Feature
Notes
Configuration Tables Wiring    

Monitoring Module

with 5 x Inputs for Active (0-10V DC) or Digital Inputs

Configuration Tables

Doorway / InSite Code

Label

Description

Units

Default Value

Range

C1
CHNL
The number of the channel to be configured
1 - 5 Hardware Inputs also (known as 'A' to 'E')
-
-
1 to 5
C2
CTYP
Selected Hardware Input Channel type
0: Analogue
1: Digital
-
0
0 to 1
C3
CDP
Selected Hardware Input channel decimal place. This also specifies the range of the measured variable.
0: -9999 to +9999
1: -999.9 to +999.9
2: -99.99 to +99.99
3: -9.999 to +9.999
-
0
0 to 3
C4
CTOP
Selected Hardware Input Channel Engineering value at 10V
-
0
-9999 to +9999
C5
CBTM
Selected Hardware Input Channel Engineering value at 0V
-
0
-9999 to +9999
C6
CLOW
Low alarm level for selected input channel', (* see issue note for delays and deadbands)
-
0
-9999 to +9999
C7
CLDY
Delay before alarm generation, after measured level falling below CLOW:
0: Hysteresis operation
>0: Delay in minutes before alarm action
Mins
2
0 to 30
C8
CHGH
High alarm level for selected input channel.
-
0
-9999 to +9999
C9
CHDY
Delay before alarm generation, after measured level rising above CHGH:
0: Hysteresis operation
>0: Delay in minutes before alarm action
Mins
2
0 to 30
C10
CAON
Selected input channel alarm on condition:
0: No alarms
1: on low alarm
2: on high alarm
3: on high and low alarm
-
-
0 to 3
C11
C OS
Applies an offset to the currently selected channel, +/- 50% of the sensor measuring range. (See note on channel failure tests)
-
-
-
C12
C NS
Set the 'heathy state' of the currently selected input if configured as a digital input.(Set by default to the state of the input when configured.)
-
0
0 to 1
C13
COPY
Copy the currently selected channel setup to channel 'x'.
-
0
0 to 5
C14
DLYO
Alarm delay on, sets delay edge for all 'CAON', TAON, etc:
0: Delay action on alarm condition (ie. Alarm delayed on input exceeding limits, but clears immediately.)
1: Delay action on alarm and clearing (ie. Alarm delayed on input exceeding limits, and delays on clearing.)
2: Delay action on clearing. (ie. Alarm reported immediatly on input exceeding limits, but delays on clearing.)
-
0
0 to 2
C15
ASAC
All stop action. On receipt of 'All Stop' alarm
0: No alarm reporting, no alarms to relays
1: Relays function, but No alarms to doorway
2: All Stop ignored
-
0
0 to 2
C16
TLOW
Low alarm level for remote devices average temperature measurement
Deg C
0
5 to 65
C17
TLDY
Delay before alarm generation, after measured level falling below TLOW:
0: Hysteresis operation
>0: Delay in minutes before alarm action
Mins
2
0 to 30
C18
THGH
High alarm level for remote devices average temperature measurement.
Deg C
0
-9999 to +9999
C19
THDY
Delay before alarm generation, after measured level rising above THGH:
0: Hysteresis operation
>0: Delay in minutes before alarm action
Mins
0
0 to 30
C20
TAON
Temperature alarm on condition:
0: No alarms
1: on low alarm
2: on high alarm
3: on high and low alarm
-
0
0 to 3
C21
HLOW
Low alarm level for remote devices average humidity measurement.
%RH
0
5 to 95
C22
HLDY
Delay before alarm generation, after measured level falling below HLOW:
0: Hysteresis operation
>0: Delay in minutes before alarm action
Mins
2
0 to 30
C23
HHGH
High alarm level for remote devices average humidity measurement.
%RH
0
5 to 95
C24
HHDY
Delay before alarm generation, after measured level rising above CHGH:
0: Hysteresis operation
>0: Delay in minutes before alarm action
Mins
2
0 to 30
C25
HAON
Humidity alarm on condition:
0: No alarms
1: on low alarm
2: on high alarm
3: on high and low alarm.
-
0
0 to 3
C26
RSAM
Remote sensor alarm mute
0: Report remote sensors status online/offline
1: Do not report remote sensor status
With the mute TRUE the condition of the remote sensors can still be monitored by checking the NSEN bit C99 which will be TRUE if any remote device has a fault.
-
1
0 to 1
C27
MAMX
Send the following parameter Temperature and Humidity to (AHU, etc) and display on S6 S7:
0: Minimum value
1: Average value
2: Maximum value
-
0
0 to 2
C28
GNAS
Generate System 'STOP' Alarm:
0: Do NOT generate STOP.
1: First Input Only generates STOP.
2: ALL Inputs generate STOP.
-
0
0 to 2
C29
LMCA
Latching mode for Common alarm on channel alarm condition.
(Reset - here means RCLR switch W5 or the common alarm reset input channel I6 - ARST).
0: Channel and common alarm output will latch on, can be reset only once the alarm has cleared.
1: Channel and common alarm output will latch on, common can be disabled by reset. Common alarm will be bourght back on by any channel changing its current state, i.e alarm or clear.
2: Channel and common alarm output will latch on, common can be disabled by reset. Common alarm will be bourght back on by any channel going into its alarm state. Any channels that are in alarm (when reset) will clear at that time if no longer in alarm, or will clear without event when that channel alarm condition clears.
3: No latching of channel or common alarm outputs, output will clear when alarm condition on input clears. Common alarm will be on if any channel is in alarm condition.
-
0
0 to 3

