| Feature Notes |
Configuration Tables | Wiring |
Doorway / InSite Code |
Label |
Description |
Units |
Default Value |
Range |
C1 |
SACT |
Sensor Action; sets pre-processing for temperature inputs:
|
- |
0 |
0 to 3 |
C2 |
SPTY |
Setpoint Type, control mode:
|
- |
0 |
0 to 2 |
C3 |
INMD |
Input Mode for use of terminals 9-10, input c:
|
- |
0 |
0 to 5 |
C4 |
MAXH |
Maximum Supply Heating setpoint (used with SPTY = 2) |
Deg C |
30 |
0 to 90 |
C5 |
MINH |
Minimum Supply Heating setpoint (used with SPTY = 2) |
Deg C |
20 |
0 to 90 |
C6 |
MAXC |
Maximum Supply Cooling setpoint (used with SPTY = 2) |
Deg C |
18 |
2 to 30 |
C7 |
MINC |
Minimum Supply Heating setpoint (used with SPTY = 2) |
Deg C |
10 |
2 to 30 |
C8 |
MIND |
Supply minimum demand, used for switching between heating and cooling |
% |
4 |
0 to 10 |
C9 |
OCCO |
When set controller will only run during the occupied period
|
- |
0 |
0 to 1 |
C10 |
HPRD |
Heating period, stroke time of valve or minimum on time |
Secs/10 |
- |
1 to 60 |
C11 |
HDLY |
Interlock delay:
|
Mins |
0 |
-30 to 30 |
C12 |
CPRD |
Cooling period, stroke time of valve or minimum on time |
Secs/10 |
- |
1 to 60 |
C13 |
CDLY |
Interlock delay:
|
Mins |
0 |
-30 to 30 |
C14 |
FPRD |
Fan period, minimum time to change fan speed steps |
Secs/10 |
12 |
1 to 60 |
C15 |
FRPT |
Frost protection:
|
- |
0 |
0 to 2 |
C16 |
MANL |
Manual level , from Doorway |
% |
0 |
-100 to 100 |
C17 |
MXCT |
Maximum CT to Boiler |
Deg C |
70 |
20 to 100 |
C18 |
MNCT |
Minimum CT to Boiler |
Deg C |
50 |
20 to 100 |
C19 |
ALRM |
Alarm mode:
|
- |
1 |
0 to 3 |
C20 |
ALST |
Defines the state of the input which is considered to be the alarm condition |
- |
0 |
0 to 1 |
C21 |
TRND |
When set sends Heat Demand, Cool Demand and Outside Temperature to SLT for onward transmission to TREND outstation(s) (see Serial Adaptor for details) |
- |
0 |
0 to 70 |
C22 |
DOMN |
Own Domain |
- |
1 |
0 to 8 |
C23 |
HTSC |
Heat source; points Energy Demand to source of Heat energy |
- |
0 |
-1 to 250 |
C24 |
CLSC |
Cool source; points Energy Demand to source of Cool energy |
- |
0 |
-1 to 250 |
C25 |
OCDS |
Occupation destination; points Occupancy Demand at another controller |
- |
0 |
0 to 250 |
C26 |
HTCT |
if non zero send value as Heating CT setpoint |
Deg C |
0 |
0 to 100 |
C27 |
CLCT |
if non zero send value as Cooling CT setpoint |
Deg C |
0 |
0 to 20 |
Doorway / InSite Code |
Label |
Description |
Units |
Default Value |
Range |
I1 (C30) |
INPA |
Input A |
- |
- |
0 to 1 |
I2 (C31) |
INPB |
Input B |
- |
- |
0 to 1 |
I3 (C32) |
RLYA |
Relay A (heating stage 1) |
- |
- |
0 to 1 |
I4 (C33) |
RLYB |
Relay B (heating stage 2) |
- |
- |
0 to 1 |
I5 (C34) |
RLYC |
Relay C (heating stage 3) |
- |
- |
0 to 1 |
I6 (C35) |
RLYD |
Relay D (cooling stage 1) |
- |
- |
0 to 1 |
I7 (C36) |
RLYE |
Relay E (cooling stage 2) |
- |
- |
0 to 1 |
I8 (C37) |
RLYF |
Relay F (cooling stage 3) |
- |
- |
0 to 1 |
W1 (C38) |
AUTO |
Automatic/Manual Status |
- |
- |
0 to 1 |
W2 (C39) |
OVRD |
Override |
- |
- |
0 to 1 |
W3 (C40) |
MISN |
Generate an alarm if any node detected as missing |
- |
0 |
0 to 1 |
W4 (C41) |
RPLN |
When registering a new node replace missing nodes |
- |
1 |
0 to 1 |
W5 (C42) |
HAND |
Manual Hand; use with MANL to set output level |
- |
0 |
0 to 1 |
W7 (C44) |
SERV |
Service Pin Msg (to Doorway +InSite, self resetting) |
- |
0 |
0 to 1 |
W8 (C45) |
CGST |
Configuration Mode Status |
- |
- |
0 to 1 |
S1* (C50) |
SPLA |
Temperature Sensor 1 (controlled medium) |
Deg C |
- |
5 to 35 |
S2* (C51) |
RTNA |
Temperature Sensor 2 (controlled medium) |
Deg C |
- |
5 to 35 |
S3 (C52) |
HCOP |
Heat Cool Output to Drivers (cooling negative) |
Deg C |
- |
5 to 35 |
S4 (C53) |
OUTS |
Outside Temperature |
% |
- |
-100 to 100 |
S5 (C54) |
SPSL |
Supply (off coil) setpoint |
Deg C |
- |
5 to 35 |
S6 (C55) |
HDMD |
Heat Demand from return loop or from Zone Controller |
% |
- |
0 to 100 |
S7 (C56) |
CDMD |
Cool Demand from return loop or from Zone Controller |
% |
- |
0 to 100 |
S8 (C57) |
OUTH |
Outside Relative Humidity (from Intelligent T+RH sensor) |
% |
- |
5 to 95 |
S9 (C58) |
PRHT |
Priority Heating Zone number |
- |
0 |
0 to 200 |
S10 (C59) |
PRCL |
Priority Cooling Zone Number |
- |
0 |
0 to 200 |
K1 (C60) |
SPOC |
Occupied setpoint |
Deg C |
20 |
5 to 35 |
K2 (C61) |
SPNO |
Non Occupied setpoint |
Deg C |
10 |
5 to 35 |
K3 (C62) |
SPSV |
Supervised setpoint from Master controller |
Deg C |
- |
0 to 35 |
K4 (C63) |
SPTR |
Setpoint Trim |
Deg C |
0 |
-10 to 10 |
|
|
|
Engineering Parameters; only accessible via Doorway and InSite |
|
|
|
C90 |
NOAL |
No alarms ; all alarms cleared when set to 1 |
- |
- |
0 or 1 |
C91 |
GENA |
General Alarm (input a) (when set to 1) |
- |
- |
0 or 1 |
C92 |
GENB |
General Alarm (input b) (when set to 1) |
- |
- |
0 or 1 |
C93 |
FREZ |
Danger of Freezing Alarm (when set to 1) |
- |
- |
0 or 1 |
C94 |
STOP |
Stop alarm (when set to 1) |
- |
- |
0 or 1 |
C95 |
OUTF |
Outside Sensor Fail (when set to 1) |
- |
- |
0 or 1 |
C96 |
FROS |
Frost Protection in operation (when set to 1) |
- |
- |
0 or 1 |
|
|
|
* 24 hour plots available for these values by default |
|
|
|
|
|
|
Plotting interval and plotted variable changeable via Doorway or InSite |
|
|
|