| Feature Notes |
Configuration Tables | Wiring |
Doorway / InSite Code |
Label |
Description |
Units |
Default Value |
Range |
C1 |
SPOC |
Occupied Setpoint |
- |
50 |
Rescalable |
C2 |
MXPV |
Maximum Sensor Scaling (value at 10V) |
- |
100 |
Rescalable |
C3 |
MNPV |
Minimum Sensor Scaling (value at 0V) |
- |
0 |
Rescalable |
C4 |
DPPV |
Decimal places for engineering scaling |
- |
1 |
0 to 4 |
C5 |
MXSP |
Maximum setpoint value |
- |
100 |
Rescalable |
C6 |
MNSP |
Minimum setpoint value |
- |
0 |
Rescalable |
C7 |
MNOP |
Minimum Output |
% |
5 |
5 to 100 |
C8 |
INVL |
Invert control sense
|
- |
0 |
0 to 1 |
C9 |
ELAG |
Percentage lag or lead for extract fan |
% |
0 |
-50 to 50 |
C10 |
HPRD |
Not used in this application |
Secs/10 |
0 |
1 to 60 |
C11 |
HDLY |
Not used in this application |
Mins |
0 |
-30 to 30 |
C12 |
CPRD |
Not used in this application |
Secs/10 |
0 |
1 to 60 |
C13 |
CDLY |
Not used in this application |
Mins |
0 |
-30 to 30 |
C14 |
MANL |
Manual level , from Doorway |
% |
0 |
0 to 100 |
C15 |
TYPE |
Fan type;
|
- |
1 |
1 to 2 |
C16 |
ACHL |
Analogue Channel select;
|
- |
2 |
1 to 2 |
C17 |
ALRM |
Alarm mode;
|
- |
0 |
0 to 3 |
C18 |
ALST |
Not used in this application |
|
|
|
C189 |
MXVA |
Maximum Voltage output a (for AOP types only) |
V |
10 |
0 to 10 |
C20 |
MNVA |
Minimum Voltage output a (for AOP types only) |
V |
0 |
0 to 10 |
C21 |
MXVB |
Maximum Voltage output b (for AOP types only) |
V |
10 |
0 to 10 |
C22 |
MNVB |
Minimum Voltage output b (for AOP types only) |
V |
0 |
0 to 10 |
Doorway / InSite Code |
Label |
Description |
Units |
Default Value |
Range |
I2 (C31) |
OCCD |
Occupied |
- |
- |
0 to 1 |
W1 (C38) |
AUTO |
Automatic/Manual Status |
- |
- |
0 to 1 |
W2 (C39) |
OVRD |
Override |
- |
- |
0 to 1 |
W3 (C40) |
POT |
When set specifies that special order potentiometer fitted, do not set unless your hardware has the potentiometer |
- |
0 |
0 to 1 |
W5 (C42) |
HAND |
Manual Hand; use with MANL to set output level |
- |
0 |
0 to 1 |
W7 (C44) |
SERV |
Service Pin Msg (to Doorway +InSite, self resetting) |
- |
- |
0 to 1 |
|
|
|
W1 and W2 used together with Doorway Auto/Manual dialog box |
|
|
|
S1* (C50) |
PVKP |
Pressure reading (or other measured value e.g CO2) |
- |
- |
Rescaleable |
S2* (C51) |
HCOP |
Controller output (shows demand to drivers,)
|
% |
- |
-100 to 100 |
S3 (C52) |
RQKP |
Controller current setpoint |
- |
- |
Rescaleable |
S4 (C53) |
DMND |
Demand to Fan Speed Control |
% |
- |
0 to 100 |
K1 (C60) |
SPOC |
Pressure setpoint |
- |
50 |
Rescaleable |
K2 (C61) |
DPPV |
Decimal point for re-scalable engineering units |
- |
1 |
0 to 4 |
K4 (C63) |
MXPV |
Maximum sensor scaling |
- |
100 |
Rescaleable |
K5 (C64) |
MNPV |
Minimum sensor scaling |
- |
0 |
Rescaleable |
K6 (C65) |
NPSD |
Night Purge Speed.If set to a non zero value the controller will drive the output to this value while its AHU is in Night Purge mode. Allows the full volume of the fans to be used when NIght cooling. |
% |
0 |
0 to 100 |
C90 |
NOAL |
No alarm |
- |
- |
0 to 1 |
C91 |
SENF |
Sensor fail |
- |
- |
0 to 1 |
C92 |
EXTN |
Alarm for external input |
- |
- |
0 to 1 |
C93 |
STOP |
STOP alarm received |
- |
- |
0 to 1 |
* 24 hour plots available for these values by default |
|||||
Plotting interval and plotted variable changeable via Doorway or InSite |