Feature
|
Configuration Tables |
Wiring |
|
|
Doorway / InSite Code |
Label |
Description |
Units |
Default Value |
Range |
C1 |
ALRM |
Alarm Mode
|
- |
1 |
0 to 3 |
C2 |
ALST |
Alarm State
|
- |
1 |
0 to 1 |
C3 |
ENBA |
Enable Boiler A |
- |
1 |
0 to 1 |
C4 |
ENBB |
Enable Boiler B |
- |
1 |
0 to 1 |
C5 |
CNDA |
Boiler A Condensing |
- |
0 |
0 to 1 |
C6 |
CNDB |
Boiler B Condensing |
- |
0 |
0 to 1 |
C7 |
MBLR |
Modulating Boiler |
- |
1 for AOP version |
0 to 1 |
|
|
|
Analogue Output version only |
|
|
|
C8 |
HRMX |
Heat re-scale maximum |
% |
100 |
0 to 100 |
C9 |
HRMN |
Heat re-scale minimum |
% |
0 |
0 to 100 |
C10 |
MXVA |
Maximum output voltage channel A |
volt |
10.0 |
0 to 10.0 |
C11 |
MNVA |
Minimum output voltage channel A |
volt |
0.0 |
0 to 10.0 |
C12 |
MXVB |
Maximum output voltage channel B |
volt |
10.0 |
0 to 10.0 |
C13 |
MNVB |
Minimum output voltage channel B |
volt |
0.0 |
0 to 10.0 |
Doorway / InSite Code |
Label |
Description |
Units |
Default Value |
Range |
I1 (C30) |
INPA |
External input a status |
- |
- |
0 to 1 |
I2 (C31) |
INPB |
External input b status |
- |
- |
0 to 1 |
I6 (C35) |
RLYA |
Status of output a |
- |
- |
0 to 1 |
I7 (C36) |
RLYB |
Status of output b |
- |
- |
0 to 1 |
I8 (C37) |
RLYC |
Status of output c |
- |
- |
0 to 1 |
W1 (C38) |
AUTO |
Automatic Mode |
- |
- |
0 to 1 |
W2 (C39) |
OVRD |
Override mode |
- |
- |
0 to 1 |
W5 (C42) |
HAND |
Manual HAND mode |
- |
- |
0 to 1 |
W7 (C44) |
SERV |
generate service pin message |
- |
0 |
0 to 1 |
|
|
|
Engineering Parameters; only accessible via Doorway and InSite |
|
|
|
C90 |
NOAL |
No Alarms; all alarms cleared when set to 1 |
- |
- |
0 or 1 |
C91 |
GENA |
General Alarm input a (when set to 1) |
- |
- |
0 or 1 |
C92 |
GENB |
General Alarm input b (when set to 1) |
- |
- |
0 or 1 |
C93 |
LOKA |
Lockout Alarm Boiler A (when set to 1) |
- |
- |
0 or 1 |
C94 |
LOKB |
Lockout Alarm Boiler B (when set to 1) |
- |
- |
0 or 1 |