Air Handing Unit Damper Submodule

with 3 x Triac Outputs (3T version)
with 2 x 0-10V DC Outputs (AOP version with Air Quality control option)

Wiring Diagram 3T Version


Specification


Wiring Diagram AOP Version


Specification


Wiring Diagram AOP Version (with Optional Air Quality Control)

Note- Use a separate SeaChange transformer for the sensor.  The 24V supply for the sensor must be isolated form Earth. No connection must be made from either conductor to earth.  If using the TRN/DIN/3.8/002 SeaChange 24VAC transformer, remove Link 1 to make SELV, this breaks the connection between 24V and Earth.  This type of transformer ensures better 24VAC line regulation of +/-10% as required by the Sontay sensor.


Specification