| Feature Notes |
Configuration Tables (heat) | Configuration Tables (cool) | Wiring |
|
|
Main FeaturesControls a Secondary LPHW or Chilled Water Circuit - Pump and Valve ControlProvides Control of Variable Temperature (VT) or Constant Temperature (CT) CircuitsWeather Compensated Control (VTC Version)Temperature Control Based on Zone Demand (VTU Version) Constant Temperature Control (CTU Version) Intelligent Demand Filtering |
![]() |

![]() ![]() |

Input 3-4 |
Optional Sensor |
Input 5-6 |
Flow Sensor |
INMD = 0 |
|
SACT = 0 |
Control on control sensor only |
SACT = 1 |
Control on average of two sensors |
SACT = 2 |
Control on maximum of two sensors |
SACT = 3 |
Control on minimum of two sensors |
Input 3-4 |
External occupancy VFC input |
Input 5-6 |
Flow Sensor |
SACT = 0 |
|
INMD = 1 |
Occupancy determined by own |
INMD = 2 |
Occupancy determined by own |
INMD = 3 |
External occupancy signal only |
Input 3-4 |
External monitor / alarm VFC input |
Input 5-6 |
Flow Sensor |
SACT = 0 |
|
INMD = 4 |
Monitor Input if ALRM = 0 Alarm Input if ALRM > 0 |
INMD = 5 |
Pump readback monitor |
ALST = 0 |
0 = Alarm State, 1 = Normal |
ALST = 1 |
0 = Normal, 1 = Alarm State |
NOAL |
No Alarms. |
SENF |
Sensor Failed. |
EXTN |
External alarm generated by VFC input. |
CNDF |
Condensation Failure |
PMPF |
Pump Fail (readback alarm) generated by VFC input (INMD = 5) or registered PCO Submodule. |
STOP |
System STOP alarm received. |
Heating |
Cooling |
Output A |
Output B |
Output C |
/ 101 |
/ 201 |
Time Proportional |
Not used |
Occupation or Optimum start switch |
/ 105 |
/ 205 |
Valve Open |
Valve Close |
Occupation or Optimum start switch |
/ 108 |
/ 208 |
Sequence 2 triacs at 33% and |
66% of demand |
Occupation or Optimum start switch |
/ 109 |
/ 209 |
Sequence 3 triacs at 25%, |
50% and |
75% of demand |
Heating |
Cooling |
Output A |
Output B |
Output C |
/ 721 |
/ 821 |
0-100% demand = 0-10Vdc |
Occupation Switch or optimum start switch |
Not available |
Input Configuration (3T and AOP versions) |
|
Input 3-4 input a |
Return Sensor (optional) or VFC status / alarm / occupancy |
Input 5-6 input b |
Flow Sensor |