Feature
Notes
Configuration Tables Wiring      

Datasheet

 

Monitoring Module
with 5 x Inputs for Active (0-10V DC) or Digital Inputs

 

MON / DIN / 6R / [Option]

 

Main Features

Monitors 5 external Volt-Free Contacts or 0-10Vdc signals

Generates Alarms for reporting at Doorway Supervisor

5 On-board relays for local alarm annunciation

Relay Output for driving external Common Alarm lamp or annunciator

Input for Common Alarm mute button

Summary Features

General

The module provides the follow capabilities
Monitor up to five inputs, 0-10v DC or digital status (no Thermistor inputs)
Up to 10 Network Intelligent Sensors or Zone controllers can be registered to this module. Module will derive Max, Min and Average for both Temperature and Humidity and generate alarm conditions
Visual indication of fault condition
Provides alarm or status information
Logging of 0-10V DC channels (max 3)
Variable delays or hysteresis can be applied to alarm conditions
Relay outputs for alarm annunciation/indication
Common alarm output (latching/non latching operation)
Alarm repeater function for remote recreation of Common Alarm signal (using Actuator Submodule)

Description of Features

Registration

The module can be used in standalone operation, but if part of a system must be registered with the appropriate system housekeeper. Up to 4 Actuator Submodules for remote recreation of common alarm signal can be registered to monitor module.
Additionally 10 remote measurement devices can be registered to the module - Network Sensors (Temperature only [including Outside type] or Temperature+Humidity) or Zone Controllers (version 4b2 onwards).

Input Channel Set-up

The analogue input channels can be configured via a Zone controller or Doorway, the procedure is the same for both, using Config parameters 1-13 to set the channels behavior (the config table is shown here for clarity).
Doorway / InSite Code
Label
Description
Units
Default Value
Range
C1
CHNL
The number of the channel to be configured
1 - 5 Hardware Inputs also (known as 'A' to 'E')
-
-
1 to 5
C2
CTYP
Selected Hardware Input Channel type
0: Analogue
1: Digital
The input channel type analogue or digital. 0 = Analogue : 1 = Digital. With the input type set to Digital all parameters with the exception of 'CHGH' and 'CHDY' are pre-set and fixed, the normal state for the input is set to the current channel condition as the channel type is set.
-
0
0 to 1
C3
CDP
Selected Hardware Input channel decimal place. This also specifies the range of the measured variable.
0: -9999 to +9999
1: -999.9 to +999.9
2: -99.99 to +99.99
3: -9.999 to +9.999
-
0
0 to 3
C4
CTOP
Selected Hardware Input Channel Engineering value at 10V
-
0
-9999 to +9999
C5
CBTM
Selected Hardware Input Channel Engineering value at 0V
-
0
-9999 to +9999
C6
CLOW
Low alarm level for selected input channel', (* see issue note for delays and deadbands)
-
0
-9999 to +9999
C7
CLDY
Delay before alarm generation, after measured level falling below CLOW:
0: Hysteresis operation
>0: Delay in minutes before alarm action
Mins
2
0 to 30
C8
CHGH
High alarm level for selected input channel.
-
0
-9999 to +9999
C9
CHDY
Delay before alarm generation, after measured level rising above CHGH:
0: Hysteresis operation
>0: Delay in minutes before alarm action
Mins
2
0 to 30
C10
CAON
Selected input channel alarm on condition:
0: No alarms
1: on low alarm
2: on high alarm
3: on high and low alarm
-
-
0 to 3
C11
C OS
Applies an offset to the currently selected channel, +/- 50% of the sensor measuring range. (See note on channel failure tests)
-
-
-
C12
C NS
Set the 'heathy state' of the currently selected input if configured as a digital input.(Set by default to the state of the input when configured.)
-
0
0 to 1
C13
COPY
Copy the currently selected channel setup to channel 'x'.
-
0
0 to 5

Example

(please read - it will save you some time when setting up using a Zone Controller)

To configure the channel to read 0-10v directly set decimal places to 2, and CTOP to 10. To simplify the setting of the range and alarm levels from a zone controller a new feature has been introduced, with the decimal places set to 2, when setting the CTOP figure the knob will move the displayed figure in increments of 0.01. To avoid the need of moving the knob the 1000 clicks to set 10.00, use the following method:- Set the displayed figure to 0.01 now press the 'Override' button on the zone, the zone will now display 0.10 , with each press of the 'override' button the display figure will be multiplied by a factor of 10.

