Configuration Tables Wiring    

Secondary Circuit Controller
with built-in Pump Changeover Facility

Configuration Tables

Doorway / InSite Code

Label

Description

Units

Default Value

Range

C1
ALRM
Alarm Mode
0: Ignore alarms
1: Report all alarms to Doorway/InSite,
2: Report all alarms, shut down on STOP alarm
-
0
0 to 2
C2
ALST
Alarm report sense
0: Alarm if input = 0 (contact open), pump running if input = 1 (closed)
1: Alarm if input = 1 (contact closed), pump running if input = 0 (open)
-
0
0 to 1
C3
FMD
Failure Mode
1: Both pumps remain enabled
2: Last pump remains enabled
3: Both pumps disabled
-
2
1 to 3
C4
DLAY
Delay to wait for proof of flow
Secs
10
1 to 250
C5
MXHR
Maximum hours run before duty pump changeover
Hrs
24
1 to 200
C6
MNON
Pump Minimum on time
Mins
5
0 to 200
C7
MXDY
Maximum days off time for pump exercise
Days
7
0 to 10
C8
NPMP
Number of pumps controlled
-
2
1 to 2
C9
MIND
Minimum Demand (types 4 and 7 only)
-
0
-
 
 
Minimum Demand (types 6 and 9 only)
-
5
-
C10
MNAV
Minimum Average Demand
%
0
0 to 100
C11
MNOC
Minimum number of Occupied Zones
-
0
0 to 200
C12
MXCT
Maximum CT demand (for Heating types only)
Deg C
82
0 to 100
 
 
Maximum CT demand (cooling types)
Deg C
16
0 to 100
C13
MNCT
Minimum CT demand (for Heating types only)
Deg C
30
0 to 100
 
 
Minimum CT demand (cooling types)
Deg C
11
0 to 100
C14
MODD
Modulate actuator
0: Drive actuator to 100% when pump set enabled
1: Drive actuator with highest demand
-
0
0 to 1
C15
FRPT
Frost Protection Mode
0: No action
1: Run pump set
-
0
0 to 1
C16
HTSC
Heat Source (for Heating types only)
-
1
0 to 8255
 
CLSC
Cool Source (for Cooling types only)
-
1
0 to 8255
C17
HTCT
Heating Demand sent as CT (for Heating types only)
0: HTSC interconnects to Secondary Circuit, demand sent %
1: HTSC interconnects to Boiler, demand sent as CT temp
-
1
0 to 1
 
CLCT
Cooling Demand sent as CT (for Cooling types only)
0: CLSC interconnects to Secondary Circuit, demand sent as %
1: CLSC interconnects to Chiller, demand sent as CT temp
-
1
0 to 1
C18
OCDS
Occupation Destination
-
0
0 to 8255

Monitoring Parameters

Doorway / InSite Code

Label

Description

Units

Default Value

Range

I1 (C30)
FL A
Flow status pump A
-
-
0 to 1
I2 (C31)
FL B
Flow status pump B
-
-
0 to 1
I3 (C32)
FROS
Frost Protection in progress
-
-
0 to 1
I4 (C33)
COND
Condensation Detected (for Cooling types only)
-
-
0 to 1
I5 (C34)
FAIL
Single or Dual Pump Failure
-
-
0 to 1
I6 (C35)
PMPA
Triac output 1 status Pump A
-
-
0 to 1
I7 (C36)
PMPB
Triac output 2 status Pump B
-
-
0 to 1
I8 (C37)
ALRS
Triac output spare status Alarm Sounder
-
-
0 to 1
W1 (C38)
AUTO
Automatic/Manual Status
-
-
0 to 1
W2 (C39)
OVRD
Override
-
-
0 to 1
W3 (C40)
RSTA
Reset hours run pump A
-
-
0 to 1
W4 (C41)
RSTB
Reset hours run pump B
-
-
0 to 1
W5 (C42)
RNON
Enable pump run on
-
1
0 to 1
W6 (C43)
ACLR
Automatically clear alarms
-
1
0 to 1
W7 (C44)
SERV
Service Pin Message (to Doorway and InSite, self resetting)
-
-
0 to 1
W8 (C45)
CGST
Configuration Mode Status
-
-
0 to 1
S1* (C50)
HRSA
Hours run pump A
Hrs
-
-
S2* (C51)
HRSB
Hours run pump B
Hrs
-
-
S3 (C52)
ZDMD
Highest demand from zones
%
-
-
S4 (C53)
AVDM
Average demand from zones
%
-
-
S5 (C54)
NOCC
Number of zones Occupied
-
-
-
K1 (C60)
MXCT
Maximum CT Demand (for Heating types only)
Deg C
82
0 to 100
 
 
Maximum CT Demand (for Cooling types only)
Deg C
16
0 to 100
K2 (C61)
MNCT
Minimum CT Demand (for Heating types only)
Deg C
30
0 to 100
 
 
Minimum CT Demand (for Cooling types only)
Deg C
11
0 to 100
 
 
Engineering Parameters; only accessible via Doorway and InSite
 
 
 
C90
NOAL
No Alarms; all alarms cleared when set to 1
-
-
0 or 1
C91
FLFA
Flow Failed pump A (when set to 1)
-
-
0 or 1
C92
FLFB
Flow Failed pump B (when set to 1)
-
-
0 or 1
C93
DPMF
Dual Pump Failure (when set to 1)
-
-
0 or 1
C94
STOP
STOP alarm received (when set to 1)
-
-
0 or 1
C95
CNDF
Condensation Alarm (for Cooling types only)
-
-
0 or 1
 
 
* 24 hour plots available for these values by default
 
 
 
 
 
Plotting interval and plotted variable changeable via Doorway or InSite
 
 
 