Air Handing Unit Preheater Submodule

with 3 x Triac Outputs (3T version)
with 2 x 0-10V DC Outputs (AOP version)

Configuration Tables

Doorway / InSite Code

Label

Description

Units

Default Value

Range

C1
OCSP
Occupied setpoint
Deg C
-
0.5 to 35
C2
SACT
Sensor Action; for future use; set to 0 for this application
-
0
0 to 3
C3
DEGR
Maximum temperature rise across battery with heating at 100%
Deg C
10
5 to 50
C4
SPFR
Frost or non occupied setpoint
Deg C
-
0 to 20.0
C5
HPRD
Heating valve period or minimum on time
Secs/10
Depends on driver
1 to 240
C6
HDLY
Interlock delay
0: Battery starts with AHU Fan (no delay)
Negative value: for wet batteries, Valve opens before AHU Fan starts
Positive Value: for electric batteries, AHU Fan starts first runs on after battery shuts down
Mins
0
-60 to 60
C7
CPRD
For future use; set to 10 for this application
Secs/10
10
1 to 60
C8
CDLY
For future use; set to 0 for this application
Mins
0
-30 to 30
C9
FPRD
Ffor future use; set to 12 for this application
Secs/10
12
1 to 60
C7
INMD
Input Mode for input terminals 3 and 4 ‘temp a’
0: Additional temperature input for max, min, ave using SACT
1: External occupation (input linked = Occupied) AND
with internal Occupation
2: External occupation (input linked = Occupied) OR
with internal Occupation
3: External Occupation signal only
4: Alarm input
5: Pump alarm
-
0
0 to 5
C10
MIND
Minimum demand used for pump output:
0: Pump runs for whole of AHU Occupancy period
>0: Pump runs only when Preheat demand exceeds MIND
 
4
0 to 100
C11
FRPT
Frost mode
0 no action
1 open valve
2: open valve and run pump (if fitted)
-
1
0 to 2
C12
MANL
Manual level , from Doorway
%
0
-100 to 100
C13
ALRM
Alarm mode
0 ignore alarms
1 report alarms
2 report alarms, shut down all outputs on alarm
3 report alarms, shut down all outputs on STOP alarm or sensor fail alarm
-
1
0 to 3
C14
ALST
not used
-
0
0 to 1
C15
MXVA
Maximum Voltage output a (for AOP types only)
V
10
0 to 10
C16
MNVA
Minimum Voltage output a (for AOP types only)
V
0
0 to 10
C17
MXVB
Maximum Voltage output b (for AOP types only)
V
10
0 to 10
C18
MNVB
Minimum Voltage output b (for AOP types only)
V
0
0 to 10

Monitoring Parameters

Doorway / InSite Code

Label

Description

Units

Default Value

Range

I1 (C30)
FRST
Frost Protection Mode
-
-
0 to 1
I2 (C31)
OCC
Occupied
-
-
0 to 1
I4 (C33)
EXTI
External Input
-
-
0 to 1
I6 (C35)
RLYA
Triac A Status
-
-
0 to 1
I7 (C36)
RLYB
Triac B Status
-
-
0 to 1
I8 (C37)
RLYC
Triac C Status
-
-
0 to 1
W1 (C38)
AUTO
Automatic/Manual Status
-
-
0 to 1
W2 (C39)
OVRD
Override
-
-
0 to 1
W5 (C42)
HAND
Manual Hand mode
-
0
0 to 1
W6 (C43)
POT
Potentiometer fitted to this board
-
0
0 to 1
W7 (C44)
SERV
Service Pin Msg (to Doorway +InSite, self resetting)
-
-
0 to 1
 
 
W1 and W2 used together with Doorway Auto/Manual dialog box
 
 
 
S1* (C50)
TEMP
Measured off coil temperature
Deg C
-
0 to 35
S2* (C51)
DMND
Controller output
%
-
-100 to 100
S3 (C52)
REQD
Controller current setpoint
Deg C
-
0 to 35
S4 (C53)
HDMD
Heating output demand
%
-
0 to 100
S5 (C54)
CDMD
Cooling Demand to valve or damper (shows position)
%
-
0 to 100
S6 (C55)
FDMD
Fan or Pump Demand
%
-
0 to 100
K1 (C60)
OCSP
Occupation Setpoint
Deg C
8
1 to 35
K2 (C61)
DEGR
Maximum temperature across battery with heating at 100%
Deg C
10
5 to 30
   
* 24 hour plots available for these values by default
     
   
Plotting interval and plotted variable changeable via Doorway or InSite
     

 

 