| Feature Notes |
Configuration Tables | Wiring |
Doorway / InSite Code |
Label |
Description |
Units |
Default Value |
Range |
C1 |
CHNL |
The number of the channel to be configured |
- |
- |
1 to 5 |
C2 |
CTYP |
Selected Hardware Input Channel type |
- |
0 |
0 to 1 |
C3 |
CDP |
Selected Hardware Input channel decimal place. This
also specifies the range of the measured variable. |
- |
0 |
0 to 3 |
C4 |
CTOP |
Selected Hardware Input Channel Engineering value at 10V |
- |
0 |
-9999 to +9999 |
C5 |
CBTM |
Selected Hardware Input Channel Engineering value at 0V |
- |
0 |
-9999 to +9999 |
C6 |
CLOW |
Low alarm level for selected input channel', (* see issue note for delays and deadbands) |
- |
0 |
-9999 to +9999 |
C7 |
CLDY |
Delay before alarm generation, after measured level
falling below CLOW: |
Mins |
2 |
0 to 30 |
C8 |
CHGH |
High alarm level for selected input channel. |
- |
0 |
-9999 to +9999 |
C9 |
CHDY |
Delay before alarm generation, after measured level
rising above CHGH: |
Mins |
2 |
0 to 30 |
C10 |
CAON |
Selected input channel alarm on condition: |
- |
- |
0 to 3 |
C11 |
C OS |
Applies an offset to the currently selected channel, +/- 50% of the sensor measuring range. (See note on channel failure tests) |
- |
- |
- |
C12 |
C NS |
Set the 'heathy state' of the currently selected input if configured as a digital input.(Set by default to the state of the input when configured.) |
- |
0 |
0 to 1 |
C13 |
COPY |
Copy the currently selected channel setup to channel 'x'. |
- |
0 |
0 to 5 |
C14 |
DLYO |
Alarm delay on, sets delay edge for all 'CAON', TAON,
etc: |
- |
0 |
0 to 2 |
C15 |
ASAC |
All stop action. On receipt of 'All Stop' alarm |
- |
0 |
0 to 2 |
C16 |
TLOW |
Low alarm level for remote devices average temperature measurement |
Deg C |
0 |
5 to 65 |
C17 |
TLDY |
Delay before alarm generation, after measured level
falling below TLOW: |
Mins |
2 |
0 to 30 |
C18 |
THGH |
High alarm level for remote devices average temperature measurement. |
Deg C |
0 |
-9999 to +9999 |
C19 |
THDY |
Delay before alarm generation, after measured level
rising above THGH: |
Mins |
0 |
0 to 30 |
C20 |
TAON |
Temperature alarm on condition: |
- |
0 |
0 to 3 |
C21 |
HLOW |
Low alarm level for remote devices average humidity measurement. |
%RH |
0 |
5 to 95 |
C22 |
HLDY |
Delay before alarm generation, after measured level
falling below HLOW: |
Mins |
2 |
0 to 30 |
C23 |
HHGH |
High alarm level for remote devices average humidity measurement. |
%RH |
0 |
5 to 95 |
C24 |
HHDY |
Delay before alarm generation, after measured level
rising above CHGH: |
Mins |
2 |
0 to 30 |
C25 |
HAON |
Humidity alarm on condition: |
- |
0 |
0 to 3 |
C26 |
RSAM |
Remote sensor alarm mute |
- |
1 |
0 to 1 |
C27 |
MAMX |
Send the following parameter Temperature and Humidity
to (AHU, etc) and display on S6 S7: |
- |
0 |
0 to 2 |
C28 |
GNAS |
Generate System 'STOP' Alarm: |
- |
0 |
0 to 2 |
C29 |
LMCA |
Latching mode for Common alarm on channel alarm
condition. |
- |
0 |
0 to 3 |
Doorway / InSite Code |
Label |
Description |
Units |
Default Value |
Range |
I1 (C30) |
IN A |
Input 'A' Status if digital |
- |
- |
0 to 1 |
I2 (C31) |
IN B |
Input 'B' Status if digital |
- |
- |
0 to 1 |
I3 (C32) |
IN C |
Input 'C' Status if digital |
- |
- |
0 to 1 |
I4 (C33) |
IN D |
Input 'D' Status if digital |
- |
- |
0 to 1 |
I5 (C34) |
IN E |
Input 'E' Status if digital |
- |
- |
0 to 1 |
I6 (C35) |
ARST |
Alarm reset input status |
- |
- |
0 to 1 |
W1 (C38) |
AUTO |
Automatic/Manual Status |
- |
1 |
0 to 1 |
W2 (C39) |
OVRD |
Override |
- |
- |
0 to 1 |
W3 (C40) |
NALM |
No Alarms - Use as MUTE durring commission phase,
no alarms to Doorway: |
- |
0 |
0 to 1 |
W4 (C41) |
CALM |
Common Alarm - Enables the common alarm output, with
this enabled the alarm relay will latch and must be reset manually by
the 'Reset input' or by setting 'RCLR': |
- |
0 |
0 to 1 |
W5 (C42) |
RCLR |
Allow remote reset of common alarm from Doorway. |
- |
0 |
0 to 1 |
W6 (C43) |
RPLN |
Replace missing nodes in database |
- |
1 |
0 to1 |
W7 (C44) |
SERV |
Service Pin Msg (to Doorway +InSite, self resetting) |
- |
0 |
0 to 1 |
W8 (C45) |
CGST |
Configuration Mode Status |
- |
0 |
0 to 1 |
S1* (C50) |
IN A |
Input 'A' Value |
- |
- |
- |
S2* (C51) |
IN B |
Input 'B' Value |
- |
- |
- |
S3* (C52) |
IN C |
Input 'C' Value |
- |
- |
- |
S4 (C53) |
IN D |
Input 'D' Value |
- |
- |
- |
S5 (C54) |
IN E |
Input 'E' Value |
- |
- |
- |
S6 (C55) |
NS T |
(Max/Min/Ave) Temperature value of remote sensors |
Deg C |
- |
- |
S7 (C56) |
NS H |
(Max/Min/Ave) Humidity value of remote sensors |
%RH |
- |
0 to 100 |
Engineering Parameters; only accessible via Doorway and InSite |
|||||
C90 |
NOAL |
No Alarms; all alarms cleared when set to 1 |
- |
- |
0 or 1 |
C91 |
ALMA |
Input 'A' Alarm state |
- |
- |
0 or 1 |
C92 |
ALMB |
Input 'B' Alarm state |
- |
- |
0 or 1 |
C93 |
ALMC |
Input 'C' Alarm state |
- |
- |
0 or 1 |
C94 |
ALMD |
Input 'D' Alarm state |
- |
- |
0 or 1 |
C95 |
ALME |
Input 'E' Alarm state |
- |
- |
0 or 1 |
C96 |
NS T |
Temperature alarm remote devices (S 6) |
- |
- |
0 to 24 |
C97 |
NS H |
Humidity alarm remote devices (S 7) |
- |
- |
0 to 24 |
C98 |
CMAL |
Common Alarm state |
- |
- |
1 to 24 |
C99 |
NSEN |
Remote networked measuring device fault |
- |
- |
0 to 4 |
* 24 hour plots available for these values by default |
|||||
Plotting interval and plotted variable changeable via Doorway or InSite |