Monitoring Parameters

Doorway / InSite Code

Label

Description

Units

Default Value

Range

I1 (C30)
IN A
Input 'A' Status if digital
-
-
0 to 1
I2 (C31)
IN B
Input 'B' Status if digital
-
-
0 to 1
I3 (C32)
IN C
Input 'C' Status if digital
-
-
0 to 1
I4 (C33)
IN D
Input 'D' Status if digital
-
-
0 to 1
I5 (C34)
IN E
Input 'E' Status if digital
-
-
0 to 1
I6 (C35)
ARST
Alarm reset input status
-
-
0 to 1
W1 (C38)
AUTO
Automatic/Manual Status
-
1
0 to 1
W2 (C39)
OVRD
Override
-
-
0 to 1
W3 (C40)
NALM
No Alarms - Use as MUTE durring commission phase, no alarms to Doorway:
0: Alarm reporting enabled
1: Mute all
-
0
0 to 1
W4 (C41)
CALM
Common Alarm - Enables the common alarm output, with this enabled the alarm relay will latch and must be reset manually by the 'Reset input' or by setting 'RCLR':
0: Common alarm disabled
1: common alarm enabled
-
0
0 to 1
W5 (C42)
RCLR
Allow remote reset of common alarm from Doorway.
1: Reset (Self clearing)
-
0
0 to 1
W6 (C43)
RPLN
Replace missing nodes in database
1: Auto replace node
-
1
0 to1
W7 (C44)
SERV
Service Pin Msg (to Doorway +InSite, self resetting)
-
0
0 to 1
W8 (C45)
CGST
Configuration Mode Status
-
0
0 to 1
S1* (C50)
IN A
Input 'A' Value
-
-
-
S2* (C51)
IN B
Input 'B' Value
-
-
-
S3* (C52)
IN C
Input 'C' Value
-
-
-
S4 (C53)
IN D
Input 'D' Value
-
-
-
S5 (C54)
IN E
Input 'E' Value
-
-
-
S6 (C55)
NS T
(Max/Min/Ave) Temperature value of remote sensors
Deg C
-
-
S7 (C56)
NS H
(Max/Min/Ave) Humidity value of remote sensors
%RH
-
0 to 100
 
 
Engineering Parameters; only accessible via Doorway and InSite
 
 
 
C90
NOAL
No Alarms; all alarms cleared when set to 1
-
-
0 or 1
C91
ALMA
Input 'A' Alarm state
-
-
0 or 1
C92
ALMB
Input 'B' Alarm state
-
-
0 or 1
C93
ALMC
Input 'C' Alarm state
-
-
0 or 1
C94
ALMD
Input 'D' Alarm state
-
-
0 or 1
C95
ALME
Input 'E' Alarm state
-
-
0 or 1
C96
NS T
Temperature alarm remote devices (S 6)
-
-
0 to 24
C97
NS H
Humidity alarm remote devices (S 7)
-
-
0 to 24
C98
CMAL
Common Alarm state
-
-
1 to 24
C99
NSEN
Remote networked measuring device fault
-
-
0 to 4
 
 
* 24 hour plots available for these values by default
 
 
 
 
 
Plotting interval and plotted variable changeable via Doorway or InSite
 
 
 

 

 