6 Channel Underfloor Heating Controller
Configuration Tables
| Doorway / InSite Code | Label | Description | Units | Default Value | Range |
C1 |
CHNL |
Heating channel to be configured |
- |
- |
1 to 6 |
C2 |
SCAL |
Sensor calibration (used for calibrating the sensor input, if required) |
- |
0 |
-5 to 5 |
C3 |
SENN |
Current channel sensor number. A sensor input is associated with each heating channel (e.g. SENN=1 relates to temperature sensor on input A), but a temperature sensor can also be shared with other control channels |
- |
0 |
1 to 6 |
C4 |
PRD |
Current heating channel stroke/minimum ON time (e.g. PRD=6 is 60 sec). The heating channels are set for time proportioning control |
secs/10 |
6 |
1 to 240 |
C5 |
DLY |
Current channel interlock delay. Negative value= delay on operation, positive value=delay off operation |
- |
0 |
-60 to +60 |
C6 |
SPTY |
Setpoint type0: Heating channels use their own setpoint determined
on parameter K1 (SPOC) |
- |
0 |
0 to 1 |
C7 |
HTSC |
Heat source. The heat source parameter determines where the heat demand is sent to (e.g. boiler controller, VTC secondary circuit controller...etc) |
- |
- |
0 to 8255 |
C8 |
CLSC |
Not used on this application |
- |
0 |
0 to 8255 |
C9 |
OCDS |
Occupancy destination. This parameter can be used to send an occupancy demand link to another controller |
- |
0 |
0 to 8255 |
C10 |
HTCT |
Heating demand sent as CT |
- |
0 |
0 to 100 |
C11 |
CLCT |
Not used on this application |
- |
0 |
0 to 20 |
C12 |
SNDT |
Not used on this application |
- |
0 |
0 to 1 |
C13 |
FPLS |
Fixed plot scaling (do not change setting) |
- |
1 |
0 to 1 |
Monitoring Parameters, knobs and Switches
| Doorway / InSite Code | Label | Description | Units | Default Value | Range |
| I1 | FRST | Frost protection status | - | - | 0 to 1 |
| I2 | OCC | Channel occupancy status | - | - | 0 to 1 |
| I3 | RLYA | Relay A status (channel 1) | - | - | 0 to 1 |
| I4 | RLYB | Relay B status (channel 2) | - | - | 0 to 1 |
| I5 | RLYC | Relay C status (channel 3) | - | - | 0 to 1 |
| I6 | RLYD | Relay D status (channel 4) | - | - | 0 to 1 |
| I7 | RLYE | Relay E status (channel 5) | - | - | 0 to 1 |
| I8 | RLYF | Relay F status (channel 6) | - | - | 0 to 1 |
| W1 | AUTO | Automatic mode | - | 0 to 1 | |
| W2 | OVRD | Override mode | - | - | 0 to 1 |
| W3 | LCKB | Not used on this application | - | - | 0 to 1 |
| W4 | MMDE | Not used on this application | - | - | 0 to 1 |
| W5 | HAND | Manual HAND mode | - | - | 0 to 1 |
| W7 | SERV | Generate service pin message | - | - | 0 to 1 |
| W8 | CGST | Configuration mode | - | - | 0 to 1 |
| S1 | ROOM | Room temperature sensor | Deg C | - | 5 to 30 |
| S2 | DMND | Control demand generated by the heating channel | % | - | 0 to 100% |
| S3 | REQD | Current required temperature (setpoint) | Deg C | - | 5 to 35 |
| S4 | HTOP | Heating output | % | - | 0 to 100% |
| S5 | CLOP | Cooling output (not used on this application) | % | - | 0 to -100% |
| S7 | OPST | Last Optimum Start time | Hrs | - | |
| S8 | OPOK | Last Optimum Start completion | Hrs | - | |
| K1 | SPOC | Occupied setpoint | Deg C | 20 | 5 to 35 |
| K2 | SPNO | Non occupied setpoint | Deg C | 10 | 5 to 35 |
| K3 | SPSV | Supervised setpoint | Deg C | 0 | |
| K4 | MXOS | Maximum optimum start (hours) | Hrs | - | 0 to 1 |
| K5 | MXOF | Maximum optimum off (hours) | Hrs | - | 0 to 1 |
| K6 | OPTE | Optimum start allowable error | Deg C | 0.5 | 0.2 to 5 |