Doorway / InSite Code
|
Label
|
Description
|
Units
|
Default Value
|
Range
|
C1
|
SACT
|
Sensor Action; for future use; set to 0 for this application
|
-
|
0
|
0 to 3
|
C2
|
HPRD
|
Heating mode period or minimum on time; Stroke Time of valve or Minimum-On
Time for TP output when in Heating mode (set to same value as C4)
|
Secs/10
|
Depends on driver
|
1 to 240
|
C3
|
HDLY
|
Interlock delay in Heating mode, for pumped runaround coils
0: Valve opens with pump (no delay)
Negative value: Valve opens before pump starts
Positive Value: Valve opens after pump starts
|
Mins
|
0
|
-60 to 60
|
C4
|
CPRD
|
Cooling mode period or minimum on time; Stroke Time of valve or Minimum-On
Time for TP output on driver when in Cooling mode (set to same value as
C2)
|
Secs/10
|
Depends on driver
|
1 to 240
|
C5
|
CDLY
|
Interlock delay Cooling mode, for pumped runaround coils
0: Valve opens with pump (no delay)
Negative value: Valve opens before pump starts
Positive Value: Valve opens after pump starts
|
Mins
|
0
|
-60 to 60
|
C6
|
FPRD
|
Not used in this application; set to 10
|
Secs/10
|
10
|
1 to 240
|
C7
|
INMD
|
Input Mode for input terminals 3 and 4 temp a
0: Additional temperature input for max, min, ave using SACT
1: External occupation (input linked = Occupied) AND
with internal Occupation
2: External occupation (input linked = Occupied) OR
with internal Occupation
3: External Occupation signal only
4: Alarm input
5: Pump alarm
|
-
|
0
|
0 to 5
|
C8
|
MIND
|
Minimum demand; used for pump output:
0: Pump runs for whole of AHU Occupancy period
>0: Pump runs only when Energy Recovery demand exceeds MIND
|
%
|
4
|
0 to 100
|
C9
|
FPRT
|
Frost mode
0: no action
1: open valve
2: open valve and run pump
|
-
|
1
|
0 to 2
|
C10
|
MANL
|
Manual level , from Doorway
|
%
|
0
|
-100 to 100
|
C11
|
ALRM
|
Alarm mode
0: Ignore alarms
1: Report alarms
2: Report alarms, shut down all outputs on alarm
3: Report alarms, shut down all outputs on STOP alarm or sensor fail alarm
|
-
|
1
|
0 to 3
|
C12
|
ALST
|
Alarm state; not used, set to 0 for this application
|
-
|
0
|
0 to 1
|
C13
|
MXVA
|
Maximum Voltage output a (for AOP types only)
|
V
|
10
|
0 to 10
|
C14
|
MNVA
|
Minimum Voltage output a (for AOP types only)
|
V
|
0
|
0 to 10
|
C15
|
MXVB
|
Maximum Voltage output b (for AOP types only)
|
V
|
10
|
0 to 10
|
C16
|
MNVB
|
Minimum Voltage output b (for AOP types only)
|
V
|
0
|
0 to 10
|
Doorway / InSite Code
|
Label
|
Description
|
Units
|
Default Value
|
Range
|
I1 (C30)
|
FRST
|
Frost Protection Mode
|
-
|
-
|
0 to 1
|
I2 (C31)
|
OCCD
|
Occupied
|
-
|
-
|
0 to 1
|
I4 (C33)
|
EXTI
|
External Input
|
-
|
-
|
0 to 1
|
I5 (C34)
|
COOL
|
Cool Mode
|
-
|
-
|
0 to 1
|
I6 (C35)
|
RLYA
|
Triac A Status
|
-
|
-
|
0 to 1
|
I7 (C36)
|
RLYB
|
Triac B Status
|
-
|
-
|
0 to 1
|
I8 (C37)
|
RLYC
|
Triac C Status
|
-
|
-
|
0 to 1
|
W1 (C38)
|
AUTO
|
Automatic/Manual Status
|
-
|
-
|
0 to 1
|
W2 (C39)
|
OVRD
|
Override
|
-
|
-
|
0 to 1
|
W5 (C42)
|
HAND
|
Manual Hand mode
|
-
|
0
|
0 to 1
|
W6 (C43)
|
POT
|
Potentiometer fitted to this board
|
-
|
0
|
0 to 1
|
W7 (C44)
|
SERV
|
Service Pin Msg (to Doorway +InSite, self resetting)
|
-
|
-
|
0 to 1
|
|
|
W1 and W2 used together with Doorway Auto/Manual dialog box
|
|
|
|
S1* (C50)
|
TEMP
|
Measured off coil temperature
|
Deg C
|
-
|
0 to 35
|
S2* (C51)
|
HCOP
|
Controller output
|
%
|
-
|
-100 to 100
|
S3 (C52)
|
REQD
|
Controller current setpoint
|
Deg C
|
-
|
0 to 35
|
S4 (C53)
|
HDMD
|
Heating Demand to valve or damper (shows position)
|
%
|
-
|
0 to 100
|
S5 (C54)
|
CDMD
|
Cooling Demand to valve or damper (shows position)
|
%
|
-
|
0 to 100
|
S6 (C55)
|
FDMD
|
Fan or Pump Demand
|
%
|
-
|
0 to 100
|
S7 (C56)
|
EOUT
|
Enthalpy of Outside Air
|
Kj/Kg
|
-
|
0 to 20000
|
S8 (C57)
|
ERTN
|
Enthalpy of Return Air
|
Kj/Kg
|
-
|
0 to 20000
|
|
|
* 24 hour plots available for these values by default
|
|
|
|
|
|
Plotting interval and plotted variable changeable via Doorway or InSite
|
|
|
|