Feature
Notes
Configuration Tables Wiring    

Door Heater Controller

with 3 x Triac Outputs

Configuration Tables

Doorway / InSite Code

Label

Description

Units

Default Value

Range

C1
SPFC
Occupied Setpoint
Deg C
20
0 to 35
C2
SPDB
Setpoint Deadband
Deg C
1
0 to 10
C3
SPTR
Setpoint Trim
Deg C
0
-10 to 10
C4
SPTY
Setpoint Type, control mode
0: control to SPFC, occupation from Master Zone
1: SPFC supervised from Master Zone
2: open loop control based on outside temp, occupation from Master Zone
-
1
0 to 2
C5
INMD
Input Mode use of terminals 3-4
0: not used
1: Internal Occupancy AND External Occupation signal (short = occupied)
2: Internal Occupancy OR External Occupation signal
3: External Occupation signal only
4: Alarm Input
-
0
0 to 4
C6
OMXC
Outside Maximum temperature for Cooling
Deg C
35
0 to 50
C7
OMNC
Outside Minimum temperature for Cooling
Deg C
25
0 to 50
C8
OMNH
Outside Minimum temperature for Heating
Deg C
15
0 to 30
C9
OMXH
Outside Maximum temperature for Heating
Deg C
5
2 to 30
C10
MIND
Minimum demand
%
4
0 to 10
C11
OCCO
When set, controller will only run during the occupied period
-
0
0 to 1
C12
HPRD
Heating valve period or minimum on time
Secs/10
depends on driver type
1 to 60
C13
HDLY
Interlock delay
negative value delays fan (or pump) after heating starts
positive value cause run on of fan after heating shuts down
Mins
0
-30 to 30
C14
CPRD
Cooling valve period or minimum on time
Secs/10
depends on driver type
1 to 60
C15
CDLY
Interlock delay
negative value delays fan (or pump) after cooling starts
positive value cause run on of fan after cooling shuts down
Mins
0
-30.to 30
C16
FPRD
Fan period, minimum time to change fan speed steps
Secs/10
12
1 to 60
C17
FRPT
Frost protect
0: no action
1: open heating valve 50%
2: open heating valve and run pump/fan
-
0
0 to 2
C18
MANL
Manual level , from Doorway
%
0
-100 to 100
C19
HTSC
Heat source
-
1
-1 to 100
C20
CLSC
Cool source
-
0
-1 to 100
C21
MXCT
Maximum CT setpoint
Deg C
70
20 to100
C22
MNCT
Minimum CT setpoint
Deg C
50
20 to 100
C23
MIDP
Mid position for Airside Damper control
%
0
0 to 99
C24
ALRM
Alarm mode 
0: ignore alarms
1: report alarms
2: report alarms, shut down all outputs on alarm
3: report alarms, shut down all outputs on STOP alarm or sensor fail alarm
-
1
0 to 3
C25
ALST
Alarm report sense (used with INMD=4)
0: Alarm if input = 0 (contact open)
1: Alarm if input = 1 (contact closed)
-
0
0 to 1

Monitoring Parameters

Doorway / InSite Code

Label

Description

Units

Default Value

Range

I1 (C30)
INPA
Input A Occupation/Alarm Contact status
-
-
0 to 1
I2 (C31)
OCCD
Occupied
-
-
0 to 1
I5 (C34)
COOL
Cooling Mode
-
-
0 to 1
I6 (C35)
RLYA
Triac A Status
-
-
0 to 1
I7 (C36)
RLYB
Triac B Status
-
-
0 to 1
I8 (C37)
RLYC
Triac C Status
-
-
0 to 1
W1 (C38)
AUTO
Automatic/Manual Status
-
-
0 to 1
W2 (C39)
OVRD
Override
-
-
0 to 1
W7 (C44)
SERV
Service Pin Msg (to Doorway +InSite, self resetting)
-
-
0 to 1
W8 (C45)
CGST
Configuration Mode Status
-
-
0 to 1
S1* (C50)
SPLA
Supply Air Temperature
Deg C
-
5 to 35
S2* (C51)
RTNA
Return Air Temperature
Deg C
-
5 to 35
S3 (C52)
HCOP
Heat Cool Output to drivers (cooling negative)
%
-
-100 to 100
S4 (C53)
SPSL
Supply (off coil) setpoint
Deg C
-
5 to 35
S5 (C54)
SPRT
Return air setpoint
Deg C
-
5 to 35
S6 (C55)
HDMD
Heat demand from return loop or from Zone Controller
%
-
0 to 100
S7 (C56)
CDMD
Cool demand from return loop or from Zone Controller
%
-
0 to 100
K1 (C60)
SPOC
Occupation Setpoint
Deg C
20
10 to 35
K2 (C61)
SPNO
Non-Occupation Setpoint
Deg C
10
5 to 20
K3 (C62)
SPSV
Supervised Setpoint from Master Controller
Deg C
0
0 to 35
K4 (C63)
SPTR
Setpoint Trim
Deg C
0
-10 to 10
K5 (C64)
MXVA
Maximum Voltage output a (for special order AOP types only)
V
10
0 to 10
K6 (C65)
MNVA
Minimum Voltage output a (for special order AOP types only)
V
0
0 to 10
K7 (C66)
MXVB
Maximum Voltage output b (for special order AOP types only)
V
10
0 to 10
K8 (C67)
MNVB
Minimum Voltage output b (for special order AOP types only)
V
0
0 to 10
 
 
Engineering Parameters; only accessible via Doorway and InSite
 
 
 
C90
NOAL
No Alarms; all alarms cleared when set to 1
-
-
0 or 1
C91
SENF
Sensor Failed (when set to 1)
-
-
0 or 1
C92
EXTN
Volt-Free Contact alarm (when set to 1)
-
-
0 or 1
C93
STOP
STOP alarm received (when set to 1)
-
-
0 or 1
 
 
* 24 hour plots available for these values by default
 
 
 
 
 
Plotting interval and plotted variable changeable via Doorway or InSite
 
 
 