Configuration Tables
|
Doorway / InSite Code
|
Label
|
Description
|
Units
|
Default Value
|
Range
|
C1
|
SPFC
|
Occupied Return temperature Setpoint
|
Deg C
|
20
|
10 to 35
|
C2
|
SPDB
|
Setpoint Deadband
|
Deg C
|
1
|
0 to 10
|
C3
|
SPTR
|
Setpoint Trim
|
Deg C
|
0
|
-10 to 10
|
C4
|
SPTY
|
Setpoint type
0: Local from C1, occupancy supervised from master Zone Controller
1: Setpoint (and occupancy) supervised from master Zone Controller
2: Supply temperature control or Driver mode (if no supply sensor
fitted) based on Heat/Cool demands from Zone Controller or another Fan
Coil
|
Deg C
|
1
|
0 to 2
|
C5
|
INMD
|
Input mode for terminals ‘temp a’ ( 'input a' for 7R )
0: Supply temperature
1: Internal Occupancy AND External Occupation signal (short = occupied)
2: Internal Occupancy OR External Occupation signal
3: External Occupation signal only
4: Alarm Input
|
-
|
0
|
0 to 4
|
C6
|
MAXH
|
Supply maximum heating setpoint
|
Deg C
|
30
|
0 to 90
|
C7
|
MINH
|
Supply minimum heating setpoint
|
Deg C
|
20
|
0 to 90
|
C8
|
MAXC
|
Supply maximum cooling setpoint
|
Deg C
|
18
|
2 to 30
|
C9
|
MINC
|
Supply minimum cooling setpoint
|
Deg C
|
10
|
2 to 30
|
C10
|
MIND
|
Supply minimum demand, used for switching between heating and
cooling
|
-
|
4
|
0 to 10
|
C11
|
OCCO
|
When set, controller will only run during the Occupied Period
|
-
|
0
|
0 to 1
|
C12
|
HPRD
|
Heating valve period or minimum time
|
Secs/10
|
6
|
0 to 60
|
C13
|
HDLY
|
Heating interlock delay. Negative value delays fan (or pump)
On after heating starts, positive value causes run-on of fan after
heating shuts down
|
Mins
|
0
|
-30 to 30
|
C14
|
CPRD
|
Cooling Valve period or minimum On time
|
Secs/10
|
6
|
1 to 60
|
C15
|
CDLY
|
Cooling Interlock delay. Negative value delays fan (or pump)
On after cooling starts, positive value causes run-on of fan after
cooling shuts down
|
Mins
|
0
|
-30 to 30
|
C16
|
FPRD
|
Fan Period, minimum time to change fan speed steps
|
Secs/10
|
12
|
1 to 60
|
C17
|
FRPT
|
Frost Protection
0 = No Action,
1 = Open Heating Valve to 50%
2 = Open Heating Valve to 50% and run fan (pump)
|
-
|
0
|
0 to 2
|
C18
|
MANL
|
Manual Level, set by Doorway and InSite
|
-
|
0
|
-100 to 100
|
C19
|
HTSC
|
Heat Source
|
-
|
0
|
-1 to 100
|
C20
|
CLSC
|
Cool Source
|
-
|
0
|
-1 to 100
|
C21
|
HTCT
|
Value of CT setpoint sent to Heat Source, % value sent if 0
|
Deg C
|
0
|
0 to 100
|
C22
|
CLCT
|
Not used, set to 0 in this application
|
Deg C
|
0
|
0 to 20
|
C23
|
MIDP
|
Mid Position
-1: selects two pipe operation
-2: Two pipe plus electric heater( heating mode only)
-3: Two pipe plus electric heater (heating and cooling mode)
0: normal operation
1 to 99: Mid position for Airside Damper control
|
%
|
0
|
-3 to 99
|
C24
|
TRRG
|
Sontay Trim Pot +/- range
|
-
|
5
|
0 to 10
|
C25
|
ALRM
|
Alarm mode
0: ignore alarms
1: report alarms
2: report alarms, shut down all outputs on alarm
3: report alarms, shut down all outputs on STOP alarm or sensor fail
alarm
|
-
|
1
|
0 to 3
|
C26
|
ALST
|
Alarm report sense (used with INMD=4)
0: Alarm if input = 0 (contact open)
1: Alarm if input = 1 (contact closed)
|
-
|
0
|
0 to 1
|
Monitoring Parameters (7R versions only)
|
Doorway / InSite Code
|
Label
|
Description
|
Units
|
Default Value
|
Range
|
I1 (C30)
|
INPA
|
Input A status
|
-
|
-
|
0 to 1
|
I2 (C31)
|
OCCD
|
Occupied
|
-
|
-
|
0 to 1
|
I3 (C32)
|
CRSE
|
SeaChange diagnostic use (cool raise)
|
-
|
-
|
0 to 1
|
I4 (C33)
|
CLWR
|
SeaChange diagnostic use (cool lower)
|
-
|
-
|
0 to 1
|
I5 (C34)
|
COOL
|
SeaChange diagnostic use (heating select)
|
-
|
-
|
0 to 1
|
I6 (C35)
|
RLYD
|
Relay D (fan 1) Status
|
-
|
-
|
0 to 1
|
I7 (C36)
|
RLYE
|
Relay E (fan 2) Status
|
-
|
-
|
0 to 1
|
I8 (C37)
|
RLYF
|
Relay F (fan 3) Status
|
-
|
-
|
0 to 1
|
W1 (C38)
|
AUTO
|
Automatic/Manual Status
|
-
|
-
|
0 to 1
|
W2 (C39)
|
OVRD
|
Override
|
-
|
-
|
0 to 1
|
