Air Handing Unit Damper Submodule
with 3 x Triac Outputs (3T version)
with 2 x 0-10V DC Outputs (AOP version with Air Quality control option)
Configuration Tables
| Doorway / InSite Code | Label | Description | Units | Default Value | Range |
| C1 | SACT |
Sensor Action; for future use; set to 0 for this application |
- | 0 | 0 to 3 |
| C2 | HPRD | Damper Stroke Time (3T version only) | Secs/10 | 18 | 1 to 240 |
| C3 | HDLY |
Interlock delay; for future use; set to 0 for this application |
Mins | 0 | -60 to 60 |
| C4 | MIND | Minimum demand; for future use, set to 4 for this application | % | 4 | 0 to 100 |
| C5 | MNFA |
Minimum Fresh air; sets Minimum Fresh air position of Damper |
% | 10 | 0 to 100 |
| C6 | MXAQ | Maximum Air Quality signal as Air Quality reaches MXAQ, dampers will reach 100% Fresh Air | % | 100 | 0 to 100 |
| C7 | MNAQ | Minimum Air Quality signal that will override Temperature Control; as Air Quality exceeds MNAQ, dampers will start to open | % | 20 | 0 to 100 |
| C8 | DMPC | Damper percent, when dampers used as a stage of the heating or cooling for the AHU this sets the percentage of the AHU demand which is utilied by the mixing dampers. Set to 0 to diable feature. | % | 0 | 0 to 50 |
C9 |
MANL |
Manual level , from Doorway |
% |
0 |
-100 to 100 |
| C10 | ALRM |
Alarm mode |
- | 1 | 0 to 3 |
| C11 | ALST | Alarm State; for future use; set to 0 for this application | - | 0 | 0 to 1 |
| C12 | MXVA | Maximum Voltage output a (for AOP types only) | V | 10 | 0 to 10 |
| C13 | MNVA | Minimum Voltage output a (for AOP types only) | V | 0 | 0 to 10 |
| C14 | MXVB | Maximum Voltage output b (for AOP types only) | V | 10 | 0 to 10 |
| C15 | MNVB | Minimum Voltage output b (for AOP types only) | V | 0 | 0 to 10 |
Monitoring Parameters
| Doorway / InSite Code | Label | Description | Units | Default Value | Range |
| I1 (C30) | FRST | Frost Protection Mode | - | - | 0 to 1 |
| I2 (C31) | OCCD | Occupied | - | - | 0 to 1 |
| I3 (C32) | OSRT | Optimim Start (not used in this application) | - | - | 0 to 1 |
| I5 (C34) | COOL | Cool Mode | - | - | 0 to 1 |
| I6 (C35) | RLYA | Triac A Status | - | - | 0 to 1 |
| I7 (C36) | RLYB | Triac B Status | - | - | 0 to 1 |
| I8 (C37) | RLYC | Triac C Status | - | - | 0 to 1 |
| W1 (C38) | AUTO | Automatic/Manual Status | - | - | 0 to 1 |
| W2 (C39) | OVRD | Override | - | - | 0 to 1 |
W5 (C42) |
HAND |
Manual Hand mode |
- |
0 |
0 to 1 |
W6 (C43) |
POT |
Potentiometer fitted to this board |
- |
0 |
0 to 1 |
W7 (C44) |
SERV |
Service Pin Msg (to Doorway +InSite, self resetting) |
- |
- |
0 to 1 |
| W1 and W2 used together with Doorway Auto/Manual dialog box | |||||
| S1* (C50) | TEMP | Measured Air temperature | Deg C | - | 0 to 95 |
| S2* (C51) | HCOP | Controller output | % | - | -100 to 100 |
| S3 (C52) | REQD | Controller current setpoint | Deg C | - | 0 to 95 |
| S4 (C53) | AIRQ | Air Quality sensor value (type /002 only) | % | - | 0 to 100 |
| S5 (C54) | POSN | Demand to damper | % | - | 0 to 100 |
S6 (C55) |
EOUT |
Enthalpy of Outside Air |
Kj/Kg |
- |
0 to 20000 |
S7 (C56) |
ERTN |
Enthalpy of Return Air |
Kj/Kg |
- |
0 to 20000 |
| K1 (C60) | MNFA | Minimum Fresh Air | % | 0 | -100 to 100 |
| K2 (C61) | MXAQ | Maximum Fresh Air when Air Quality reading equal to or greater than this value (type /002 only) | % | 80 | 0 to 100 |
| K3 (C62) | MNAQ | Minimum value for Air Quality override (type /002 only) | % | 20 | 0 to 100 |
| * 24 hour plots available for these values by default | |||||
| Plotting interval and plotted variable changeable via Doorway or InSite |