the cable before entry into the sensor.Remove the front cover by twisting the lid and separating from the main body. Using the base of the housing as a template mark the hole centres. Drill two pilot holes at 85mm centres in the surface on which the sensor is to be mounted. Apply the gasket provided to the base of the housing. Align the holes in the probe so that they point into the airflow, not at right-angles to it. Press onto the side of the ductwork to form a seal between the sensor and the duct. Fix the sensor with appropriate screws. The housing is designed to make it easy for an electric screwdriver to be used if desired.Feed the cable through the waterproof gland and terminate the cores at the terminal block. Leaving some slack inside the units, tighten the cable gland onto the cable to ensure watertightness. Replace the lid after the electrical connections have been made. |
Accessories |
Pocket for Immersion Temperature Sensor |
![]() |
SEN / BP |
Brass Pocket
|
MountingPockets can be installed in any system that is constructed from compatible materials whose operating pressures are within the specified ranges and fit into a 1/2" BSPT boss using a thread-seal compound.In pipework systems, fit into an elbow such that the pocket runs down the centre of the pipe, against the direction of flow |
Pattress Mount Sensors |
Room Temperature Sensor |
![]() |
SEN / PTR / ROM / 001
|
Enclosure |
![]() |
MountingRemove the tamperproof screw at the bottom of the housing and gently pull outwards from the base. Using the base of the housing as a template mark the hole centres and fix to the wall with suitable screws. Alternatively, the housing can be mounted on to a pattress box. |
|
Pattress Mount Sensors |
Room Temperature Sensor with Setpoint Adjust |
![]() |
SEN / PTR / ROM / 002 |
Enclosure |
MountingRemove the tamperproof screw at the bottom of the housing and gently pull outwards from the base. Using the base of the housing as a template mark the hole centres and fix to the wall with suitable screws. Alternatively, the housing can be mounted on to a pattress box. See SEN/PTR/ROM/OO1 for fixing details.Connections
|
Pattress Mount Sensors |
Room Temperature Sensor with Setpoint Adjust and Fan Switch |
![]() |
SEN / PTR / ROM / 003 |
Enclosure
|
MountingRemove the tamperproof screw at the bottom of the housing and gently pull outwards from the base. Using the base of the housing as a template mark the hole centres and fix to the wall with suitable screws. Alternatively, the housing can be mounted on to a pattress box. See SEN/PTR/ROM/OO1 for fixing details.Connections
|
Pattress Mount Sensors |
Room Temperature Sensor with Setpoint Adjust and Override Switch |
Picture currently not available. |
SEN / PTR / ROM / 004 |
Enclosure
|
MountingRemove the tamperproof screw at the bottom of the housing and gently pull outwards from the base. Using the base of the housing as a template mark the hole centres and fix to the wall with suitable screws. Alternatively, the housing can be mounted on to a pattress box. See SEN/PTR/ROM/OO1 for fixing details.Connections
|
Pattress Mount Sensors |
Indoor Black Bulb Sensor |
![]() |
SEN / PTR / BLK / 001
|
Enclosure |
MountingRemove the tamperproof screw at the bottom of the housing and gently pull outwards from the base. Using the base of the housing as a template mark the hole centres and fix to the wall with suitable screws. Alternatively, the housing can be mounted on to a pattress box. See SEN/PTR/ROM/OO1 for fixing details. |
Pattress Mount Sensors |
Room Temperature Sensors - Special Finishes |
![]() |
The room temperature sensors are also available in a number of alternative finishes for special requirements. These finishes are not stocked but are available on special request. Some samples are shown alongside. |
Enclosure |
MountingRemove the tamperproof screw at the bottom of the housing and gently pull outwards from the base. Using the base of the housing as a template mark the hole centres and fix to the wall with suitable screws. Alternatively, the housing can be mounted on to a pattress box. See SEN/PTR/ROM/OO1 for fixing details. |
Flying Lead Sensors |
Bead Sensors |
![]() |
SEN / FL / 1M / 001 |
Probe |
Flying Lead Sensors |
Thimble Sensors |
![]() |
SEN / THM / P
|
Probe |
Mounting
|
Deg C |
Ohms |
Deg C |
Ohms |
Deg C |
Ohms |
Deg C |
Ohms |
-50 |
667828 |
1 |
31030 |
16 |
15001 |
35 |
6530 |
-40 |
335671 |
2 |
29500 |
17 |
14325 |
40 |
5325 |
-30 |
176683 |
3 |
28054 |
18 |
13623 |
45 |
4367 |
-20 |
96974 |
4 |
26688 |
19 |
13053 |
50 |
3601 |
-10 |
55298 |
5 |
25396 |
20 |
12494 |
55 |
2985 |
-5 |
42314 |
6 |
24173 |
21 |
11943 |
60 |
2487 |
0 |
32650 |
7 |
23016 |
22 |
11420 |
65 |
2082 |
8 |
21921 |
23 |
10923 |
70 |
1751 |
||
9 |
20885 |
24 |
10450 |
75 |
1480 |
||
10 |
19904 |
25 |
10000 |
80 |
1256 |
||
11 |
18974 |
26 |
9572 |
85 |
1070 |
||
12 |
18092 |
27 |
9165 |
90 |
916.1 |
||
13 |
17257 |
28 |
8777 |
95 |
787.0 |
||
14 |
16465 |
29 |
8408 |
100 |
678.6 |
||
15 |
15714 |
30 |
8056 |
105 |
587.3 |
||
110 |
510.1 |
||||||
115 |
444.5 |
||||||
120 |
388.6 |
Code |
|
SEN / PR / IMM / 001 |
Immersion Temperature Sensor IP65 |
SEN / PR / CLP / 001 |
Clamp-On Temperature Sensor IP65 |
SEN / PR / OAT / 001 |
Outside Air Temperature Sensor IP65 |
SEN / PR / DCT / 001 |
Duct Temperature Sensor |
Code |
|
SEN / BP |
Brass Pocket for Immersion Temperature Sensor |
SEN / SS |
Stainless Steel Pocket for Immersion Temperature Sensor |
Code |
|
SEN / PTR / ROM / 001 |
Room Temperature Sensor |
SEN / PTR / ROM / 002 |
Room Temperature Sensor with Setpoint Adjust |
SEN / PTR / ROM / 003 |
Room Temperature Sensor with Setpoint Adjust |
SEN / PTR / ROM / 004 |
Room Temperature Sensor with Setpoint Adjust |
SEN / PTR / BLK / 001 |
Black Bulb Sensor |
Code |
|
SEN / FL / 1M / 001 |
Bead Temperature Sensor with 1M Flying Lead |
SEN / FL / 3M / 001 |
Bead Temperature Sensor with 3M Flying Lead |
Code |
|
SEN / THM / P |
Thimble Temperature Sensor with White Plastic Finish |
SEN / THM / BR |
Thimble Temperature Sensor with Brass Finish |
SEN / THM / ALP |
Thimble Temperature Sensor with Polished Aluminium Finish |
SEN / THM / ALB |
Thimble Temperature Sensor with Brushed Aluminium Finish |
SEN / THM / SS |
Thimble Temperature Sensor with Stainless Steel Finish |