Feature
Notes
Configuration Tables Wiring    

Multi Channel Controller
with 3 x Triac Outputs

Configuration Parameters

Doorway / InSite Code

Label

Description

Units

Default Value

Range

C1
FRSP
Frost protection/ Non Occupied setpoint
Deg C
10
2 to 15
C2
MAXF
Maximum Flow setpoint (used with HTCT to set CT setpoint in BLR)
Deg C
70
5 to 100
C3
MINF
Minimum Flow setpoint (used with HTCT to set CT setpoint in BLR)
Deg C
30
1 to 100
C4
SACT
Sensor action:
0: either
1: average
2: maximum
3: minimum
-
0
0 to 3
C5
SCAL
Sensor calibration
Deg C
0
-10 to 10
C6
SPTY
Setpoint Type (used with HTCT to set CT setpoint in BLR):
0: Setpoint fixed at Max Flow MAXF
1: Setpoint varies linearly based on Maximum Demand Signal from Consumers
2: Setpoint varies linearly based on Average Demand Signal from Consumers
-
0
0 to 2
C7
INMD
Input Mode use of terminals 3-4 'temp a'
0: additional temperature input for max,min,average using SACT
1: External occupation (short = occupied) AND internal occ
2: External occupation OR internal occ
3: External occupation signal only
4: Alarm input
5: Pump Alarm
-
0
0 to 5
C8
MIND
Minimum Demand:
When highest demand from all registered zones is less than this value,controller uses non occupied FRST setpoint
0: controller runs to Occupied setpoint for Occupation period
%
5
0 to 100
C9
MNDV
Minimum demand for driver, affects control of Fan or Pump
%
0
0 to 100
C10
LOSS
Flow Loss:
amount added to the Controller’s setpoint and sent as a CT setpoint to Heat Provider; offsets distrbution heat losses
Deg C
10
0 to 20
C11
PRDA
Minimum on time channel A
Secs/10
Depends on type
1 to 240
C12
DLYA
Interlock delay channel A;
0: Pump starts as valve opens; no delay
Negative value: Valve opens before Pump starts
Positive Value: Pump runs on after valve shuts down
Mins
0
-60 to 60
C13
PRDB
Minimum on time channel B
Secs/10
Depends on type
1 to 240
C14
DLYB
Interlock delay channel B;
0: Pump starts as valve opens; no delay
Negative value: Valve opens before Pump starts
Positive Value: Pump runs on after valve shuts down
Mins
0
-60 to 60
C15
PRDC
Minimum on time channel C
Secs/10
Depends on type
1 to 240
C16
IVOP
Invert outputs when set provided driver is set to sequence or time proportioning
-
0
0 to 1
C17
FRPT
Frost protect mode:
0: none
1: valve only
2: valve and pump
3: pump only
-
0
0 to 3
C18
MANL
Manual level
-
0
0 to 1
C19
CMDE
Control Mode, when set to 0 disables control loop, sensors can be used for monitoring. Demands passed direct to outputs.
-
0
0 to 1
C20
ALRM
Alarm mode:
0: ignore alarms
1: report alarms
2: report alarms, shut down all outputs on local alarm
3: report alarms, shut down all outputs on STOP alarm or local alarm
4: report alarms, shut down all outputs on STOP alarm only
-
0
0 to 4
C21
ALST
Alarm State sets the state which is considered to be the Alarm state for the External Alarm input:
0: open circuit
1: short circuit
-
0
0 to 1
C22
HTSC
Heat Source; points Energy Demand to source of Heating energy
-
1
0 to 8255
C23
OCDS
Occupation Destination:
points Occupancy Demand at another controller
-
0
0 to 8255
C24
HTCT
Heating Demand Selector:
Set to1 if HTSC is pointing Energy Demand at a Boiler Controller - demand sent as a CT setpoint
Set to 0 if HTSC is pointing to another Secondary Circuit Controller - demand sent as a % signal
-
1
0 to 1

 

Monitoring Parameters

Doorway / InSite Code

Label

Description

Units

Default Value

Range

I1 (C30)
EXTI
External input (function depends on input mode)
-
-
0 to 1
I2 (C31)
OCC
Occupied
-
-
0 to 1
I6 (C35)
RLYA
Triac A Status
-
-
0 to 1
I7 (C36)
RLYB
Triac B Status
-
-
0 to 1
I8 (C37)
RLYC
Triac C Status
-
-
0 to 1
W1 (C38)
AUTO
Automatic/Manual Status
-
-
0 to 1
W2 (C39)
OVRD
Override
-
-
0 to 1
W3 (C40)
ILKP
Interlock Pump
-
-
0 to 1
W5 (C42)
HAND
Manual Hand; use with MANL to set output level
-
0
0 to 1
W6 (C41)
POT
Enable use of optional potentiometer (special order hardware)
-
-
0 to 1
W7 (C44)
SERV
Service Pin Msg (to Doorway +InSite, self resetting)
-
-
0 to 1
W8 (C45)
CGST
Configuration Mode Status
-
-
0 to 1
S1* (C50)
HTMP
Heating temperature (resultant of processing by SACT) (for monitoring only)
Deg C
-
-
S2* (C51)
DMND
Control Demand
%
-
-
S3 (C52)
REQD
Current Setpoint
Deg C
-
-
S4 (C53)
DMDA
Demand received for channel A (see knob 3)
%
-
-
S5 (C54)
DMDB
Demand received for channel B (see knob 4)
%
-
-
S6 (C55)
DMDC
Demand received for channel C (see knob 5)
%
-
-
S7 (C56)
FLOW
Temperature (terminals 5-6)
Deg C
-
-
S8 (C57)
RTRN
Temperature (terminals 3-4)
Deg C
-
-
K1 (C60)
MAXF
Maximum Flow setpoint (used with HTCT to set CT setpoint in BLR)
Deg C
-
-
K2 (C61)
MINF
Minimum Flow setpoint (used with HTCT to set CT setpoint in BLR)
Deg C
-
-
K3 (C62)
ZONA
Number of Zone Controller whose demand is to be used for channel A
-
-
-
K4 (C63)
ZONB
Number of Zone Controller whose demand is to be used for channel B
-
-
-
K5 (C64)
ZONC
Number of Zone Controller whose demand is to be used for channel C
-
-
-
 
 
Engineering Parameters; only accessible via Doorway and InSite
 
 
 
C90
NOAL
No alarms ; all alarms cleared when set to 1
-
-
0 or 1
C91
SENF
Sensor fail alarm (when set to 1)
-
-
0 or 1
C92
EXTN
External alarm input (when set to 1)
-
-
0 or 1
C93
CNDF
Condensation alarm (when set to 1)
-
-
0 or 1
C94
PMPF
Pump fail alarm (when set to 1)
-
-
0 or 1
C95
STOP
Stop alarm received (when set to 1)
-
-
0 or 1
C180
DI A
Input 3-4 digital status
-
-
0 or 1
C181
DI B
Input 5-6 digital status
-
-
0 or 1
 
 
* 24 hour plots available for these values by default
 
 
 
 
 
Plotting interval and plotted variable changeable via Doorway or InSite
 
 
 