Doorway / InSite Code |
Label |
Description |
Units |
Default Value |
Range |
C1 |
SACT
|
Sensor Action
0: Use input 5-6 temp for Pool temp sensor, input 3-4 for
VFC
1: Use average of valid sensor values
2: Use maximum of valid sensor values
3: Use minimum of valid sensor values
4: Use remote sensor as Occupation input , shorted is occupied
5: Use networked temperature (nviRemoteTemp) if valid, else remote hardwired
if valid, else local
6: Use remote sensor as PIR input, shorted is occupied with close control.
open circuit is standby or non-occupied according to zone occupancy pattern
|
- |
0 |
0 to 6 |
C2 |
SCAL
|
Calibrate sensor value
|
Deg C |
0 |
-5 to 5 |
C3 |
SPMD
|
Midpoint of absolute setpoint adjustment range
|
Deg C |
30 |
5 to 95 |
C4 |
SPRG
|
Range of absolute setpoint adjustment about midpoint
|
Deg C |
5 |
0 to 10 |
C5 |
SPDB
|
Setpoint deadband between heating and cooling setpoints. If zero disables
cooling |
Deg C |
0 |
0 to 10 |
C6 |
SBDB
|
Additional deadband used in Standby Mode and Optimum off
|
Deg C |
2 |
0 to 10 |
C7 |
SPTY
|
Setpoint type
0: use local setpoint
1: use remote setpoint (from supervising Zone Controller), disable local
OSS |
- |
0 |
0 to 1 |
C8 |
XHRS
|
Extension hours when override pressed outside occupation
|
Hrs |
1 |
0 to 8 |
C9 |
FRSE
|
Fabric/frost rise; added to SPNO to form termination temperature for
heating run if temperature dips below SPNO value during non-occupation
|
Deg C |
0 |
0 to 10 |
C10 |
MIND |
Minimum demand to maintain Occupancy output for pump |
% |
0 |
0 to 10 |
C11 |
OCCO
|
Run during occupancy only
0: run during occupancy, OSS and frost
1: run during ocupancy only |
- |
0 |
0 to 1 |
C12 |
HPRD |
Heating valve period or minimum on time
|
Secs/10 |
- |
1 to 60 |
C13 |
HDLY |
Heating Interlock Delay
negative value delays fan (or pump) after heating starts
positive value cause run on of fan after heating shuts down
|
Mins |
0 |
-30 to 30 |
C14 |
CPRD
|
Cooling valve period or minimum on time
|
Secs/10 |
- |
1 to 60 |
C15 |
CDLY
|
Cooling Interlock delay
negative value delays fan (or pump) after cooling starts
positive value cause run on of fan after cooling shuts down
|
Mins |
0 |
-30 to 30 |
C16 |
FPRD |
Not used in this application |
Secs/10 |
12 |
1 to 60 |
C17 |
FRPT
|
Frost protect
0: no action
1: open heating valve 50%
2: open heating valve and run pump/fan |
- |
0 |
0 to 2 |
C18 |
MANL
|
Manual level , from Doorway
|
% |
0 |
-100 to 100 |
C19 |
ALRM
|
Alarm mode
0: Ignore alarms
1: Report alarms
2: Report alarms, shut down all outputs on alarm
3: Report alarms, shut down all outputs on STOP alarm or sensor fail alarm
|
- |
1 |
0 to 3 |
C20 |
ALST |
Alarm report sense
0: Alarm if input = 0 (contact open), healthy if input = 1 (closed)
1: Alarm if input = 1 (contact closed), healthy if input = 0 (open) |
- |
0 |
0 to 1 |
C21 |
HTSC |
Heat Source; points Energy Demand to source of Heating energy |
- |
1 |
0 to 8255 |
C22 |
CLSC |
