Feature
Notes
Configuration Tables Wiring    

6 Channel Underfloor Heating Controller

Configuration Tables

Doorway / InSite Code Label Description Units Default Value Range
C1
CHNL
Heating channel to be configured
-
-
1 to 6
C2
SCAL
Sensor calibration (used for calibrating the sensor input, if required)
-
0
-5 to 5
C3
SENN
Current channel sensor number.  A sensor input is associated with each heating channel (e.g. SENN=1 relates to temperature sensor on input A), but a temperature sensor can also be shared with other control channels
-
0
1 to 6
C4
PRD
Current heating channel stroke/minimum ON time (e.g. PRD=6 is 60 sec). The heating channels are set for time proportioning control
secs/10
6
1 to 240
C5
DLY
Current channel interlock delay.  Negative value= delay on operation, positive value=delay off operation
-
0
-60 to +60
C6
SPTY
Setpoint type

0: Heating channels use their own setpoint determined on parameter K1 (SPOC)
1: Heating channels are setpoint supervised from a zone controller (disable local OSS)

-
0
0 to 1
C7
HTSC
Heat source.  The heat source parameter determines where the heat demand is sent to (e.g. boiler controller, VTC secondary circuit controller...etc)
-
-
0 to 8255
C8
CLSC
Not used on this application
-
0
0 to 8255
C9
OCDS
Occupancy destination.  This parameter can be used to send an occupancy demand link to another controller
-
0
0 to 8255
C10
HTCT
Heating demand sent as CT
-
0
0 to 100
C11
CLCT
Not used on this application
-
0
0 to 20
C12
SNDT
Not used on this application
-
0
0 to 1
C13
FPLS
Fixed plot scaling (do not change setting)
-
1
0 to 1

Monitoring Parameters, knobs and Switches

Doorway / InSite Code Label Description Units Default Value Range
I1 FRST Frost protection status - - 0 to 1
I2 OCC Channel occupancy status - - 0 to 1
I3 RLYA Relay A status (channel 1) - - 0 to 1
I4 RLYB Relay B status (channel 2) - - 0 to 1
I5 RLYC Relay C status (channel 3) - - 0 to 1
I6 RLYD Relay D status (channel 4) - - 0 to 1
I7 RLYE Relay E status (channel 5) - - 0 to 1
I8 RLYF Relay F status (channel 6) - - 0 to 1
W1 AUTO Automatic mode   - 0 to 1
W2 OVRD Override mode - - 0 to 1
W3 LCKB Not used on this application - - 0 to 1
W4 MMDE Not used on this application - - 0 to 1
W5 HAND Manual HAND mode - - 0 to 1
W7 SERV Generate service pin message - - 0 to 1
W8 CGST Configuration mode - - 0 to 1
S1 ROOM Room temperature sensor Deg C - 5 to 30
S2 DMND Control demand generated by the heating channel % - 0 to 100%
S3 REQD Current required temperature (setpoint) Deg C - 5 to 35
S4 HTOP Heating output % - 0 to 100%
S5 CLOP Cooling output (not used on this application) % - 0 to -100%
S7 OPST Last Optimum Start time Hrs -  
S8 OPOK Last Optimum Start completion Hrs -  
K1 SPOC Occupied setpoint Deg C 20 5 to 35
K2 SPNO Non occupied setpoint Deg C 10 5 to 35
K3 SPSV Supervised setpoint Deg C 0  
K4 MXOS Maximum optimum start (hours) Hrs - 0 to 1
K5 MXOF Maximum optimum off (hours) Hrs - 0 to 1
K6 OPTE Optimum start allowable error Deg C 0.5 0.2 to 5

 

 