Air Handing Unit Damper Submodule for Natural Ventilation

Feature
Notes
Configuration Tables Wiring    

Configuration Tables

Doorway / InSite Code Label Description Units Default Value Range
C1 SACT

Sensor Action; for future use; set to 0 for this application

- 0 0 to 3
C2 HPRD Damper Stroke Time (3T version only) Secs/10 18 1 to 60
C3 HDLY

Interlock delay; for future use; set to 0 for this application

Mins 0 -30 to 30
C4 MIND Minimum demand; for future use, set to 4 for this application % 4 0 to 100
C5 MNFA

Minimum Fresh air; sets Minimum Fresh air position of Damper
0 : no Minimum Fresh air position in normal operation
>0 : sets Minimum Fresh Air position in normal operation

% 10 0 to 100
C6 MXAQ Maximum Air Quality signal as Air Quality reaches MXAQ, dampers will reach 100% Fresh Air % 100 0 to 100
C7 MNAQ Minimum Air Quality signal that will override Temperature Control; as Air Quality exceeds MNAQ, dampers will start to open % 20 0 to 100
C8 DMPC Damper percent, when dampers used as a stage of the heating or cooling for the AHU this sets the percentage of the AHU demand which is utilied by the mixing dampers. Set to 0 to diable feature. % 0 0 to 50
C9 MANL Manual output level % 0 0 to 100
C10 ALRM

Alarm mode
0 ignore alarms
1 report alarms
2 report alarms, shut down all outputs on alarm
3 report alarms, shut down all outputs on STOP alarm or sensor fail alarm

- 1 0 to 3
C11 ALST Alarm State; for future use; set to 0 for this application - 0 0 to 1
C12 MNDP Minimum damper position while occupied, this is regardless of wind or temperature factoring % 5 0 to 100
C13 CMDE Control Mode:
0: both heating and cooling controlled by demand percentage
1: heating controlled from mixed air or supply temperature sensor, cooling by demand percent
2: cooling controlled from mixed air or supply temperature sensor, heating by demand percent
3: Both heating and cooling controlled from mixed air or supply temperature sensor
- 0 0 to 3
C14 MXWS Maximum Wind Speed: windspeed at which dampers are forced shut; override factor equals 0 m/sec 0 0 to 25
C15 MNWS Minimum Wind Speed: windspeed at which dampers are not effected; override factor equals 100 m/sec 0 0 to 25
C16 WNWD Window Direction: compass reading when looking directly out of the window Degrees 0 0 to 360
C17 DDEV Wind Direction Deviation: number of degrees from dead downwind when the window will be forced shut; when override factor equals 0 Degrees 0 0 to 360
C18 CALC Calculation Mode: defines how the override factors (wind speed, wind direction and outside temperature) are combined:
0: multiply the individual factors
1: apply the lowest factor
2: apply the average
- 0 0 to 2
C19 FIMN Fan re-scale input minimum % 0 0 to 100
C20 FIMX Fan re-scale input maximum % 100 0 to 100
C21 FOMN Fan re-scale output minimum % 0 0 to 100
C22 FOMX Fan re-scale output maximum % 100 0 to 100
C23 MXVA Maximum Voltage output a (for AOP types only) V 10 0 to 10
C24 MNVA Minimum Voltage output a (for AOP types only) V 0 0 to 10
C25 MXVB Maximum Voltage output b (for AOP types only) V 10 0 to 10
C26 MNVB Minimum Voltage output b (for AOP types only) V 0 0 to 10

 

Monitoring Parameters

Doorway / InSite Code Label Description Units Default Value Range
I1 (C30) FRST Frost Protection Mode - - 0 to 1
I2 (C31) OCCD Occupied - - 0 to 1
I3 (C32) OSRT Optimim Start (not used in this application) - - 0 to 1
I5 (C34) COOL Cool Mode - - 0 to 1
I6 (C35) RLYA Triac A Status (3T types only) - - 0 to 1
I7 (C36) RLYB Triac B Status (3T types only) - - 0 to 1
I8 (C37) RLYC Triac C Status (3T types only) - - 0 to 1
W1 (C38) AUTO Automatic/Manual Status - - 0 to 1
W2 (C39) OVRD Override - - 0 to 1
W3 (C40) POT Potentiometer fitted, enables use of on board potentiometer in manual - - 0 to 1
W5 (C42) HAND Manual HAND mode from Doorway supervisor - - 0 to 1
W7 (C44) SERV Remote access to registration button - - 0 to 1
    W1 and W2 used together with Doorway Auto/Manual dialog box      
S1* (C50) TEMP Measured Air temperature Deg C - 0 to 95
S2* (C51) HCOP Controller output % - -100 to 100
S3 (C52) REQD Controller current setpoint Deg C - 0 to 95
S4 (C53) AIRQ Air Quality sensor value (AOP type only) % - 0 to 100
S5 (C54) POSN Demand to damper % - 0 to 100
S6 (C55) FANS Demand to Fans % - 0 to 100
S7 (C56) OSFR Outside temperature override factor % - 0 to 100
S8 (C57) WSFR Wind Speed override factor % - 0 to 100
S9 (C58) WDFR Wind Direction override factor % - 0 to 100
S10 (C59) FACT Overall resultant override factor, combination of above three factors based on CALC % - 0 to 100
K1 (C60) MNFA Minimum Fresh Air % 0 -100 to 100
K2 (C61) MXAQ Maximum Fresh Air when Air Quality reading equal to or greater than this value (AOP type only) % 80 0 to 100
K3 (C62) MNAQ Minimum value for Air Quality override (AOP type only) % 20 0 to 100
K4 (C63) MXWS Maximum Wind Speed: windspeed at which dampers are forced shut; override factor equals 0 m/sec 0 0 to 25
K5 (C64) MNWS Minimum Wind Speed: windspeed at which dampers are not effected; override factor equals 100 m/sec 0 0 to 25
K6 (C65) NOWS No Wind Speed below this speed the Wind direction override is ignored m/sec 0 0 to 25
K7 (C66) DDEV Wind Direction Deviation: number of degrees from dead downwind when the window will be forced shut; when override factor equals 0 Degrees 0 0 to 360
K8 (C67) OUTT OUTside temperature Top at which no temperature override is applied, override factor equals 100 Deg C 0 0 to 25
K9 (C68) OUTB OUTside temperature Bottom at which full temperature override is applied, override factor equals 0 Deg C 0 0 to 25
    * 24 hour plots available for these values by default      
    Plotting interval and plotted variable changeable via Doorway or InSite      

 

 