Feature
Notes
Configuration Tables Wiring    

Pool Controller

Configuration Tables

Doorway / InSite Code

Label

Description

Units

Default Value

Range

C1
SACT
Sensor Action
0: Use input 5-6 ’temp’ for Pool temp sensor, input 3-4 for VFC
1: Use average of valid sensor values
2: Use maximum of valid sensor values
3: Use minimum of valid sensor values
4: Use remote sensor as Occupation input , shorted is occupied
5: Use networked temperature (nviRemoteTemp) if valid, else remote hardwired if valid, else local
6: Use remote sensor as PIR input, shorted is occupied with close control. open circuit is standby or non-occupied according to zone occupancy pattern
-
0
0 to 6
C2
SCAL
Calibrate sensor value
Deg C
0
-5 to 5
C3
SPMD
Midpoint of absolute setpoint adjustment range
Deg C
30
5 to 95
C4
SPRG
Range of absolute setpoint adjustment about midpoint
Deg C
5
0 to 10
C5
SPDB
Setpoint deadband between heating and cooling setpoints. If zero disables cooling
Deg C
0
0 to 10
C6
SBDB
Additional deadband used in Standby Mode and Optimum off
Deg C
2
0 to 10
C7
SPTY
Setpoint type
0: use local setpoint
1: use remote setpoint (from supervising Zone Controller), disable local OSS
-
0
0 to 1
C8
XHRS
Extension hours when override pressed outside occupation
Hrs
1
0 to 8
C9
FRSE
Fabric/frost rise; added to SPNO to form termination temperature for heating run if temperature dips below SPNO value during non-occupation
Deg C
0
0 to 10
C10
MIND
Minimum demand to maintain Occupancy output for pump
%
0
0 to 10
C11
OCCO
Run during occupancy only
0: run during occupancy, OSS and frost
1: run during ocupancy only
-
0
0 to 1
C12
HPRD
Heating valve period or minimum on time
Secs/10
-
1 to 60
C13
HDLY
Heating Interlock Delay
negative value delays fan (or pump) after heating starts
positive value cause run on of fan after heating shuts down
Mins
0
-30 to 30
C14
CPRD
Cooling valve period or minimum on time
Secs/10
-
1 to 60
C15
CDLY
Cooling Interlock delay
negative value delays fan (or pump) after cooling starts
positive value cause run on of fan after cooling shuts down
Mins
0
-30 to 30
C16
FPRD
Not used in this application
Secs/10
12
1 to 60
C17
FRPT
Frost protect
0: no action
1: open heating valve 50%
2: open heating valve and run pump/fan
-
0
0 to 2
C18
MANL
Manual level , from Doorway
%
0
-100 to 100
C19
ALRM
Alarm mode
0: Ignore alarms
1: Report alarms
2: Report alarms, shut down all outputs on alarm
3: Report alarms, shut down all outputs on STOP alarm or sensor fail alarm
-
1
0 to 3
C20
ALST
Alarm report sense
0: Alarm if input = 0 (contact open), healthy if input = 1 (closed)
1: Alarm if input = 1 (contact closed), healthy if input = 0 (open)
-
0
0 to 1
C21
HTSC
Heat Source; points Energy Demand to source of Heating energy
-
1
0 to 8255
C22
CLSC
Not used in this application
 
0
0 to 8255
C23
OCDS
Occupation Destination:
points Occupancy Demand at another controller
-
0
0 to 8255
C24
HTCT
Setpoint selector
0: send Heating Demand signal as %
>0: CT Setpoint, send Heating Demand as CT setpoint only accepted by Primary Boiler Controller set temperature required from boiler (for CT Circuit Control)
Deg C
0
0 to 100
C25
CLCT
Reserved for future use
Deg C
0
0 to 20
C26
ISS3
Set to force single domain operation (should only be needed when using issue 3 Floor Controllers)
-
0
0 to 1

Monitoring Parameters

Doorway / InSite Code

Label

Description

Units

Default Value

Range

I1 (C30)
FRST
Frost Protection Mode (SPNO violated)
-
-
0 to 1
I2 (C31)
OCC
Occupied
-
-
0 to 1
I3 (C32)
OSRT
Optimum Start in operation
-
-
0 to 1
I4 (C33)
OOFF
Optimum Off in operation
-
-
0 to 1
I5 (C34)
COOL
Controller in cooling mode
-
-
0 to 1
I6 (C35)
COND
Condensation detected
-
-
0 to 1
I8 (C37)
XOCC
External Occupation signal
-
-
0 to 1
W1 (C38)
AUTO
Automatic/Manual Status
-
-
0 to 1
W2 (C39)
OVRD
Override
-
-
0 to 1
W5 (C42)
HAND
Manual Hand; use with MANL to set output level
-
0
0 to 1
W8 (C45)
CGST
Configuration Mode Status
-
-
0 to 1
S1* (C50)
ROOM
Controller measured temperature
Deg C
-
5 to 30
S2* (C51)
DMND
Control Demand
%
-
-100 to 100
S3 (C52)
REQD
Controller current setpoint
Deg C
-
5 to 30
S4 (C53)
HTOP
Heating Output to driver
%
-
0 to 100
S5 (C54)
CLOP
Cooling Output to driver
%
-
0 to 100
S6 (C55)
RHUM
Relative Humidity (Not used in this application)
%
-
0 to 100
S7 (C56)
OPST
Last Optimum Start time
hours
-
0 to 24
S8 (C57)
OPOK
Last Optimum Start complete (OK)
hours
-
0 to 24
K1 (C60)
SPOC
Occupation Setpoint
Deg C
20
10 to 30
K2 (C61)
SPNO
Non-Occupation Setpoint
Deg C
10
5 to 30
K3 (C62)
SPSV
Supervised Setpoint from Master Controller
Deg C
-
0 to 30
K4 (C63)
SPRH
Humidity protection setpoint (Not used in this application)
Deg C
0
0 to 95
K5 (C64)
MXOS
Maximum Optimum Start time
hours
6
1 to 24
K6 (C65)
MXOF
Maximum Optimum Stop time
hours
2
0 to 4
K7 (C66)
NOSV
Non Occupied Supervised setpoint
Deg C
0
0 to 30
 
 
Engineering Parameters; only accessible via Doorway and InSite
 
 
 
C90
NOAL
No alarms; all alarms cleared when set to 1
-
-
0 or 1
C91
SENF
Sensor fail alarm (when set to 1)
-
-
0 or 1
C92
RPVF
Remote PV fail alarm (when set to 1)
-
-
0 or 1
C93
STOP
Stop alarm received (when set to 1)
-
-
0 or 1
 
 
* 24 hour plots available for these values by default
 
 
 
 
 
Plotting interval and plotted variable changeable via Doorway or InSite
 
 
 

 

 