Doorway / InSite Code |
Label |
Description |
Units |
Default Value |
Range |
C1 |
SPFC |
Occupied Setpoint |
Deg C |
20 |
0 to 35 |
C2 |
SPDB |
Setpoint Deadband |
Deg C |
1 |
0 to 10 |
C3 |
SPTR |
Setpoint Trim |
Deg C |
0 |
-10 to 10 |
C4 |
SPTY
|
Setpoint Type, control mode
0: control to SPFC, occupation from Master Zone
1: SPFC supervised from Master Zone
2: open loop control based on outside temp, occupation from Master Zone
|
- |
1
|
0 to 2
|
C5 |
INMD
|
Input Mode use of terminals 3-4
0: not used
1: Internal Occupancy AND External Occupation signal (short = occupied)
2: Internal Occupancy OR External Occupation signal
3: External Occupation signal only
4: Alarm Input |
- |
0
|
0 to 4
|
C6 |
OMXC
|
Outside Maximum temperature for Cooling
|
Deg C |
35 |
0 to 50 |
C7 |
OMNC
|
Outside Minimum temperature for Cooling
|
Deg C |
25 |
0 to 50 |
C8 |
OMNH
|
Outside Minimum temperature for Heating
|
Deg C |
15 |
0 to 30 |
C9 |
OMXH
|
Outside Maximum temperature for Heating |
Deg C |
5 |
2 to 30 |
C10 |
MIND |
Minimum demand |
% |
4
|
0 to 10 |
C11 |
OCCO
|
When set, controller will only run during the occupied
period
|
- |
0 |
0 to 1 |
C12 |
HPRD
|
Heating valve period or minimum on time
|
Secs/10 |
depends on driver type |
1 to 60
|
C13 |
HDLY
|
Interlock delay
negative value delays fan (or pump) after heating starts
positive value cause run on of fan after heating shuts down
|
Mins |
0 |
-30 to 30 |
C14 |
CPRD
|
Cooling valve period or minimum on time |
Secs/10 |
depends on driver type
|
1 to 60
|
C15 |
CDLY
|
Interlock delay
negative value delays fan (or pump) after cooling starts
positive value cause run on of fan after cooling shuts down
|
Mins |
0
|
-30.to 30
|
C16 |
FPRD
|
Fan period, minimum time to change fan speed steps
|
Secs/10 |
12 |
1 to 60
|
C17 |
FRPT
|
Frost protect
0: no action
1: open heating valve 50%
2: open heating valve and run pump/fan
|
- |
0 |
0 to 2 |
C18 |
MANL
|
Manual level , from Doorway |
% |
0 |
-100 to 100 |
C19 |
HTSC
|
Heat source
|
- |
1 |
-1 to 100 |
C20 |
CLSC
|
Cool source
|
- |
0
|
-1 to 100
|
C21 |
MXCT |
Maximum CT setpoint |
Deg C |
70 |
20 to100 |
C22 |
MNCT |
Minimum CT setpoint |
Deg C |
50
|
20 to 100 |
C23 |
MIDP |
Mid position for Airside Damper control |
% |
0 |
0 to 99 |
C24 |
ALRM |
Alarm mode
0: ignore alarms
1: report alarms
2: report alarms, shut down all outputs on alarm
3: report alarms, shut down all outputs on STOP alarm or sensor fail alarm |
- |
1 |
0 to 3 |
C25 |
ALST |
Alarm report sense (used with INMD=4)
0: Alarm if input = 0 (contact open)
1: Alarm if input = 1 (contact closed) |
- |
0 |
0 to 1 |
Doorway / InSite Code |
Label |
Description |
Units |
Default Value |
Range |
I1 (C30)
|
INPA |
Input A Occupation/Alarm Contact status |
- |
- |
0 to 1 |
I2 (C31)
|
OCCD |
Occupied
|
- |
- |
0 to 1 |
I5 (C34)
|
COOL |
Cooling Mode |
- |
- |
0 to 1 |
I6 (C35)
|
RLYA
|
Triac A Status
|
- |
- |
0 to 1 |
I7 (C36)
|
RLYB
|
Triac B Status
|
- |
- |
0 to 1 |
I8 (C37)
|
RLYC
|
Triac C Status
|
- |
- |
0 to 1 |
W1 (C38)
|
AUTO
|
Automatic/Manual Status
|
- |
- |
0 to 1 |
W2 (C39)
|
OVRD
|
Override
|
- |
- |
0 to 1 |
W7 (C44)
|
SERV
|
Service Pin Msg (to Doorway +InSite, self resetting)
|
- |
- |
0 to 1 |
W8 (C45)
|
CGST
|
Configuration Mode Status
|
- |
- |
0 to 1 |
S1* (C50) |
SPLA |
Supply Air Temperature |
Deg C
|
- |
5 to 35 |
S2* (C51)
|
RTNA |
Return Air Temperature |
Deg C
|
- |
5 to 35 |
S3 (C52)
|
HCOP |
Heat Cool Output to drivers (cooling negative) |
% |
- |
-100 to 100 |
S4 (C53)
|
SPSL |
Supply (off coil) setpoint |
Deg C
|
- |
5 to 35 |
S5 (C54) |
SPRT |
Return air setpoint |
Deg C
|
- |
5 to 35 |
S6 (C55)
|
HDMD |
Heat demand from return loop or from Zone Controller |
% |
- |
0 to 100 |
S7 (C56)
|
CDMD |
Cool demand from return loop or from Zone Controller |
% |
- |
0 to 100 |
K1 (C60)
|
SPOC
|
Occupation Setpoint |
Deg C |
20 |
10 to 35 |
K2 (C61) |
SPNO
|
Non-Occupation Setpoint |
Deg C |
10 |
5 to 20 |
K3 (C62)
|
SPSV
|
Supervised Setpoint from Master Controller |
Deg C |
0 |
0 to 35 |
K4 (C63) |
SPTR |
Setpoint Trim
|
Deg C |
0 |
-10 to 10 |
K5 (C64) |
MXVA |
Maximum Voltage output a (for special order AOP types only) |
V |
10 |
0 to 10 |
K6 (C65)
|
MNVA |
Minimum Voltage output a (for special order AOP types only) |
V |
0 |
0 to 10 |
K7 (C66) |
MXVB |
Maximum Voltage output b (for special order AOP types only) |
V |
10 |
0 to 10 |
K8 (C67) |
MNVB |
Minimum Voltage output b (for special order AOP types only) |
V |
0 |
0 to 10 |
|
|
Engineering Parameters; only accessible via Doorway and InSite |
|
|
|
C90
|
NOAL
|
No Alarms; all alarms cleared when set to 1
|
- |
- |
0 or 1 |
C91
|
SENF
|
Sensor Failed (when set to 1)
|
- |
- |
0 or 1 |
C92
|
EXTN
|
Volt-Free Contact alarm (when set to 1)
|
- |
- |
0 or 1 |
C93
|
STOP
|
STOP alarm received (when set to 1)
|
- |
- |
0 or 1 |
|
|
* 24 hour plots available for these values by default |
|
|
|
|
|
Plotting interval and plotted variable changeable via Doorway or InSite |
|
|
|