Not used in this application |
|
0 |
0 to 8255 |
C23 |
OCDS |
Occupation Destination:
points Occupancy Demand at another controller |
- |
0 |
0 to 8255 |
C24 |
HTCT |
Setpoint selector
0: send Heating Demand signal as %
>0: CT Setpoint, send Heating Demand as CT setpoint only accepted by
Primary Boiler Controller set temperature required from boiler (for CT
Circuit Control) |
Deg C |
0 |
0 to 100 |
C25 |
CLCT |
Reserved for future use
|
Deg C |
0 |
0 to 20 |
C26 |
ISS3 |
Set to force single domain operation (should only be needed when using
issue 3 Floor Controllers) |
- |
0 |
0 to 1 |
Doorway / InSite Code |
Label |
Description |
Units |
Default Value |
Range |
I1 (C30)
|
FRST
|
Frost Protection Mode (SPNO violated)
|
- |
- |
0 to 1 |
I2 (C31)
|
OCC
|
Occupied
|
- |
- |
0 to 1 |
I3 (C32)
|
OSRT
|
Optimum Start in operation
|
- |
- |
0 to 1 |
I4 (C33)
|
OOFF |
Optimum Off in operation
|
- |
- |
0 to 1 |
I5 (C34)
|
COOL |
Controller in cooling mode
|
- |
- |
0 to 1 |
I6 (C35)
|
COND |
Condensation detected |
- |
- |
0 to 1 |
I8 (C37)
|
XOCC |
External Occupation signal
|
- |
- |
0 to 1 |
W1 (C38)
|
AUTO
|
Automatic/Manual Status
|
- |
- |
0 to 1 |
W2 (C39)
|
OVRD
|
Override
|
- |
- |
0 to 1 |
W5 (C42) |
HAND
|
Manual Hand; use with MANL to set output level
|
- |
0
|
0 to 1 |
W8 (C45)
|
CGST
|
Configuration Mode Status
|
- |
- |
0 to 1 |
S1* (C50) |
ROOM |
Controller measured temperature
|
Deg C
|
- |
5 to 30 |
S2* (C51)
|
DMND
|
Control Demand
|
%
|
- |
-100 to 100 |
S3 (C52)
|
REQD
|
Controller current setpoint
|
Deg C
|
- |
5 to 30 |
S4 (C53)
|
HTOP
|
Heating Output to driver
|
%
|
- |
0 to 100 |
S5 (C54) |
CLOP
|
Cooling Output to driver
|
% |
- |
0 to 100 |
S6 (C55)
|
RHUM |
Relative Humidity (Not used in this application)
|
% |
- |
0 to 100 |
S7 (C56)
|
OPST |
Last Optimum Start time
|
hours
|
- |
0 to 24 |
S8 (C57) |
OPOK |
Last Optimum Start complete (OK) |
hours
|
- |
0 to 24 |
K1 (C60)
|
SPOC
|
Occupation Setpoint
|
Deg C |
20 |
10 to 30 |
K2 (C61) |
SPNO
|
Non-Occupation Setpoint
|
Deg C |
10 |
5 to 30 |
K3 (C62)
|
SPSV
|
Supervised Setpoint from Master Controller |
Deg C |
- |
0 to 30 |
K4 (C63) |
SPRH |
Humidity protection setpoint (Not used in this application) |
Deg C |
0 |
0 to 95 |
K5 (C64) |
MXOS
|
Maximum Optimum Start time
|
hours
|
6 |
1 to 24 |
K6 (C65)
|
MXOF
|
Maximum Optimum Stop time
|
hours
|
2 |
0 to 4 |
K7 (C66) |
NOSV |
Non Occupied Supervised setpoint |
Deg C |
0 |
0 to 30 |
|
|
Engineering Parameters; only accessible via Doorway
and InSite |
|
|
|
C90
|
NOAL
|
No alarms; all alarms cleared when set to 1
|
- |
- |
0 or 1 |
C91
|
SENF
|
Sensor fail alarm (when set to 1) |
- |
- |
0 or 1 |
C92
|
RPVF
|
Remote PV fail alarm (when set to 1) |
- |
- |
0 or 1 |
C93
|
STOP
|
Stop alarm received (when set to 1) |
- |
- |
0 or 1 |
|
|
* 24 hour plots available for these values by default |
|
|
|
|
|
Plotting interval and plotted variable changeable
via Doorway or InSite |
|
|
|