Feature
Notes

Configuration Tables

Wiring

 

 

Floor Controller

with 6 x Relay Outputs

Configuration Tables

Doorway / InSite Code

Label

Description

Units

Default Value

Range

C1
SACT
Sensor Action; sets pre-processing for temperature input:
0: if a sensor is fitted to inputB use that in preference to input A otherwise use which ever input has a valid value.
1: average of valid sensor values
2: maximum of valid sensor values
3: minimum of valid sensor values
The value selected here is used for control and passed to Zone, FCU and AHU unit for use as the medium temperature. This selection is important on Two Pipe systems.
-
0
0 to 3
C2
SPTY
Setpoint Type, control mode:
1: Driver only
2: Off Coil temperature control, Heat/Cool demands from Zone Controllers and/or Fan Coils derive a setpoint using MAXH, MINH, MAXC, MINC
-
0
0 to 2
C3
INMD
Input Mode for use of terminals 13-14:
0: Feature disabled
1: External occupation (input linked = Occupied) AND with internal Occupation
2: External occupation (input linked = Occupied) OR with internal Occupation
3: External Occupation signal only
4: Alarm input
5: Rivermill Project Heat Pump fan speed switch
-
0
0 to 5
C4
MAXH
Maximum Supply Heating setpoint (used with SPTY = 2)
Deg C
30
0 to 90
C5
MINH
Minimum Supply Heating setpoint (used with SPTY = 2)
Deg C
20
0 to 90
C6
MAXC
Maximum Supply Cooling setpoint (used with SPTY = 2)
Deg C
18
2 to 30
C7
MINC
Minimum Supply Heating setpoint (used with SPTY = 2)
Deg C
10
2 to 30
C8
MIND
Supply minimum demand, used for switching between heating and cooling
%
4
0 to 10
C9
OCCO
When set controller will only run during the occupied period
-
0
0 to 1
C10
HPRD
Heating period, stroke time of valve or minimum on time
Secs/10
-
1 to 60
C11
HDLY
Not used in this application
Mins
0
-30 to 30
C12
CPRD
Cooling period, stroke time of valve or minimum on time
Secs/10
-
1 to 60
C13
CDLY
Not used in this application
Mins
0
-30 to 30
C14
FPRD
Not used in this application
Secs/10
12
1 to 60
C15
FRPT
Frost protection:
0: no action
1: open heating valve 50%
2: open heating valve and run pump/fan
-
0
0 to 2
C16
MANL
Manual level , from Doorway
%
0
-100 to 100
C17
ALRM
Alarm mode:
0: ignore alarms
1: report alarms
2: report alarms, shut down all outputs on alarm
3: report alarms, shut down all outputs on STOP alarm or sensor fail alarm
-
1
0 to 3
C18
ALST
Defines the state of the input which is considered to be the alarm condition
-
0
0 to 1
C19
TRND
When set sends Heat Demand, Cool Demand and Outside Temperature to SLT for onward transmission to TREND outstation(s) (see Serial Adaptor for details)
-
0
0 to 1
C20
DOMN
Domain setting
-
1
0 to 8
C21
HTSC
Heat source; points Energy Demand to source of Heat energy
-
0
0 to 8250
C22
CLSC
Cool source; points Energy Demand to source of Cool energy
-
0
0 to 8250
C23
OCDS
Occupation destination; points Occupancy Demand at another controller
-
0
0 to 8250
C24
HTCT
When set defines the CT setpoint which will be sent to this modules heat source. Only set if demanding heat from the primary side of a Boiler controller
Deg C
0
0 to 100
C25
CLCT
Not used in this application
Deg C
0
0 to 20

Monitoring Parameters

Doorway / InSite Code

Label

Description

Units

Default Value

Range

I1 (C30)
INPA
Input A occupation/window contact
-
-
0 to 1
I2 (C31)
INPB
Input B
-
-
0 to 1
I3 (C32)
RLYA
Relay A (heating stage 1)
-
-
0 to 1
I4 (C33)
RLYB
Relay B (heating stage 2)
-
-
0 to 1
I5 (C34)
RLYC
Relay C (heating stage 3)
-
-
0 to 1
I6 (C35)
RLYD
Relay D (cooling stage 1)
-
-
0 to 1
I7 (C36)
RLYE
Relay E (cooling stage 2)
-
-
0 to 1
I8 (C37)
RLYF
Relay F (cooling stage 3)
-
-
0 to 1
W1 (C38)
AUTO
Automatic/Manual Status
-
-
0 to 1
W2 (C39)
OVRD
Override
-
-
0 to 1
W3 (C40)
MISN
Generate an alarm if any node detected as missing
-
0
0 to 1
W4 (C41)
RPLN
When registering a new node replace missing nodes
-
1
0 to 1
W5 (C42)
HAND
Manual Hand; use with MANL to set output level
-
0
0 to 1
W7 (C44)
SERV
Service Pin Msg (to Doorway +InSite, self resetting)
-
0
0 to 1
W8 (C45)
CGST
Configuration Mode Status
-
-
0 to 1
S1* (C50)
SPLA
Supply Temperature
Deg C
-
5 to 35
S2* (C51)
RTNA
Return Temperature
Deg C
-
5 to 35
S3 (C52)
HCOP
Heat Cool Output to Drivers (cooling negative)
%
-
-100 to 100
S4 (C53)
SPSL
Supply Setpoint
Deg C
-
5 to 35
S5 (C54)
HDMD
Heat Demand from return loop or from Zone Controller
%
-
0 to 100
S6 (C55)
CDMD
Cool Demand from return loop or from Zone Controller
%
-
0 to 100
S7 (C56)
OUTH
Outside Humidity; monitoring only from intelligent TRH sensor
%
-
0 to 100
 
 
Engineering Parameters; only accessible via Doorway and InSite
 
 
 
C90
NOAL
No alarms ; all alarms cleared when set to 1
-
-
0 or 1
C91
SENF
Sensor fail alarm (when set to 1)
-
-
0 or 1
C92
EXTN
External alarm input (when set to 1)
-
-
0 or 1
C93
STOP
Stop alarm received (when set to 1)
-
-
0 or 1
 
 
* 24 hour plots available for these values by default
 
 
 
 
 