Main FeaturesIdeal for MTHW heating applicationsControls 2 MTHW Boilers and associated plantUp to 8 Boilers in one sequence using Boiler Cascade SubmodulesSelf adapting Weather CompensationSystem Housekeeping functionBoiler plant operates on demand from the building, not fixed time programme |
![]() |
Input 5-6 |
Flow Sensor (High Temperature) |
Input 7-8 |
Return Sensor (High Temperature) |
Input 9-10 |
Flow Sensor (Low Temperature) |
Input 11-12 |
Return Sensor (Low Temperature) |
Input 13-14 |
VT Sensor |
Input 15-16 |
Outside Sensor |
SACT = 0 |
Control on flow or return or average if both sensors valid |
SACT = 1 |
Control on Flow sensor only |
SACT = 2 |
Control on Return sensor only |
SACT = 3 |
Control on average of Flow and Return sensor values |
Fault |
Condition |
Indication |
Low temperature sensor fault (both flow and return) |
Boiler will not run |
Flow and Return temperature indicate 180°C & Error lamp will flash red |
High temperature sensor fault (both flow and return) |
Boiler operates at a reduced setpoint |
Flow Setpoint set to Maximum variable temperature circuit setpoint. FLSP = MXVT |


CRNG = 0 |
Disables Zone Trim and Adaption. |
TRNG = 0 |
Disables Zone Trim and Adaption. |
ZBST = 0 |
Disables Boost Mode. |
MIND = 0 |
Ensures VT pumps run constantly during occupancy. |
MODE = 0 |
Primary Pumps run for BRON period. |
MODE = 1 |
Primary and VT Pumps run on and VT Valve open for BRON period. |
MODE = 2 |
Primary and VT Pumps run on and VT Valve open and Zone valves overridden
to 100% for BRON period. |
NOAL |
No Alarms. |
SNFL |
Sensor Failure - see parameters I1 & I2 (C30 & C31) for details |
FREZ |
Danger of Freezing alarm. |
STOP |
System STOP alarm generated. |
OUTF |
Outside temperature Fail alarm. |
FROS |
Frost protection in progress. |
H |
Heat Source |
20 |
C |
Cool Source |
20 |
A |
AHU Controller |
50 |
Z |
Zones |
100 |
M |
Monitoring Modules |
25 |
S |
Communications |
4 |
R |
Routers |
4 |
Option |
Function |
Max Cascade Submodules |
Max PCO Submodules |
/ SH / 001 |
With duty and sequence rotation, with housekeeping |
4 |
3 |
/ SH / 003 |
With fixed sequence, with housekeeping |
4 |
3 |
/ NH / 004 |
With duty and sequence rotation, no housekeeping |
2 |
1 |
/ NH / 006 |
With fixed sequence, no housekeeping |
2 |
1 |