W3 (C40)
|
FSWM
|
Sontay Fan Switch Mode
0: Intelligent Occupation switching changing fan switch after hours will
bring unit back on. Select AUTO to switch off
1: Forced Occupation if Fan Switch is 1-3
|
-
|
0
|
0 to 1
|
W5 (C42)
|
HAND
|
Manual Hand; use with MANL to set output level
|
-
|
0
|
0 to 1
|
W7 (C44)
|
SERV
|
Service Pin Msg (to Doorway +InSite, self resetting)
|
-
|
-
|
0 to 1
|
W8 (C45)
|
CGST
|
Configuration Mode Status
|
-
|
-
|
0 to 1
|
Monitoring Parameters (all versions)
|
Doorway / InSite Code
|
Label
|
Description
|
Units
|
Default Value
|
Range
|
S1* (C50)
|
SPLA
|
Supply Air Temperature
|
Deg C
|
-
|
-
|
S2* (C51)
|
RTNA
|
Return Air Temperature
|
Deg C
|
-
|
-
|
S3* (C52)
|
HCOP
|
Heat Cool Output Valves
|
%
|
-
|
0 to 100
|
S4 (C53)
|
SPSL
|
Current Supply Setpoint
|
Deg C
|
-
|
-
|
S5 (C54)
|
SPRT
|
Current Return Setpoint
|
Deg C
|
-
|
-
|
S6 (C55)
|
HDMD
|
Heat Demand from Room Loop
|
%
|
-
|
0 to 100
|
S7 (C56)
|
CDMD
|
Cool Demand from Room Loop
|
%
|
-
|
0 to 100
|
K1 (C60)
|
SPOC
|
Occupation Setpoint
|
Deg C
|
20
|
5 to 35
|
K2 (C61)
|
SPNO
|
Non-Occupation Setpoint
|
Deg C
|
10
|
5 to 20
|
K3 (C62)
|
SPSV
|
Supervised Setpoint from Master Controller
|
Deg C
|
-
|
0 to 35
|
K4 (C63)
|
SPTR
|
Setpoint Trim
|
Deg C
|
0
|
-10 to 10
|
K5 (C64)
|
FANS
|
Fan Speed
0 switches Fans OFF and controller to override OFF
1-100 manually selects Fan Speed and sets controller to override ON if
not already running
-1 sets Fan Speed to AUTO mode, cancels occupancy override
Current Fan Speed returned when read.
|
%
|
0
|
-1 to 100
|
K6 (C65)
|
MXVA
|
Maximum voltage channel A (AOP versions only, to special order)
|
V
|
10
|
0 to 10
|
K7 (C66)
|
MNVA
|
Minimum voltage channel A (AOP versions only, to special order)
|
V
|
0
|
0 to 10
|
K8 (C67)
|
MXVB
|
Maximum voltage channel B (AOP versions only, to special order)
|
V
|
10
|
0 to 10
|
K9 (C68)
|
MNVB
|
Minimum voltage channel B (AOP versions only, to special order)
|
V
|
0
|
0 to 10
|
| |
|
Engineering Parameters; only accessible via Doorway and InSite
|
|
|
|
C83
|
MANL
|
Fixed HAND manual
|
%
|
0
|
-100 to 100
|
Alarm Parameters
|
C90
|
NOAL
|
No Alarms; all alarms cleared when set to 1
|
-
|
-
|
0 or 1
|
C91
|
SENF
|
Sensor Failed (when set to 1)
|
-
|
-
|
0 or 1
|
C92
|
EXTN
|
Alarm for external input
|
-
|
-
|
0 or 1
|
C93
|
STOP
|
STOP alarm received (when set to 1)
|
-
|
-
|
0 or 1
|
Extended Configuration and Monitoring
|
C150
|
HTYP
|
Heating Driver type
|
|
|
0 to 8
|
C151
|
HSTG
|
Heating Driver stages (negative value inverts the output)
|
|
|
-8 to 8
|
C152
|
CTYP
|
Cooling Driver type
|
|
|
0 to 8
|
C153
|
CSTG
|
Cooling Driver stages (negative value inverts the output)
|
|
|
-8 to 8
|
C154
|
FTYP
|
Fan Driver type
|
|
|
0 to 8
|
C155
|
FSTG
|
Fan Driver stages (negative value inverts the output)
Stages set at >100 sets different stages for heating and cooling
|
|
|
-3 to 155
|
C156
|
HRMX
|
Heating driver rescale maximum
|
%
|
100
|
0 to 100
|
C157
|
HRMN
|
Heating driver rescale minimum
|
%
|
0
|
0 to 100
|
C158
|
CRMX
|
Cooling driver rescale maximum
|
%
|
100
|
0 to 100
|
C159
|
CRMN
|
Cooling driver rescale minimum
|
%
|
0
|
0 to 100
|
C160
|
HDRV
|
Heating demand to the driver after the rescale function
|
%
|
|
read only
|
C161
|
CDRV
|
Cooling demand to the driver after the rescale function
|
%
|
|
read only
|
C162
|
FDRV
|
Fan Speed demand to the driver after the rescale function
|
%
|
|
read only
|
C163
|
NOHS
|
Non Occupied
Heating Supply setpoint
if set to zero Fan Coil will be off regardless of Supply Temperature
|
degC
|
10
|
0 to 30
|
C164
|
NOCS
|
Non Occupied
Cooling Supply setpoint
if set to zero Fan Coil will be off regardless of Supply Temperature
|
degC
|
35
|
0 to 100
|
|
|
* 24 hour plots available for these values by default
|
|
|
|
|
|
Plotting interval and plotted variable changeable via Doorway or