| Feature Notes |
Configuration Tables | Wiring |
Doorway / InSite Code |
Label |
Description |
Units |
Default Value |
Range |
C1 |
OCSP |
Occupied setpoint |
Deg C |
- |
0.5 to 35 |
C2 |
SACT |
Sensor Action; for future use; set to 0 for this application |
- |
0 |
0 to 3 |
C3 |
DEGR |
Maximum temperature rise across battery with heating at 100% |
Deg C |
10 |
5 to 50 |
C4 |
SPFR |
Frost or non occupied setpoint |
Deg C |
- |
0 to 20.0 |
C5 |
HPRD |
Heating valve period or minimum on time |
Secs/10 |
Depends on driver |
1 to 240 |
C6 |
HDLY |
Interlock delay
|
Mins |
0 |
-60 to 60 |
C7 |
CPRD |
For future use; set to 10 for this application |
Secs/10 |
10 |
1 to 60 |
C8 |
CDLY |
For future use; set to 0 for this application |
Mins |
0 |
-30 to 30 |
C9 |
FPRD |
Ffor future use; set to 12 for this application |
Secs/10 |
12 |
1 to 60 |
C7 |
INMD |
Input Mode for input terminals 3 and 4 temp a
|
- |
0 |
0 to 5 |
C10 |
MIND |
Minimum demand used for pump output:
|
|
4 |
0 to 100 |
C11 |
FRPT |
Frost mode
|
- |
1 |
0 to 2 |
C12 |
MANL |
Manual level , from Doorway |
% |
0 |
-100 to 100 |
C13 |
ALRM |
Alarm mode
|
- |
1 |
0 to 3 |
C14 |
ALST |
not used |
- |
0 |
0 to 1 |
C15 |
MXVA |
Maximum Voltage output a (for AOP types only) |
V |
10 |
0 to 10 |
C16 |
MNVA |
Minimum Voltage output a (for AOP types only) |
V |
0 |
0 to 10 |
C17 |
MXVB |
Maximum Voltage output b (for AOP types only) |
V |
10 |
0 to 10 |
C18 |
MNVB |
Minimum Voltage output b (for AOP types only) |
V |
0 |
0 to 10 |
Doorway / InSite Code |
Label |
Description |
Units |
Default Value |
Range |
I1 (C30) |
FRST |
Frost Protection Mode |
- |
- |
0 to 1 |
I2 (C31) |
OCC |
Occupied |
- |
- |
0 to 1 |
I4 (C33) |
EXTI |
External Input |
- |
- |
0 to 1 |
I6 (C35) |
RLYA |
Triac A Status |
- |
- |
0 to 1 |
I7 (C36) |
RLYB |
Triac B Status |
- |
- |
0 to 1 |
I8 (C37) |
RLYC |
Triac C Status |
- |
- |
0 to 1 |
W1 (C38) |
AUTO |
Automatic/Manual Status |
- |
- |
0 to 1 |
W2 (C39) |
OVRD |
Override |
- |
- |
0 to 1 |
W5 (C42) |
HAND |
Manual Hand mode |
- |
0 |
0 to 1 |
W6 (C43) |
POT |
Potentiometer fitted to this board |
- |
0 |
0 to 1 |
W7 (C44) |
SERV |
Service Pin Msg (to Doorway +InSite, self resetting) |
- |
- |
0 to 1 |
|
|
|
W1 and W2 used together with Doorway Auto/Manual dialog box |
|
|
|
S1* (C50) |
TEMP |
Measured off coil temperature |
Deg C |
- |
0 to 35 |
S2* (C51) |
DMND |
Controller output |
% |
- |
-100 to 100 |
S3 (C52) |
REQD |
Controller current setpoint |
Deg C |
- |
0 to 35 |
S4 (C53) |
HDMD |
Heating output demand |
% |
- |
0 to 100 |
S5 (C54) |
CDMD |
Cooling Demand to valve or damper (shows position) |
% |
- |
0 to 100 |
S6 (C55) |
FDMD |
Fan or Pump Demand |
% |
- |
0 to 100 |
K1 (C60) |
OCSP |
Occupation Setpoint |
Deg C |
8 |
1 to 35 |
K2 (C61) |
DEGR |
Maximum temperature across battery with heating at 100% |
Deg C |
10 |
5 to 30 |
* 24 hour plots available for these values by default |
|||||
Plotting interval and plotted variable changeable via Doorway or InSite |