Feature
Notes

Configuration Tables

  Wiring

 

 

 

 

Air Handing Unit Damper Submodule
with 3 x Triac Outputs (3T version)
with 2 x 0-10V DC Outputs (AOP version with Air Quality control option)

Configuration Tables

Doorway / InSite Code Label Description Units Default Value Range
C1 SACT

Sensor Action; for future use; set to 0 for this application

- 0 0 to 3
C2 HPRD Damper Stroke Time (3T version only) Secs/10 18 1 to 240
C3 HDLY

Interlock delay; for future use; set to 0 for this application

Mins 0 -60 to 60
C4 MIND Minimum demand; for future use, set to 4 for this application % 4 0 to 100
C5 MNFA

Minimum Fresh air; sets Minimum Fresh air position of Damper
0 : no Minimum Fresh air position in normal operation
>0 : sets Minimum Fresh Air position in normal operation

% 10 0 to 100
C6 MXAQ Maximum Air Quality signal as Air Quality reaches MXAQ, dampers will reach 100% Fresh Air % 100 0 to 100
C7 MNAQ Minimum Air Quality signal that will override Temperature Control; as Air Quality exceeds MNAQ, dampers will start to open % 20 0 to 100
C8 DMPC Damper percent, when dampers used as a stage of the heating or cooling for the AHU this sets the percentage of the AHU demand which is utilied by the mixing dampers. Set to 0 to diable feature. % 0 0 to 50
C9
MANL
Manual level , from Doorway
%
0
-100 to 100
C10 ALRM

Alarm mode
0 ignore alarms
1 report alarms
2 report alarms, shut down all outputs on alarm
3 report alarms, shut down all outputs on STOP alarm or sensor fail alarm

- 1 0 to 3
C11 ALST Alarm State; for future use; set to 0 for this application - 0 0 to 1
C12 MXVA Maximum Voltage output a (for AOP types only) V 10 0 to 10
C13 MNVA Minimum Voltage output a (for AOP types only) V 0 0 to 10
C14 MXVB Maximum Voltage output b (for AOP types only) V 10 0 to 10
C15 MNVB Minimum Voltage output b (for AOP types only) V 0 0 to 10

 

Monitoring Parameters

Doorway / InSite Code Label Description Units Default Value Range
I1 (C30) FRST Frost Protection Mode - - 0 to 1
I2 (C31) OCCD Occupied - - 0 to 1
I3 (C32) OSRT Optimim Start (not used in this application) - - 0 to 1
I5 (C34) COOL Cool Mode - - 0 to 1
I6 (C35) RLYA Triac A Status - - 0 to 1
I7 (C36) RLYB Triac B Status - - 0 to 1
I8 (C37) RLYC Triac C Status - - 0 to 1
W1 (C38) AUTO Automatic/Manual Status - - 0 to 1
W2 (C39) OVRD Override - - 0 to 1
W5 (C42)
HAND
Manual Hand mode
-
0
0 to 1
W6 (C43)
POT
Potentiometer fitted to this board
-
0
0 to 1
W7 (C44)
SERV
Service Pin Msg (to Doorway +InSite, self resetting)
-
-
0 to 1
    W1 and W2 used together with Doorway Auto/Manual dialog box      
S1* (C50) TEMP Measured Air temperature Deg C - 0 to 95
S2* (C51) HCOP Controller output % - -100 to 100
S3 (C52) REQD Controller current setpoint Deg C - 0 to 95
S4 (C53) AIRQ Air Quality sensor value (type /002 only) % - 0 to 100
S5 (C54) POSN Demand to damper % - 0 to 100
S6 (C55)
EOUT
Enthalpy of Outside Air
Kj/Kg
-
0 to 20000
S7 (C56)
ERTN
Enthalpy of Return Air
Kj/Kg
-
0 to 20000
K1 (C60) MNFA Minimum Fresh Air % 0 -100 to 100
K2 (C61) MXAQ Maximum Fresh Air when Air Quality reading equal to or greater than this value (type /002 only) % 80 0 to 100
K3 (C62) MNAQ Minimum value for Air Quality override (type /002 only) % 20 0 to 100
    * 24 hour plots available for these values by default      
    Plotting interval and plotted variable changeable via Doorway or InSite      

 

 