| Feature Notes |
Configuration Tables | Wiring |
Doorway / InSite Code |
Label |
Description |
Units |
Default Value |
Range |
C1 |
SPRH |
Occupied setpoint |
%RH |
50 |
0 to 100 |
C2 |
SPMD |
Midpoint of setpoint adjustment range |
% |
50 |
10 to 90 |
C3 |
SPRG |
Range of setpoint adjustment about midpoint |
% |
20 |
0 to 40 |
C4 |
SPDB |
Setpoint deadband between humidification and de_humidification setpoints. If zero disables de-hum |
% |
10 |
0 to 20 |
C5 |
RDLY |
Recirculation delay , for use with evaporative coolers
on Dessicant Plant; |
Hours |
2 |
0 to 10 |
C6 |
HPRD |
Minimum on time for humidifier stages |
Secs/10 |
1 to 60 |
|
C7 |
HDLY |
Not used in this application |
Mins |
0 |
-30 to 30 |
C8 |
CPRD |
Not used in this application |
Secs/10 |
1 to 60 |
|
C9 |
CDLY |
Not used in this application |
Mins |
0 |
-30 to 30 |
C10 |
FPRD |
Not used in this application |
Secs/10 |
12 |
1 to 60 |
C11 |
MIND |
Minimum demand |
% |
4 |
0 to 100 |
C12 |
MANL |
Manual level , from Doorway |
% |
0 |
-100 to 100 |
C13 |
ALRM |
Alarm mode |
- |
1 |
0 to 3 |
C14 |
ALST |
Not used in this application |
- |
0 |
0 to 1 |
C15 |
CMDE |
Control mode |
- |
0 |
0 to 2 |
C16 |
MXSH |
Maximum Supply Humidity setpoint |
%RH |
60 |
0 to 100 |
C17 |
MNSH |
Minimum Supply Humidity setpoint |
%RH |
40 |
0 to 100 |
C18 |
DHOF |
Supply DeHum setpoint offset |
%RH |
2 |
0 to 10 |
Engineering Parameters for advanced applications: contact SeaChange for further details |
|||||
C19 |
TRGT |
Target mean value for Humidifier control minimum output |
% |
10 |
3 to 100 |
C20 |
ICGN |
InterCoil setpoint Gain (controls rate of adjustment) |
- |
10 |
1 to 255 |
C21 |
ICSP |
InterCoil temperature setpoint for monitoring |
Deg C |
30 |
0 to 50 |
C22 |
ICLT |
InterCoil temperature for monitoring |
Deg C |
- |
0 to 50 |
C23 |
ICOP |
InterCoil loop output for monitoring |
% |
- |
0 to 100 |
C24 |
RTMD |
Return Mode, provides extra control features when using
cascade control |
- |
0 |
0 to 2 |
C25 |
PROP |
Proportional gain term for Humidity control loop |
- |
0 |
0 to 250 |
C26 |
MXVA |
Maximum Voltage output a (for AOP types only) |
V |
10 |
0 to 10 |
C27 |
MNVA |
Minimum Voltage output a (for AOP types only) |
V |
0 |
0 to 10 |
C28 |
MXVB |
Maximum Voltage output b (for AOP types only) |
V |
10 |
0 to 10 |
C29 |
MNVB |
Minimum Voltage output b (for AOP types only) |
V |
0 |
0 to 10 |
Doorway / InSite Code |
Label |
Description |
Units |
Default Value |
Range |
I2 (C31) |
OCC |
Occupied |
- |
- |
0 to 1 |
I3 (C32) |
OSRT |
Optimim Start |
- |
- |
0 to 1 |
I6 (C35) |
RLYA |
Triac A Status |
- |
- |
0 to 1 |
I7 (C36) |
RLYB |
Triac B Status |
- |
- |
0 to 1 |
I8 (C37) |
RLYC |
Triac C Status |
- |
- |
0 to 1 |
W1 (C38) |
AUTO |
Automatic/Manual Status |
- |
- |
0 to 1 |
W2 (C39) |
OVRD |
Override |
- |
- |
0 to 1 |
W8 (C45) |
CGST |
Configuration mode |
- |
- |
0 to 1 |
| |
W1 and W2 used together with Doorway Auto/Manual dialog box |
||||
S1* (C50) |
RTRH |
Return Relative Humidity |
%RH |
- |
0 to 100 |
S2* (C51) |
SLRH |
Supply Relative Humidity |
%RH |
- |
0 to 100 |
S3 (C52) |
DMND |
Return Loop output |
% |
- |
-100 to 100 |
S4 (C53) |
RTSP |
Return Humidity Setpoint |
%RH |
- |
0 to 100 |
S5 (C54) |
SLSP |
Supply Humidity Setpoint |
%RH |
- |
0 to 100 |
S6 (C55) |
HDMD |
Humidification output demand |
% |
- |
0 to 100 |
S7 (C56) |
CDMD |
De-humudification output demand |
% |
- |
0 to 100 |
S8 (C57) |
RDMD |
Recirculation demand |
% |
- |
0 to 100 |
S9 (C58) |
HTIP |
Heat demand from AHU |
% |
- |
0 to 100 |
S10 (C59) |
CLIP |
Cool demand from AHU |
% |
- |
0 to 100 |
K1 (C60) |
SPRH |
Occupied setpoint |
%RH |
50 |
0 to 100 |
* 24 hour plots available for these values by default |
|||||
Plotting interval and plotted variable changeable via Doorway or InSite |