Override mode

To simplify testing or witnessing after set-up, placing the module in the override condition will cause all alarm delays to be ignored.

Alarms

Alarm levels

High and low alarm levels per channel can be specified by the user.

Alarm On

In addition to specifying the alarm levels, the module can be configured to only alarm on certain conditions i.e. low, high or both.

Delays

The module generates an alarm condition when any of its inputs are not in the desired state, or exceed the allowed levels. To prevent spurious alarms, delays are applied to each input, such that the input must remain in the alarm state for the delay period before the alarm is acted on. The default delay period is 2 minutes, individual delays can be applied to the high and low alarm levels of each input.
In addition parameter DLYO is common to all inputs and determines how the delay is applied. The default setting is 0, alarm conditions must exist for the delay period before being reported but clear alarms report immediately. Setting 1 allows the delay to be applied to both the alarm and clear condition, and 2 reports the alarm immediately, but must remain in the healthy state for the delay period before clearing.

Digital only

In the case of digital inputs only the high delay and enable is used. In this mode all other channel parameters are pre-set and cannot be adjusted by the user.

Hysteresis

If any delay is set to 0 then Hysteresis is applied at that alarm level to give an operational deadband, this is calculated as 5% of the span between the limits (or 1% of span which ever is the greater), applied as - 5% at the upper level and +5% at the lower level. i.e. High level = 30, Low level = 10 Hence the span 30 - 10 = 20 therefore 5% of 20 = 1 Giving a high level alarm at 30°C and clearing at 29°C.If the span is wide and you wish to have a tighter alarm band around one of the alarms only then set the other alarm level to the same value, this will force the alarm to operate at the reduced span of 1% . It is permissible to use a delay on one limit and hysteresis on the other.

Other Parameters

All stop condition ASAC - this parameter determines how the module should react to a system 'all stop' alarm.
Generation of System STOP alarm GNAS - this parameter determines if this monitor board should generate System STOP alarms. The STOP alarm when enabled is generated by any recognised alarm condition on any channel analogue or digital. (The simple rule here is if the channel alarm relay is energized a STOP alarm would have been generated if enabled). If a System STOP alarm is received by the monitor module, it will NOT generate further System STOP alarms while another STOP alarm is still current.

Alarm Codes

Alarm status codes represent the following conditions.
Code
Alarm condition
1
Special Alarm
5
DIG_ALARM
15
HIGH_ALARM
25
LOW_ALARM
35
BUSTED
50
CLEAR_ALARM
55
CLEAR_DIG
65
CLEAR_HIGH
75
CLEAR_LOW
120
NOT_BUST
127
NO_ALARMS
Note the Alarm times and clear times, are for future use and are not currently updated. Remember Doorway time and date stamps all the alarms on receipt.
Alarm Priority - after checking the inputs the module applies the following priority order to any conditions found:- digital alarm, high alarm, low alarm, faulty sensor alarm, clear digital alarm, clear high alarm, clear low alarm, clear fault alarm; this ensures that faults are always reported in preference to clear alarms. Alarm reporting is rationalised so that a faulty device will report faulty, not high or low first assuming it was not already out of the specified levels. If a number of inputs are in alarm and then come back within limits they will raise clear alarms, however the last input to clear will cause the module to raise a NOAL' indicating that all points are now within operating limits.
Network sensor fault alarms - these are assigned the lowest priority and sent after all other alarms have been sent. The reporting of remote sensor alarms can be disabled with the RSAM parameter.

Common Alarm Channel/Relay Outputs and Latching Mode

The common alarm is eabled by setting the common alarm enable config parameter CALM to 'ON'. This then makes the common alarm output enabled when any input is in alarm. In this mode the output relays can be set to latch (see latching modes) so the user can see visually which input is out of limits via the lamps. To reset the outputs, input 6 is shorted or RCLR is set. The common alarm output is NOT enabled when alarms are generated from networked sensor values.
 
