Light Commercial Boiler Controller

Configuration Tables

Doorway / InSite Code

Label

Description

Units

Default Value

Range

C1
HWSP
Domestic Hot water setpoint
Deg C
55
25 to 65
C2
FRST
Frost protection level, can disabled by setting FRST = 0 (see Data Sheet for details)
Deg C
3
2 to 15
C3
MAXF
Maximum flow water temperature
Deg C
80
30 to 110
C4
MINR
Minimum return water temperature
Deg C
40
10 to 50
C5
FLAV
Flow Temperature for 10°C outside temperature
Deg C
50
20 to 100
C6
SACT
Sensor Action
0: Use flow or return, or average if both sensors valid
1: Use flow sensor value
2: Use return sensor value
3: Use average of flow and return sensor values
-
1
0 to 3
C7
BLRS
Number of boilers in sequence
-
2
1 to 8
C8
NPMP
Total number of pumps
-
1
1 to 2
C9
MXVT
Maximum VT circuit water temperature
Deg C
60
20 to 100
C10
HWRO
Domestic hot water run-on length of time hot water is extended past heating occupation stop time. (e.g. Cleaners, etc)
Mins
0
0 to 12
C11
DHWP
Domestic Hot Water Priority:
0: Hot water and heating have equal priority
1: VT valve closes when DHW is demanding heat
-
0
0 to 1
C12
MIN
Boiler minimum run time
Mins
5
1 to 20
C13
BRON
Primary pump run on time
Mins
1
0 to 30
C14
PERD
VT valve stroke time
Secs/10
18
2 to 60
C15
TRNG
Maximum trim effect on heating setpoint
Deg C
10
0 to 20
C16
CRNG
Maximum adaptive effect on heating setpoint
Deg C
10
0 to 20
C17
MODE
Zone actuator/valves operation: (MODE
0: actuators/valves match their zone heat demand
1: zone with highest heating demand sets actuator/valve 100%, other zones ratio output dependant on their heat demand. All actuators/valves open fully in BRON period (heat dissipation)
-
0
0 to 1
C18
BLOK
Number of boiler stages available to run (i.e. not locked out)
-
read only
0 to 8
C19
AREM
All boilers remote
0: Boiler outputs on controller included in sequence
1: All boiler stages via cascade modules
Boiler Controller outputs disabled
-
0
0 to 1
C20
SMRT
Summer heating inhibit if outside temperature > SMRT
Deg C
20
10 to 30
C21
MIND
Minimum Demand for Boiler Controller to operate
0: When demand drops to zero, boilers and pumps continue to run
MIND > 1: When demand drops to zero, boilers and pumps stop
%
2
0 to 10
C22
COMP
Compensator offset
Deg C
0
-50 to 50
C23
ALRM
Alarm Mode
0: Ignore alarms
1: Disable Boiler outputs, no alarm (maintenance switches)
2: Report all alarms, continue running (lockout alarms)
3: Report all alarms, continue running (general alarms)
4: Report all alarms, shut down on STOP alarm only
-
0
0 to 4
C24
ALST
Alarm report sense
0: Alarm if input = 0 (contact open)
1: Alarm if input = 1 (contact closed)
-
1
0 to 1
C25
TYPE
Output type : Not available from Zone Controller (Doorway only). Factory set to:
1 = Auto Rotation of stages (/001 version only)
3 = Fixed sequencing of stages (/003 version only)
-
1
0 to 8

Monitoring Parameters

Doorway / InSite Code

Label

Description

Units

Default Value

Range

I1 (C30)
INPA
External input ‘a’ status
-
-
0 to 1
I2 (C31)
INPB
External input ‘b’ status
-
-
0 to 1
I3 (C32)
BLRA
Boiler 1 output status
-
-
0 to 1
I4 (C33)
BLRB
Boiler 2 output status
-
-
0 to 1
I5 (C34)
PMPA
Pump 1 output status
-
-
0 to 1
I6 (C35)
PMPB
Pump 2 output status
-
-
0 to 1
I7 (C36)
HTOP
Heating output status
-
-
0 to 1
I8 (C37)
HWOP
Hot water output status
-
-
0 to 1
W1 (C38)
AUTO
Automatic/Manual Status
-
-
0 to 1
W2 (C39)
OVRD
Override
-
-
0 to 1
W3 (C40)
SHOF
Summer heating (inhibited if SHOF = 1)
-
read only
0 to 1
W4 (C41)
ZBST
Zone boost (disabled if ZBST = 0)
-
1
0 to 1
W6 (C43)
RPLN
Replace missing nodes in Database (for SH types only)
-
1
0 to 1
W7 (C44)
SERV
Service Pin Msg (to Doorway +InSite, self resetting)
-
-
0 to 1
W8 (C45)
CGST
Configuration Mode Status
-
-
0 to 1
S1* (C50)
FLOW
Flow Temperature
Deg C
-
-
S2* (C51)
RTRN
Return Temperature
Deg C
-
-
S3* (C52)
HWTP
Domestic hot water temperature
Deg C
-
-
S4* (C53)
OUTS
Outside Temperature (logged in SH types only)
Deg C
-
-
S5 (C54)
FLSP
Flow Temperature Setpoint
Deg C
-
-
S6 (C55)
BLOP
Boiler demand
%
-
-
S7 (C56)
HWOP
Domestic hot water demand
%
-
-
S8 (C57)
ZDMD
Maximum Zone Demand
%
-
-
K1 (C60)
MAXF
Maximum Flow Setpoint
Deg C
80
0 to 100
K2 (C61)
MINR
Minimum Return Setpoint
Deg C
40
0 to 100
K3 (C62)
HWSP
Domestic Hot Water Setpoint
Deg C
55
10 to 80
 
 
Engineering Parameters; only accessible via Doorway and InSite
 
 
 
C90
NOAL
No Alarms; all alarms cleared when set to 1
-
-
0 or 1
C91
GENA
General Alarm input ‘a’ (when set to 1)
-
-
0 or 1
C92
GENB
General Alarm input ‘b’ (when set to 1)
-
-
0 or 1
C93
LOKA
Lockout Alarm Boiler 1 (when set to 1)
-
-
0 or 1
C94
LOKB
Lockout Alarm Boiler 2 (when set to 1)
-
-
0 or 1
C95
FREZ
Danger of freezing (when set to 1)
-
-
0 or 1
C96
STOP
STOP alarm (when set to 1)
-
-
0 or 1
 
 
* 24 hour plots available for these values by default
 
 
 
 
 
Plotting interval and plotted variable changeable via Doorway or InSite
 
 
 