Feature
Notes
Configuration Tables Wiring    

Monitoring Module
with 5 x Temperature or Digital Inputs

Configuration Tables

Doorway / InSite Code Label Description Units Default Value Range
C1
CHNL
The number of the channel to be configured
1 - 5 Hardware Inputs also (known as 'A' to 'E')
-
-
1 to 5
C2
XTYP
Selected Hardware Input Channel type
0: Analogue
1: Digital
-
0
0 to 1
C3
XLOW
Low alarm level for selected input channel', (* see issue note for delays and deadbands)
-
0
-9999 to +9999
C4
XLDY
Delay before alarm generation, after measured level falling below CLOW:
0: Hysteresis operation
>0: Delay in minutes before alarm action
Mins
2
0 to 30
C5
XHGH
High alarm level for selected input channel.
-
0
-9999 to +9999
C6
XHDY
Delay before alarm generation, after measured level rising above CHGH:
0: Hysteresis operation
>0: Delay in minutes before alarm action
Mins
2
0 to 30
C7
XAON
Selected input channel alarm on condition:
0: No alarms
1: on low alarm
2: on high alarm
3: on high and low alarm
-
-
0 to 3
C8
X NS
Set the 'heathy state' of the currently selected input if configured as a digital input.(Set by default to the state of the input when configured.)
-
0
0 to 1
C9
RTYP
Remote Control Type
0: No action relays controlled by Alarm condition only
1: Relay follows the remote control setting C111- C115. If RTIM is set then the relay will switch off when the time interval expires. The time interval commences when the remote switch setting is changed.
2: Relay follows the remote control setting (C111 C115) If the channel goes into alarm then the relay will switch off. If RTIM is set then the relay will switch off when the time interval expires. The time interval commences when the remote switch setting is changed.
3: Auto-Override When in Auto (C11 RAUT=1) Relay follows Alarm condition, changing the remote control setting forces channel into Override. It will stay in override until the Alarm and Remote settings match. If RTIM is set then the channel will revert to Automaitic, i.e. follow the Alarm setting when the timer expires.
4:Override-until Timeout The relay will follow the alarm unless it is overriden by a change in the Remote control state, when the time times out it will revert to Automatic.
-
0
0 to 4
C10
RTIM
Remote control timer. Provided timmed operation in conjunction with the Remote control options set on RTYP.
-
0.0
24.0 hours
C11
RAUT
Channel Automatic mode
When in Auto the channel relay will be set by the Alarm action, otherwise the relay will follow the Remote control setting.
-
0
0 to 1
C12
ROVD
Current relay State. If changed will force channel into Override mode
-
0
0 to 1
C13
COPY
Copy the currently selected channel setup to channel 'x'.
-
0
0 to 5
C14
DLYO
Alarm delay on, sets delay edge for all 'CAON', :
0: Delay action on alarm condition (ie. Alarm delayed on input exceeding limits, but clears immediately.)
1: Delay action on alarm and clearing (ie. Alarm delayed on input exceeding limits, and delays on clearing.)
2: Delay action on clearing. (ie. Alarm reported immediatly on input exceeding limits, but delays on clearing.)
-
0
0 to 2
C15
ASAC
All stop action. On receipt of 'All Stop' alarm
0: No alarm reporting, no alarms to relays
1: Relays function, but No alarms to doorway
2: All Stop ignored
-
0
0 to 2
C16 GNAS Generate System 'STOP' Alarm
0 = Do NOT generate STOP.
1 = First Input Only generates STOP.
2 = ALL Inputs generate STOP.
- 0 0 to 2
C17 LMCA

Latching mode for Common alarm on channel alarm condition. (Reset - here means RCLR switch W5 or the common alarm reset input channel I6 - ARST)
0 = Channel and common alarm output will latch on, can be reset only once the alarm has cleared.
1 = Channel and common alarm output will latch on, common can be disabled by reset. Common alarm will be bourght back on by any channel changing its current state, i.e alarm or clear.
2 = Channel and common alarm output will latch on, common can be disabled by reset. Common alarm will be bourght back on by any channel going into its alarm state. Any channels that are in alarm (when reset) will clear at that time if no longer in alarm, or will clear without event when that channel alarm condition clears.
3 = No latching of channel or common alarm outputs, output will clear when alarm condition on input clears. Common alarm will be on if any channel is in alarm condition.

