Feature
Notes
Configuration Tables Wiring    

Air Handing Unit Humidity Submodule

with 3 x Triac Outputs (3T version)
with 2 x 0-10V DC Outputs (AOP version)

Configuration Tables

Doorway / InSite Code

Label

Description

Units

Default Value

Range

C1
SPRH
Occupied setpoint
%RH
50
0 to 100
C2
SPMD
Midpoint of setpoint adjustment range
%
50
10 to 90
C3
SPRG
Range of setpoint adjustment about midpoint
%
20
0 to 40
C4
SPDB
Setpoint deadband between humidification and de_humidification setpoints. If zero disables de-hum
%
10
0 to 20
C5
RDLY
Recirculation delay , for use with evaporative coolers on Dessicant Plant;
hours of continuous running before water recircualtion is allowed
Hours
2
0 to 10
C6
HPRD
Minimum on time for humidifier stages
Secs/10
 
1 to 60
C7
HDLY
Not used in this application
Mins
0
-30 to 30
C8
CPRD
Not used in this application
Secs/10
 
1 to 60
C9
CDLY
Not used in this application
Mins
0
-30 to 30
C10
FPRD
Not used in this application
Secs/10
12
1 to 60
C11
MIND
Minimum demand
%
4
0 to 100
C12
MANL
Manual level , from Doorway
%
0
-100 to 100
C13
ALRM
Alarm mode
0 ignore alarms
1 report alarms
2 report alarms, shut down all outputs on alarm
3 report alarms, shut down all outputs on STOP alarm or sensor fail alarm
-
1
0 to 3
C14
ALST
Not used in this application
-
0
0 to 1
C15
CMDE
Control mode
0 driver only mode
1 closed loop control of humidity
2 closed loop control of Humidity and DeHum (see Close Control for setup details)
-
0
0 to 2
C16
MXSH
Maximum Supply Humidity setpoint
%RH
60
0 to 100
C17
MNSH
Minimum Supply Humidity setpoint
%RH
40
0 to 100
C18
DHOF
Supply DeHum setpoint offset
%RH
2
0 to 10
 
 
Engineering Parameters for advanced applications: contact SeaChange for further details
 
 
 
C19
TRGT
Target mean value for Humidifier control minimum output
%
10
3 to 100
C20
ICGN
InterCoil setpoint Gain (controls rate of adjustment)
-
10
1 to 255
C21
ICSP
InterCoil temperature setpoint for monitoring
Deg C
30
0 to 50
C22
ICLT
InterCoil temperature for monitoring
Deg C
-
0 to 50
C23
ICOP
InterCoil loop output for monitoring
%
-
0 to 100
C24
RTMD
Return Mode, provides extra control features when using cascade control
0 cascade control disabled
1 cascade control enabled (must have both Supply and return RH sensors)
2 cascade control enabled, return loop output locked if supply loop reaches 0 or 100% to prevent wind up.
-
0
0 to 2
C25
PROP
Proportional gain term for Humidity control loop
-
0
0 to 250
C26
MXVA
Maximum Voltage output a (for AOP types only)
V
10
0 to 10
C27
MNVA
Minimum Voltage output a (for AOP types only)
V
0
0 to 10
C28
MXVB
Maximum Voltage output b (for AOP types only)
V
10
0 to 10
C29
MNVB
Minimum Voltage output b (for AOP types only)
V
0
0 to 10

Monitoring Parameters

Doorway / InSite Code

Label

Description

Units

Default Value

Range

I2 (C31)
OCC
Occupied
-
-
0 to 1
I3 (C32)
OSRT
Optimim Start
-
-
0 to 1
I6 (C35)
RLYA
Triac A Status
-
-
0 to 1
I7 (C36)
RLYB
Triac B Status
-
-
0 to 1
I8 (C37)
RLYC
Triac C Status
-
-
0 to 1
W1 (C38)
AUTO
Automatic/Manual Status
-
-
0 to 1
W2 (C39)
OVRD
Override
-
-
0 to 1
W8 (C45)
CGST
Configuration mode
-
-
0 to 1
 
 
W1 and W2 used together with Doorway Auto/Manual dialog box
 
 
 
S1* (C50)
RTRH
Return Relative Humidity
%RH
-
0 to 100
S2* (C51)
SLRH
Supply Relative Humidity
%RH
-
0 to 100
S3 (C52)
DMND
Return Loop output
%
-
-100 to 100
S4 (C53)
RTSP
Return Humidity Setpoint
%RH
-
0 to 100
S5 (C54)
SLSP
Supply Humidity Setpoint
%RH
-
0 to 100
S6 (C55)
HDMD
Humidification output demand
%
-
0 to 100
S7 (C56)
CDMD
De-humudification output demand
%
-
0 to 100
S8 (C57)
RDMD
Recirculation demand
%
-
0 to 100
S9 (C58)
HTIP
Heat demand from AHU
%
-
0 to 100
S10 (C59)
CLIP
Cool demand from AHU
%
-
0 to 100
K1 (C60)
SPRH
Occupied setpoint
%RH
50
0 to 100
   
* 24 hour plots available for these values by default
     
   
Plotting interval and plotted variable changeable via Doorway or InSite
     