Feature
|
Configuration Tables |
Wiring |
|
|
Boiler Controller
|
|
Doorway / InSite Code |
Label |
Description |
Units |
Default Value |
Range |
C1 |
FRST |
Frost Protection / Non Occupied Setpoint |
Deg C |
3 |
2 to 15 |
C2 |
MAXF |
Maximum Primary Setpoint |
Deg C |
80 |
30 to 110 |
C3 |
MINR |
Minimum Return Setpoint |
Deg C |
40 |
10 to 50 |
C4 |
FLAV |
This parameter is associated with the weather compensated VT circuit and determines the flow temperature when the outside temperature is 10C. |
Deg C |
50 |
20 to 100 |
C5 |
SACT |
Sensor Action for controlling the boiler temperature.
|
- |
1 |
0 to 3 |
C6 |
BLRS |
Number of boilers in sequence |
- |
2 |
1 to 8 |
C7 |
MXVT |
Maximum VT circuit water temperature |
Deg C |
80 |
20 to 100 |
C8 |
VLIM |
Limits the opening of VT valve if return temp is below MINR
|
% |
100 |
0 to 100 |
C9 |
DHWP |
Hot Water Priority:
|
- |
0 |
0 to 1 |
C10 |
MIN |
Boiler minimum run time |
Mins |
5 |
1 to 20 |
C11 |
BRON |
Pump run-on period for the boiler primary pump |
Mins |
5 |
0 to 30 |
C12 |
PERD |
VT valve stroke time. This parameter determines the stroke time of the valve actuator fitted to the VT valve. It is recommended that the valve stroking process is carried out manually to ensure the stroke time is calculated accurately |
Secs/10 |
18 |
2 to 60 |
C13 |
TRNG |
Maximum trim effect on heating setpoint |
Deg C |
10 |
0 to 20 |
C14 |
CRNG |
Maximum adaptive effect on heating setpoint |
Deg C |
10 |
0 to 20 |
C15 |
MODE |
Mode select:
|
- |
0 |
0 to 2 |
C16 |
BLOK |
Number of boiler stages available to run (i.e. not locked out) |
- |
read only |
0 to 8 |
C17 |
AREM |
All boilers remote
|
- |
0 |
0 to 1 |
C18 |
SMRT |
Summer heating inhibit if outside temperature is greater than the SMRT parameter. This feature is used to automatically disable the VT circuit when the outside temperature reaches or exceeds the SMRT setting. |
Deg C |
20 |
10 to 30 |
C19 |
MIND |
Minimum Demand for Boiler Controller to operate
|
% |
2 |
0 to 10 |
C20 |
COMP |
Compensator offset |
Deg C |
0 |
-50 to 50 |
C21 |
ALRM |
Alarm Mode
|
- |
0 |
0 to 5 |
C22 |
ALST |
Alarm report sense
|
- |
1 |
0 to 1 |
C23 |
DOMN |
Own Domain (for SH types only) |
- |
0 |
0 to 8 |
C24 |
TYPE |
This setting determines the type of boiler used.