- 0 0 to 3

 

Monitoring Parameters

Doorway / InSite Code Label Description Units Default Value Range
I1 (C30) IN A Input a status (if Digital) - - 0 to 1
I2 (C31) IN B Input b status (if Digital) - - 0 to 1
I3 (C32) IN C Input c status (if Digital) - - 0 to 1
I4 (C33) IN D Input d status (if Digital) - - 0 to 1
I5 (C34) IN E Input e status (if Digital) - - 0 to 1
I6 (C35) ARST Alarm reset input status - - 0 to 1
W1 (C38) AUTO Automatic/Manual Status - - 0 to 1
W2 (C39) OVRD Override - - 0 to 1
W3 (C40) NALM No Alarms; use to mute all channels during commissioning
0: Alarm reporting enabled
1: Local and network alarms inhibited
- 0 0 to 1
W4 (C41) CALM Common Alarm; enables channel f relay, and makes relays on channels a-e latch on alarm. Use in conjunction with C29, LMCA
0: Common Alarm disabled, channels a-e de-energise on clear
1: Common Alarm enabled, all channels latch, reset via pushbutton on input f or via RCLR parameter
- 0 0 to 1
W5 (C42) RCLR Remote Clear; allows remote reset of latched alarms via Doorway (set to 1 to reset alarms); parameter self resetting after use
- 0 0 to 1
W6 (C43) RPLN Replace nodes - 1 0 to 1
W7 (C44) SERV Generate Service Pin message - 0 0 to 1
W8 (C45) CGST Configuration Mode status - 0 0 to 1
S1* (C50) IN A Input a Temperature (if not Digital) Deg C - 2 to 110
S2* (C51) IN B Input b Temperature (if not Digital) Deg C - 2 to 110
S3* (C52) IN C Input c Temperature (if not Digital) Deg C - 2 to 110
S4* (C53) IN D Input d Temperature (if not Digital) Deg C - 2 to 110
S5* (C54) IN E Input e Temperature (if not Digital) Deg C - 2 to 110
K1 (C60 RCFG Remote Configuration; Initiates Set-up Mode for single channel or all channels
(depends on setting of CINP). Self resetting to state ‘0’
- 0 0 to 1
K2 (C61) CINP Configure Input; used in conjunction with RCFG to select channel to be configured using Set-up Mode:
0: Configure all channels (when RCFG set to ‘1’)
1-5: Configure this channel only (1=channel a, 2= channel b etc.)
- 0 0 to 5
    Engineering Parameters; only accessible via Doorway and InSite      
C90 NOAL No Alarms current in this Module (1 = No Alarms) - - 0 to 1
C91 ALMA Channel a Alarm state (state of output relay a) - - 0 to 1
C92 ALMB Channel b Alarm state (state of output relay b) - - 0 to 1
C93 ALMC Channel c Alarm state (state of output relay c) - - 0 to 1
C94 ALMD Channel d Alarm state (state of output relay d) - - 0 to 1
C95 ALME Channel e Alarm state (state of output relay e) - - 0 to 1
C96 CMAL Common Alarm state (state of output relay f) - - 0 to 1
    * 4 of the 5 channels have 24 hour graphs available; the logging facility is allocated
automatically to the lowest 4 channels which are configured as Thermistor inputs
     
C110 RMIO Enables control of outputs 'a - e', via configuration parameters C111 - C115. (i.e. Only common alarm relay follows alarm state if enabled) - 0 0 to 1
C111 REMA Enables relay 'a' - - 0 to 1
C112 REMB Enables relay 'b' - - 0 to 1
C113 REMC Enables relay 'c' - - 0 to 1
C114 REMD Enables relay 'd' - - 0 to 1
C115 REME Enables relay 'e' - - 0 to 1
C140 HRST Clears all or individual run hour totals to zero - - 0 to 5
C141 HRSA Remote Hours 'a' run on time - - 0 to 9999
C142 HRSB Remote Hours 'b' run on time - - 0 to 9999
C143 HRSC Remote Hours 'c' run on time - - 0 to 9999
C144 HRSD Remote Hours 'd' run on time - - 0 to 9999
C145 HRSE Remote Hours 'e' run on time     0 to 9999
C146 HSAV Remote Hours Save Current Hours to Non-Volitile Memory - - 0 to 1

 

 