| Feature Notes |
Configuration Tables | Wiring |
Doorway / InSite Code |
Label |
Description |
Units |
Default Value |
Range |
C1 |
ALRM |
Alarm mode |
- |
1 |
0 to 1 |
C2 |
ALST |
Alarm state |
- |
0 |
0 to 1 |
C3 |
FMDE |
Failure mode |
- |
1 |
1 to 3 |
C4 |
DLAY |
Delay to wait for proof of flow |
Secs |
10 |
0 to 250 |
C5 |
MXHR |
Maximum run hours on one fan before automatic changeover is initiated |
Hours |
24 |
1 to 200 |
C6 |
TYPE |
Driver type |
- |
1 |
1 to 2 |
Doorway / InSite Code |
Label |
Description |
Units |
Default Value |
Range |
I1 (C30) |
FL A |
Flow signal Fan A |
- |
- |
0 to 1 |
I2 (C31) |
FL B |
Flow signal Fan B |
- |
- |
0 to 1 |
I3 (C32) |
EN A |
Not used in this application |
- |
- |
0 to 1 |
I4 (C33) |
EN B |
Not used in this application |
- |
- |
0 to 1 |
I5 (C34) |
FAIL |
One or more fans failed |
- |
- |
0 to 1 |
I6 (C35) |
FANA |
Fan A status |
- |
- |
0 to 1 |
I7 (C36) |
FANB |
Fan B status |
- |
- |
0 to 1 |
I8 (C37) |
ALRM |
Triac C alarm indication |
- |
- |
0 to 1 |
W1 (C38) |
AUTO |
Automatic/Manual Status |
- |
- |
0 to 1 |
W2 (C39) |
OVRD |
Override |
- |
- |
0 to 1 |
W3 (C40) |
RSTA |
Reset Hours run Fan A |
- |
- |
0 to 1 |
W4 (C41) |
RSTB |
Reset Hours run Fan B |
- |
- |
0 to 1 |
S1 (C50) |
HRSA |
Hours Run Fan A |
Hours |
- |
- |
S2 (C51) |
HRSB |
Hours Run Fan B |
Hours |
- |
- |
C90 |
NOAL |
No alarms |
- |
1 |
0 to 1 |
C91 |
FLFA |
Flow fail alarm Fan A |
- |
0 |
0 to 1 |
C92 |
FLFB |
Flow fail alarm Fan B |
- |
0 |
0 to 1 |