Latching Mode
LMCA = 0
Channel and common alarm output will latch on, can be reset only once the alarm has cleared. Common alarm will be brought on by any channel in alarm condition.
LMCA = 1
Channel and common alarm output will latch on, common can be disabled by reset. Common alarm will be brought back on by any channel changing its current state, i.e alarm or clear condition.
LMCA = 2
Channel and common alarm output will latch on, common can be disabled by reset. Common alarm will be brought back on by any channel going into its alarm state. Any channels that are in alarm (when reset) will clear at that time if no longer in alarm, or will clear without event when that channel alarm condition clears. i.e common alarm brought on by alarm condition only.
LMCA = 3
No latching of channel or common alarm outputs, output will clear when alarm condition on input clears. Common alarm will be on if any channel is in its alarm condition.

Plotting channels

The plotting channels are automatically allocated to non-digital channels, during the module set-up phase, but can be reallocated using the appropriate Config Variables. This controller has Configurable Plots like most of the other SeaChange controllers. These plots are now automatically re-scaled within the controller to achieve the best resolution for the data recorded. This happens at the end of every 96 readings when new maximum and minimum settings are calculated and also if a new value is outside the current range settings.

Remote alarm signaling

Up to 4 Actuator Submodules for remote recreation of common alarm signal can be registered to monitor module. A typical application would be to have a sounder in the plant room driven from the Common Alarm output on the Monitoring Module and a remote alarm in the security lodge driven from an Actuator Submodule registered to the Monitoring Module.

Network Sensor Values

The module can support up to 10 remote measuring devices that are registered to it. From these sensors the following values are derived;-
Average - updated when a new value is received from any remote device. A value from remote devices will only be included if the device is functional. (A regular check is made that the device is still present, if a known device go's missing then a device failure alarm will be generated)
Maximum - the current highest measured value
Minimum - the current lowest measured value
By default the average values are displayed on Sensor 6 (Temperature) and Sensor 7(Humidity). However, by changing the 'MAMX' parameter these can display the Minimum, Maximum or the Average. Alarms can then be applied to these values; delay and hysteresis as per other alarms.
Individual channel values can be read on configs C170 onwards. It is recommended that Zone values are obtained directly from the Zone controllers. Notice that the Zone controllers are added to the end of the list separate from the other sensor readings. Configs C190 onwards allow the user to see which zone controllers are registered to the module, and the reference they are allocated. (This is done because zone addresses are allocated by the system master, whereas the intelligent sensors registered to the module are given addresses in the module's local address space, this means that it is possible for the zone to be allocated a different reference after an automatic rebuild if the monitor device is ever replaced. However, the checking is still performed on the validity of the value and that the zone is still functional).

Status lamp

The lamp condition indicates the following;
'slow flashing green' - configuration mode selected
'fast flashing green' - manual mode selected
'steady green' - module is healthy
'steady red' - module has a fault

Error lamp

The lamp condition indicates the following;
'green' - no alarm conditions, normal state
'alternating red/green' - input in high alarm, within hysteresis band or delay active
'alternating yellow green' - input in low alarm, within hysteresis band or delay active
'alternating green red' - inputs in high and low alarm, within hysteresis band or delay active

Options and Product Codes

Monitoring Module

MON / DIN / 6R / [Option]

Options

Option

Inputs

/ 002
5 Input Channels for Active (0-10Vdc) Inputs or Digital Inputs

 

Input Configuration

Input 5-6
Input a (VFC or 0-10Vdc)
Input 7-8
Input b (VFC or 0-10Vdc)
Input 9-10
Input c (VFC or 0-10Vdc)
Input 11-12
Input d (VFC or 0-10Vdc)
Input 13-14
Input e (VFC or 0-10Vdc)
Input 15-16
Input f (momentary pushbutton for mute)

 

SC Controls Ltd
PO Box313
Wadhurst
East Sussex
TN5 6JL
phone 08707 606040
fax 08707 606041
e-mail seachange@sccontrols.co.uk
http:// www.seachange.co.uk