Wind Speed and Direction Interface Module

Feature
Notes

Configuration Tables

Wiring

 

 

Configuration Tables

Latest released version is 4c2

Document last updated 24/01/2002
Recent features not included on Data sheet are in
RED text

Configuration Parameters

Doorway / InSite Code
Label
Description
Units
Default Value
Range
C1
AVWP
Period in minutes over which the average wind speed is calculated
mins
1
1 to 10
C2
AVDP
Period in minutes over which the average wind direction is calculated
mins
1
1 to 10
C3
WCAL
Wind Speed Calibration parameter, changes the calibration constant by plus or minus 50%
%
100
50 to 150
C4
DCAL
Wind Direction Calibration, allows the direction reading to be changed to match the orientation of the wind sensor
Degrees
0
-360 to 360

Monitoring Parameters

Doorway / InSite Code
Label
Description
Units
Default Value
Range
S1* (C50)
WNDS
Wind Speed
m/sec
-
0.1 to 90
S2* (C51)
WNDD
Wind Direction (0 degrees is North)
Degrees
-
0 to 360
S3 (C52)
AVWS
Average Wind Speed, averaged over the period set in knob 1
m/sec
-
0.5 to 90
S4 (C53)
AVWD
Average Wind Direction, averaged over the period set in knob 2
Degrees
-
0 to 360
S5 (C54)
WMPH
Wind Speed in miles per hour
mph
-
0 to 100
S6 (C55)
WKNT
Wind Speed in Knots (nautical miles per hour)
knots
-
0 to 100
S7 (C56)
WBFT
Wind Speed Beaufort Scale
-
-
0 to 17
S8 (C57)
varies
4-char Label varies to indicate Wind Direction (Cardinal Points)
Value indicates Wind Speed (Beaufort Scale, 0-17)
-
-
0 to 17
K1 (C60)
WCAL
Wind Speed Calibration parameter, changes the calibration constant by plus or minus 50%
%
100
50 to 150
K2 (C61)
DCAL
Wind Direction Calibration, allows the direction reading to be changed to match the orientation of the wind sensor
Degrees
0
-360 to 360
K3 (C62)
WTST
Forces a Test value for Wind Speed if non zero
m/sec
0
0 to 100
K4 (C63)
DTST
Forces a Test value for Wind Direction if non zero
Degrees
0
-360 to 360
 
 
* 24 hour plots available for these values by default
 
 
 
 
 