Feature
Notes
Configuration Tables Wiring    

Heat Pump Controller

with 6 x Relay Outputs

Configuration Tables

Doorway / InSite Code

Label

Description

Units

Default Value

Range

C1
SACT
Sensor Action; sets pre-processing for temperature inputs:
0: use either sensor for control
1: average of valid sensor values
2: maximum of valid sensor values
3: minimum of valid sensor values
-
0
0 to 3
C2
SPTY
Setpoint Type, control mode:
1: Driver only demand-based control
2: Temperature control, Heat/Cool demands from Zone Controllers and/or Fan Coils derive a setpoint using MAXH, MINH, MAXC, MINC
-
0
0 to 2
C3
INMD
Input Mode for use of terminals 9-10, input c:
0: Feature disabled, used for temperature sensing
1: External occupation (input linked = Occupied) AND with internal Occupation
2: External occupation (input linked = Occupied) OR with internal Occupation
3: External Occupation signal only
4: Alarm input
5: Rivermill Project Heat Pump fan speed switch
-
0
0 to 5
C4
MAXH
Maximum Supply Heating setpoint (used with SPTY = 2)
Deg C
30
0 to 90
C5
MINH
Minimum Supply Heating setpoint (used with SPTY = 2)
Deg C
20
0 to 90
C6
MAXC
Maximum Supply Cooling setpoint (used with SPTY = 2)
Deg C
18
2 to 30
C7
MINC
Minimum Supply Heating setpoint (used with SPTY = 2)
Deg C
10
2 to 30
C8
MIND
Supply minimum demand, used for switching between heating and cooling
%
4
0 to 10
C9
OCCO
When set controller will only run during the occupied period
-
0
0 to 1
C10
HPRD
Heating period, stroke time of valve or minimum on time
Secs/10
-
1 to 60
C11
HDLY
Interlock delay:
Negative value delays fan (or pump) after heating starts
Positive value cause run on of fan after heating shuts down
Mins
0
-30 to 30
C12
CPRD
Cooling period, stroke time of valve or minimum on time
Secs/10
-
1 to 60
C13
CDLY
Interlock delay:
Negative value delays fan (or pump) after cooling starts
Positive value cause run on of fan after cooling shuts down
Mins
0
-30 to 30
C14
FPRD
Fan period, minimum time to change fan speed steps
Secs/10
12
1 to 60
C15
FRPT
Frost protection:
0: no action
1: open heating valve 50%
2: open heating valve and run pump/fan
-
0
0 to 2
C16
MANL
Manual level , from Doorway
%
0
-100 to 100
C17
MXCT
Maximum CT to Boiler
Deg C
70
20 to 100
C18
MNCT
Minimum CT to Boiler
Deg C
50
20 to 100
C19
ALRM
Alarm mode:
0: ignore alarms
1: report alarms
2: report alarms, shut down all outputs on alarm
3: report alarms, shut down all outputs on STOP alarm or sensor fail alarm
-
1
0 to 3
C20
ALST
Defines the state of the input which is considered to be the alarm condition
-
0
0 to 1
C21
TRND
When set sends Heat Demand, Cool Demand and Outside Temperature to SLT for onward transmission to TREND outstation(s) (see Serial Adaptor for details)
-
0
0 to 70
C22
DOMN
Own Domain
-
1
0 to 8
C23
HTSC
Heat source; points Energy Demand to source of Heat energy
-
0
-1 to 250
C24
CLSC
Cool source; points Energy Demand to source of Cool energy
-
0
-1 to 250
C25
OCDS
Occupation destination; points Occupancy Demand at another controller
-
0
0 to 250
C26
HTCT
if non zero send value as Heating CT setpoint
Deg C
0
0 to 100
C27
CLCT
if non zero send value as Cooling CT setpoint
Deg C
0
0 to 20

Monitoring Parameters

Doorway / InSite Code

Label

Description

Units

Default Value

Range

I1 (C30)
INPA
Input A
-
-
0 to 1
I2 (C31)
INPB
Input B
-
-
0 to 1
I3 (C32)
RLYA
Relay A (heating stage 1)
-
-
0 to 1
I4 (C33)
RLYB
Relay B (heating stage 2)
-
-
0 to 1
I5 (C34)
RLYC
Relay C (heating stage 3)
-
-
0 to 1
I6 (C35)
RLYD
Relay D (cooling stage 1)
-
-
0 to 1
I7 (C36)
RLYE
Relay E (cooling stage 2)
-
-
0 to 1
I8 (C37)
RLYF
Relay F (cooling stage 3)
-
-
0 to 1
W1 (C38)
AUTO
Automatic/Manual Status
-
-
0 to 1
W2 (C39)
OVRD
Override
-
-
0 to 1
W3 (C40)
MISN
Generate an alarm if any node detected as missing
-
0
0 to 1
W4 (C41)
RPLN
When registering a new node replace missing nodes
-
1
0 to 1
W5 (C42)
HAND
Manual Hand; use with MANL to set output level
-
0
0 to 1
W7 (C44)
SERV
Service Pin Msg (to Doorway +InSite, self resetting)
-
0
0 to 1
W8 (C45)
CGST
Configuration Mode Status
-
-
0 to 1
S1* (C50)
SPLA
Temperature Sensor 1 (controlled medium)
Deg C
-
5 to 35
S2* (C51)
RTNA
Temperature Sensor 2 (controlled medium)
Deg C
-
5 to 35
S3 (C52)
HCOP
Heat Cool Output to Drivers (cooling negative)
Deg C
-
5 to 35
S4 (C53)
OUTS
Outside Temperature
%
-
-100 to 100
S5 (C54)
SPSL
Supply (off coil) setpoint
Deg C
-
5 to 35
S6 (C55)
HDMD
Heat Demand from return loop or from Zone Controller
%
-
0 to 100
S7 (C56)
CDMD
Cool Demand from return loop or from Zone Controller
%
-
0 to 100
S8 (C57)
OUTH
Outside Relative Humidity (from Intelligent T+RH sensor)
%
-
5 to 95
S9 (C58)
PRHT
Priority Heating Zone number
-
0
0 to 200
S10 (C59)
PRCL
Priority Cooling Zone Number
-
0
0 to 200
K1 (C60)
SPOC
Occupied setpoint
Deg C
20
5 to 35
K2 (C61)
SPNO
Non Occupied setpoint
Deg C
10
5 to 35
K3 (C62)
SPSV
Supervised setpoint from Master controller
Deg C
-
0 to 35
K4 (C63)
SPTR
Setpoint Trim
Deg C
0
-10 to 10
 
 
Engineering Parameters; only accessible via Doorway and InSite
 
 
 
C90
NOAL
No alarms ; all alarms cleared when set to 1
-
-
0 or 1
C91
GENA
General Alarm (input a) (when set to 1)
-
-
0 or 1
C92
GENB
General Alarm (input b) (when set to 1)
-
-
0 or 1
C93
FREZ
Danger of Freezing Alarm (when set to 1)
-
-
0 or 1
C94
STOP
Stop alarm (when set to 1)
-
-
0 or 1
C95
OUTF
Outside Sensor Fail (when set to 1)
-
-
0 or 1
C96
FROS
Frost Protection in operation (when set to 1)
-
-
0 or 1
 
 
* 24 hour plots available for these values by default
 
 
 
 
 