Doorway / InSite Code |
Label |
Description |
Units |
Default Value |
Range |
C1 |
SACT
|
Sensor Action; sets pre-processing for temperature input:
0: if a sensor is fitted to inputB use that in preference to input A otherwise
use which ever input has a valid value.
1: average of valid sensor values
2: maximum of valid sensor values
3: minimum of valid sensor values
The value selected here is used for control and passed to Zone, FCU
and AHU unit for use as the medium temperature. This selection is important
on Two Pipe systems.
|
- |
0 |
0 to 3 |
C2 |
SPTY |
Setpoint Type, control mode:
1: Driver only
2: Off Coil temperature control, Heat/Cool demands from Zone Controllers
and/or Fan Coils derive a setpoint using MAXH, MINH, MAXC, MINC |
- |
0 |
0 to 2 |
C3 |
INMD |
Input Mode for use of terminals 13-14:
0: Feature disabled
1: External occupation (input linked = Occupied) AND with internal Occupation
2: External occupation (input linked = Occupied) OR with internal Occupation
3: External Occupation signal only
4: Alarm input
5: Rivermill Project Heat Pump fan speed switch |
- |
0 |
0 to 5 |
C4 |
MAXH |
Maximum Supply Heating setpoint (used with SPTY =
2) |
Deg C |
30 |
0 to 90 |
C5 |
MINH |
Minimum Supply Heating setpoint (used with SPTY =
2) |
Deg C |
20 |
0 to 90 |
C6 |
MAXC |
Maximum Supply Cooling setpoint (used with SPTY =
2) |
Deg C |
18 |
2 to 30 |
C7 |
MINC |
Minimum Supply Heating setpoint (used with SPTY =
2) |
Deg C |
10 |
2 to 30 |
C8 |
MIND |
Supply minimum demand, used for switching between
heating and cooling |
% |
4 |
0 to 10 |
C9 |
OCCO |
When set controller will only run during the occupied
period
|
- |
0 |
0 to 1 |
C10 |
HPRD |
Heating period, stroke time of valve or minimum on
time |
Secs/10 |
- |
1 to 60 |
C11 |
HDLY |
Not used in this application |
Mins |
0 |
-30 to 30 |
C12 |
CPRD |
Cooling period, stroke time of valve or minimum on
time |
Secs/10 |
- |
1 to 60 |
C13 |
CDLY |
Not used in this application |
Mins |
0 |
-30 to 30 |
C14 |
FPRD |
Not used in this application |
Secs/10 |
12 |
1 to 60 |
C15 |
FRPT |
Frost protection:
0: no action
1: open heating valve 50%
2: open heating valve and run pump/fan
|
- |
0 |
0 to 2 |
C16 |
MANL |
Manual level , from Doorway |
% |
0 |
-100 to 100 |
C17 |
ALRM |
Alarm mode:
0: ignore alarms
1: report alarms
2: report alarms, shut down all outputs on alarm
3: report alarms, shut down all outputs on STOP alarm or sensor fail alarm
|
- |
1 |
0 to 3 |
C18 |
ALST |
Defines the state of the input which is considered
to be the alarm condition |
- |
0 |
0 to 1 |
C19 |
TRND |
When set sends Heat Demand, Cool Demand and Outside
Temperature to SLT for onward transmission to TREND outstation(s) (see
Serial Adaptor for details) |
- |
0 |
0 to 1 |
C20 |
DOMN |
Domain setting
|
- |
1 |
0 to 8 |
C21 |
HTSC |
Heat source; points Energy Demand to source of Heat
energy |
- |
0 |
0 to 8250 |
C22 |
CLSC |
Cool source; points Energy Demand to source of Cool
energy |
- |
0 |
0 to 8250 |
C23 |
OCDS |
Occupation destination; points Occupancy Demand at
another controller |
- |
0 |
0 to 8250 |
C24 |
HTCT |
When set defines the CT setpoint which will be sent
to this modules heat source. Only set if demanding heat from the primary
side of a Boiler controller |
Deg C |
0 |
0 to 100 |
C25 |
CLCT |
Not used in this application |
Deg C |
0 |
0 to 20 |
Doorway / InSite Code |
Label |
Description |
Units |
Default Value |
Range |
I1 (C30)
|
INPA |
Input A occupation/window contact |
- |
- |
0 to 1 |
I2 (C31)
|
INPB |
Input B |
- |
- |
0 to 1 |
I3 (C32)
|
RLYA |
Relay A (heating stage 1) |
- |
- |
0 to 1 |
I4 (C33)
|
RLYB |
Relay B (heating stage 2) |
- |
- |
0 to 1 |
I5 (C34)
|
RLYC |
Relay C (heating stage 3) |
- |
- |
0 to 1 |
I6 (C35)
|
RLYD |
Relay D (cooling stage 1) |
- |
- |
0 to 1 |
I7 (C36) |
RLYE |
Relay E (cooling stage 2) |
- |
- |
0 to 1 |
I8 (C37)
|
RLYF |
Relay F (cooling stage 3) |
- |
- |
0 to 1 |
W1 (C38)
|
AUTO
|
Automatic/Manual Status
|
- |
- |
0 to 1 |
W2 (C39)
|
OVRD
|
Override
|
- |
- |
0 to 1 |
W3 (C40) |
MISN |
Generate an alarm if any node detected as missing |
- |
0 |
0 to 1 |
W4 (C41) |
RPLN |
When registering a new node replace missing nodes |
- |
1 |
0 to 1 |
W5 (C42) |
HAND
|
Manual Hand; use with MANL to set output level
|
- |
0
|
0 to 1 |
W7 (C44)
|
SERV
|
Service Pin Msg (to Doorway +InSite, self resetting)
|
- |
0 |
0 to 1 |
W8 (C45)
|
CGST
|
Configuration Mode Status
|
- |
- |
0 to 1 |
S1* (C50) |
SPLA |
Supply Temperature |
Deg C
|
- |
5 to 35 |
S2* (C51)
|
RTNA |
Return Temperature |
Deg C |
- |
5 to 35 |
S3 (C52)
|
HCOP |
Heat Cool Output to Drivers (cooling negative) |
% |
- |
-100 to 100 |
S4 (C53)
|
SPSL |
Supply Setpoint |
Deg C |
- |
5 to 35 |
S5 (C54) |
HDMD |
Heat Demand from return loop or from Zone Controller |
% |
- |
0 to 100 |
S6 (C55)
|
CDMD |
Cool Demand from return loop or from Zone Controller |
% |
- |
0 to 100 |
S7 (C56)
|
OUTH
|
Outside Humidity; monitoring only from intelligent
TRH sensor |
% |
- |
0 to 100 |
|
|
Engineering Parameters; only accessible via Doorway
and InSite |
|
|
|
C90 |
NOAL
|
No alarms ; all alarms cleared when set to 1
|
- |
- |
0 or 1 |
C91 |
SENF
|
Sensor fail alarm (when set to 1)
|
- |
- |
0 or 1 |
C92 |
EXTN
|
External alarm input (when set to 1)
|
- |
- |
0 or 1 |
C93 |
STOP
|
Stop alarm received (when set to 1)
|
- |
- |
0 or 1 |
|
|
* 24 hour plots available for these values by default |
|
|
|
|
|
Plotting interval and plotted variable changeable
via Doorway or InSite |
|
|
|