Feature
Notes
Configuration Tables Wiring

   

Air Handing Unit Heat Recovery Submodule

with 3 x Triac Outputs (3T version)
with 2 x 0-10V DC Outputs (AOP version)

Configuration Tables

Doorway / InSite Code

Label

Description

Units

Default Value

Range

C1
SACT
Sensor Action; for future use; set to 0 for this application
-
0
0 to 3
C2
HPRD
Heating mode period or minimum on time; Stroke Time of valve or Minimum-On Time for TP output when in Heating mode (set to same value as C4)
Secs/10
Depends on driver
1 to 240
C3
HDLY
Interlock delay in Heating mode, for pumped runaround coils
0: Valve opens with pump (no delay)
Negative value: Valve opens before pump starts
Positive Value: Valve opens after pump starts
Mins
0
-60 to 60
C4
CPRD
Cooling mode period or minimum on time; Stroke Time of valve or Minimum-On Time for TP output on driver when in Cooling mode (set to same value as C2)
Secs/10
Depends on driver
1 to 240
C5
CDLY
Interlock delay Cooling mode, for pumped runaround coils
0: Valve opens with pump (no delay)
Negative value: Valve opens before pump starts
Positive Value: Valve opens after pump starts
Mins
0
-60 to 60
C6
FPRD
Not used in this application; set to 10
Secs/10
10
1 to 240
C7
INMD
Input Mode for input terminals 3 and 4 ‘temp a’
0: Additional temperature input for max, min, ave using SACT
1: External occupation (input linked = Occupied) AND
with internal Occupation
2: External occupation (input linked = Occupied) OR
with internal Occupation
3: External Occupation signal only
4: Alarm input
5: Pump alarm
-
0
0 to 5
C8
MIND
Minimum demand; used for pump output:
0: Pump runs for whole of AHU Occupancy period
>0: Pump runs only when Energy Recovery demand exceeds MIND
%
4
0 to 100
C9
FPRT
Frost mode
0: no action
1: open valve
2: open valve and run pump
-
1
0 to 2
C10
MANL
Manual level , from Doorway
%
0
-100 to 100
C11
ALRM
Alarm mode
0: Ignore alarms
1: Report alarms
2: Report alarms, shut down all outputs on alarm
3: Report alarms, shut down all outputs on STOP alarm or sensor fail alarm
-
1
0 to 3
C12
ALST
Alarm state; not used, set to 0 for this application
-
0
0 to 1
C13
MXVA
Maximum Voltage output a (for AOP types only)
V
10
0 to 10
C14
MNVA
Minimum Voltage output a (for AOP types only)
V
0
0 to 10
C15
MXVB
Maximum Voltage output b (for AOP types only)
V
10
0 to 10
C16
MNVB
Minimum Voltage output b (for AOP types only)
V
0
0 to 10

Monitoring Parameters

Doorway / InSite Code

Label

Description

Units

Default Value

Range

I1 (C30)
FRST
Frost Protection Mode
-
-
0 to 1
I2 (C31)
OCCD
Occupied
-
-
0 to 1
I4 (C33)
EXTI
External Input
-
-
0 to 1
I5 (C34)
COOL
Cool Mode
-
-
0 to 1
I6 (C35)
RLYA
Triac A Status
-
-
0 to 1
I7 (C36)
RLYB
Triac B Status
-
-
0 to 1
I8 (C37)
RLYC
Triac C Status
-
-
0 to 1
W1 (C38)
AUTO
Automatic/Manual Status
-
-
0 to 1
W2 (C39)
OVRD
Override
-
-
0 to 1
W5 (C42)
HAND
Manual Hand mode
-
0
0 to 1
W6 (C43)
POT
Potentiometer fitted to this board
-
0
0 to 1
W7 (C44)
SERV
Service Pin Msg (to Doorway +InSite, self resetting)
-
-
0 to 1
 
 
W1 and W2 used together with Doorway Auto/Manual dialog box
 
 
 
S1* (C50)
TEMP
Measured off coil temperature
Deg C
-
0 to 35
S2* (C51)
HCOP
Controller output
%
-
-100 to 100
S3 (C52)
REQD
Controller current setpoint
Deg C
-
0 to 35
S4 (C53)
HDMD
Heating Demand to valve or damper (shows position)
%
-
0 to 100
S5 (C54)
CDMD
Cooling Demand to valve or damper (shows position)
%
-
0 to 100
S6 (C55)
FDMD
Fan or Pump Demand
%
-
0 to 100
S7 (C56)
EOUT
Enthalpy of Outside Air
Kj/Kg
-
0 to 20000
S8 (C57)
ERTN
Enthalpy of Return Air
Kj/Kg
-
0 to 20000
 
 
* 24 hour plots available for these values by default
 
 
 
 
 
Plotting interval and plotted variable changeable via Doorway or InSite
 
 
 