Doorway / InSite Code |
Label |
Description |
Units |
Default Value |
Range |
C1 |
ALRM |
Alarm Mode
0: Ignore alarms
1: Report all alarms to Doorway/InSite,
2: Report all alarms, shut down on STOP alarm |
- |
0 |
0 to 2 |
C2 |
ALST |
Alarm report sense
0: Alarm if input = 0 (contact open), pump running if input = 1 (closed)
1: Alarm if input = 1 (contact closed), pump running if input = 0 (open)
|
- |
0 |
0 to 1 |
C3 |
FMD |
Failure Mode
1: Both pumps remain enabled
2: Last pump remains enabled
3: Both pumps disabled |
- |
2 |
1 to 3 |
C4 |
DLAY |
Delay to wait for proof of flow |
Secs |
10 |
1 to 250 |
C5 |
MXHR |
Maximum hours run before duty pump changeover |
Hrs |
24 |
1 to 200 |
C6 |
MNON |
Pump Minimum on time |
Mins |
5 |
0 to 200 |
C7 |
MXDY |
Maximum days off time for pump exercise |
Days |
7 |
0 to 10 |
C8 |
NPMP |
Number of pumps controlled |
- |
2 |
1 to 2 |
C9 |
MIND |
Minimum Demand (types 4 and 7 only) |
- |
0 |
- |
|
|
Minimum Demand (types 6 and 9 only) |
- |
5 |
- |
C10 |
MNAV |
Minimum Average Demand |
% |
0 |
0 to 100 |
C11 |
MNOC |
Minimum number of Occupied Zones |
- |
0 |
0 to 200 |
C12 |
MXCT |
Maximum CT demand (for Heating types only) |
Deg C |
82 |
0 to 100 |
|
|
Maximum CT demand (cooling types) |
Deg C |
16 |
0 to 100 |
C13 |
MNCT |
Minimum CT demand (for Heating types only) |
Deg C |
30 |
0 to 100 |
|
|
Minimum CT demand (cooling types) |
Deg C |
11 |
0 to 100 |
C14 |
MODD |
Modulate actuator
0: Drive actuator to 100% when pump set enabled
1: Drive actuator with highest demand |
- |
0 |
0 to 1 |
C15 |
FRPT |
Frost Protection Mode
0: No action
1: Run pump set |
- |
0 |
0 to 1 |
C16 |
HTSC |
Heat Source (for Heating types only) |
- |
1 |
0 to 8255 |
|
CLSC |
Cool Source (for Cooling types only) |
- |
1 |
0 to 8255 |
C17 |
HTCT |
Heating Demand sent as CT (for Heating types only)
0: HTSC interconnects to Secondary Circuit, demand sent %
1: HTSC interconnects to Boiler, demand sent as CT temp |
- |
1 |
0 to 1 |
|
CLCT |
Cooling Demand sent as CT (for Cooling types only)
0: CLSC interconnects to Secondary Circuit, demand sent as %
1: CLSC interconnects to Chiller, demand sent as CT temp |
- |
1 |
0 to 1 |
C18 |
OCDS |
Occupation Destination |
- |
0 |
0 to 8255 |
Doorway / InSite Code |
Label |
Description |
Units |
Default Value |
Range |
I1 (C30) |
FL A |
Flow status pump A |
- |
- |
0 to 1 |
I2 (C31) |
FL B |
Flow status pump B |
- |
- |
0 to 1 |
I3 (C32) |
FROS |
Frost Protection in progress |
- |
- |
0 to 1 |
I4 (C33) |
COND |
Condensation Detected (for Cooling types only) |
- |
- |
0 to 1 |
I5 (C34) |
FAIL |
Single or Dual Pump Failure |
- |
- |
0 to 1 |
I6 (C35) |
PMPA |
Triac output 1 status Pump A |
- |
- |
0 to 1 |
I7 (C36) |
PMPB |
Triac output 2 status Pump B |
- |
- |
0 to 1 |
I8 (C37) |
ALRS |
Triac output spare status Alarm Sounder |
- |
- |
0 to 1 |
W1 (C38) |
AUTO |
Automatic/Manual Status |
- |
- |
0 to 1 |
W2 (C39) |
OVRD |
Override |
- |
- |
0 to 1 |
W3 (C40) |
RSTA |
Reset hours run pump A |
- |
- |
0 to 1 |
W4 (C41) |
RSTB |
Reset hours run pump B |
- |
- |
0 to 1 |
W5 (C42) |
RNON |
Enable pump run on |
- |
1 |
0 to 1 |
W6 (C43) |
ACLR |
Automatically clear alarms |
- |
1 |
0 to 1 |
W7 (C44) |
SERV |
Service Pin Message (to Doorway and InSite, self resetting) |
- |
- |
0 to 1 |
W8 (C45) |
CGST |
Configuration Mode Status |
- |
- |
0 to 1 |
S1* (C50) |
HRSA |
Hours run pump A |
Hrs |
- |
- |
S2* (C51) |
HRSB |
Hours run pump B |
Hrs |
- |
- |
S3 (C52) |
ZDMD |
Highest demand from zones |
% |
- |
- |
S4 (C53) |
AVDM |
Average demand from zones |
% |
- |
- |
S5 (C54) |
NOCC |
Number of zones Occupied |
- |
- |
- |
K1 (C60) |
MXCT |
Maximum CT Demand (for Heating types only) |
Deg C |
82 |
0 to 100 |
|
|
Maximum CT Demand (for Cooling types only) |
Deg C |
16 |
0 to 100 |
K2 (C61) |
MNCT |
Minimum CT Demand (for Heating types only) |
Deg C |
30 |
0 to 100 |
|
|
Minimum CT Demand (for Cooling types only) |
Deg C |
11 |
0 to 100 |
|
|
Engineering Parameters; only accessible via Doorway and InSite |
|
|
|
C90 |
NOAL |
No Alarms; all alarms cleared when set to 1 |
- |
- |
0 or 1 |
C91 |
FLFA |
Flow Failed pump A (when set to 1) |
- |
- |
0 or 1 |
C92 |
FLFB |
Flow Failed pump B (when set to 1) |
- |
- |
0 or 1 |
C93 |
DPMF |
Dual Pump Failure (when set to 1) |
- |
- |
0 or 1 |
C94 |
STOP |
STOP alarm received (when set to 1) |
- |
- |
0 or 1 |
C95 |
CNDF |
Condensation Alarm (for Cooling types only) |
- |
- |
0 or 1 |
|
|