|
- |
1 |
0 to 3 |
C25 |
MNVF |
Minimum VT Flow: used to ensure a minimum opening on the VT valve while the boilers are running. This only needs to be used when the Boiler does not have a pumped primary circuit or shunt circuit. |
% |
0 |
0 to 100 |
C26 |
DMOR |
Demand Override:
|
- |
0 |
0 or 1 |
Monitoring Parameters |
|||||
Doorway / InSite Code |
Label |
Description |
Units |
Default Value |
Range |
I1 (C30) |
INPA |
External input a status |
- |
- |
0 to 1 |
I2 (C31) |
INPB |
External input b status |
- |
- |
0 to 1 |
I3 (C32) |
BLRA |
Boiler 1 output status |
- |
- |
0 to 1 |
I4 (C33) |
BLRB |
Boiler 2 output status |
- |
- |
0 to 1 |
I5 (C34) |
PPMP |
Primary pump output status |
- |
- |
0 to 1 |
I6 (C35) |
VTOP |
VT valve open output status |
- |
- |
0 to 1 |
I7 (C36) |
VTCL |
VT valve close output status |
- |
- |
0 to 1 |
I8 (C37) |
VPMP |
Secondary pump output status |
- |
- |
0 to 1 |
W1 (C38) |
AUTO |
Automatic/Manual Status |
- |
- |
0 to 1 |
W2 (C39) |
OVRD |
Override |
- |
- |
0 to 1 |
W3 (C40) |
SHOF |
Summer heating (inhibited if SHOF = 1) |
- |
read only |
0 to 1 |
W4 (C41) |
ZBST |
Zone boost (disabled if ZBST = 0) |
- |
1 |
0 to 1 |
W5 (C42) |
HAND |
Manual HAND mode |
- |
0 |
0 to 1 |
W6 (C43) |
RPLN |
Replace missing nodes in Database (for SH types only) |
- |
1 |
0 to 1 |
W7 (C44) |
SERV |
Service Pin Msg (to Doorway +InSite, self resetting) |
- |
- |
0 to 1 |
W8 (C45) |
CGST |
Configuration Mode Status |
- |
- |
0 to 1 |
S1* (C50) |
FLOW |
Flow Temperature |
Deg C |
- |
- |
S2* (C51) |
RTRN |
Return Temperature |
Deg C |
- |
- |
S3* (C52) |
VTMP |
VT circuit Temperature |
Deg C |
- |
- |
S4* (C53) |
OUTS |
Outside Temperature (logged in SH types only) |
Deg C |
- |
- |
S5 (C54) |
FLSP |
Primary Temperature Setpoint |
Deg C |
- |
- |
S6 (C55) |
BLOP |
Boiler Output |
% |
- |
- |
S7 (C56) |
VTPN |
VT Valve Position |
% |
- |
- |
S8 (C57) |
ZDMD |
Maximum Zone Demand |
% |
- |
- |
S9 (C58) |
VTSP |
VT Setpoint |
Deg C |
- |
- |
K1 (C60) |
MAXF |
Maximum Primary Setpoint |
Deg C |
80 |
0 to 100 |
K2 (C61) |
MINR |
Minimum Return Setpoint |
Deg C |
40 |
0 to 100 |
Engineering Parameters; only accessible via Doorway and InSite |
|||||
C83 |
MANL |
Used with W5 HAND to position VT Valve manually
|
% |
0 |
0 to 100 |
C90 |
NOAL |
No Alarms; all alarms cleared when set to 1 |
- |
- |
0 or 1 |
C91 |
GENA |
General Alarm input a (when set to 1) |
- |
- |
0 or 1 |
C92 |
GENB |
General Alarm input b (when set to 1) |
- |
- |
0 or 1 |
C93 |
LOKA |
Lockout Alarm Boiler 1 (when set to 1) |
- |
- |
0 or 1 |
C94 |
LOKB |
Lockout Alarm Boiler 2 (when set to 1) |
- |
- |
0 or 1 |
C95 |
FREZ |
Danger of freezing (when set to 1) |
- |
|
0 or 1 |
C96 |
STOP |
STOP alarm (when set to 1) |
- |
- |
0 or 1 |
C97 |
OUTF |
Outside temperature failed (when set to 1) |
- |
- |
0 or 1 |
C98 |
FROS |
Frost protection stage 3 in progress (when set to 1) |
- |
- |
0 or 1 |
C99 |
PMPF |
Pump Failure (PCO Submodule) |
- |
- |
0 or 1 |
C150 |
MNVO |
Minimum Variable Output :sets lowest level to run modulating Boilers |
% |
20 |
0 to 100 |
C151 |
MXPL |
Run Maximum number of Condensing Boilers in Parallel |
- |
0 |
0 to 1 |
| * 24 hour plots available for these values by default | |||||
| Plotting interval and plotted variable changeable via Doorway or InSite | |||||